IST6-120 · Modular UPS

IST6-120, 1 × 30 kVA Modular UPS, 30 kVA modules

VRLA30 kVAmodular online UPS, 30 kVA modules

The IST6-120 with one 30 kVA power module is a 30 kVA / 30 kW modular online UPS: a 600 × 860 × 2000 mm cabinet with five slots, one of them used. For a site that needs 30 kW today and expects to grow to 120 kW without changing the UPS or the floor space.

30 kVA / 30 kWRating
600 × 860 × 2000 mmW × D × H
195 kg + 1 × 24 kg moduleWeight

Quick answers

IST6-120, 1 × 30 kVA: quick answers

What it is
The IST6-120 with one 30 kVA power module is a 30 kVA / 30 kW modular online UPS: a 600 × 860 × 2000 mm cabinet with five slots, one of them used.
Who it is for
For a site that needs 30 kW today and expects to grow to 120 kW without changing the UPS or the floor space.
Supply and configuration
3 ph + N + PE · 220 / 230 / 240 V L-N · 220 / 230 / 240 V L-N · 380 / 400 / 415 V L-L
Size and weight
600 × 860 × 2000 mm · 195 kg + 1 × 24 kg module
Ordering code
IST6-120 + 1 × IST6-30-J (2 × for N+1)

IST6-120

What sets apart the IST6-120, 1 × 30 kVA

This is the starting configuration of the IST6-120: the cabinet (code IST6-120, supplied without modules) with one IST6-30-J module of 30 kVA in 2U. For N+1 redundancy, a second module goes in: if one stops, the other carries the load without transfer to bypass. Three free slots remain for 60, 90 and 120 kVA, each module added online from the front.

With one module the charger gives up to 10 A, since charging current is 10 A per power module; a larger battery for long backup may call for a second module for the charge as well as for redundancy. The battery is a split string of ±14 to ±23 blocks of 12 V (default ±16); below ±16 blocks the output is limited to 80%.

Planning data

IST6-120, 1 × 30 kVA: currents, breakers, cables, batteries

The rows and columns of the EMEA 2026 catalogue's and AEC manuals' tables that concern the IST6-120, 1 × 30 kVA.

Power added one 30 kVA module at a time

IST6-120, 1 × 30 kVA · Power added one 30 kVA module at a time
Load up toModules (N)Modules for N+1
30 kVA12

Installation

Installing the IST6-120, 1 × 30 kVA: space, heat, cables

Each figure with its source. Heat is the power lost at the peak efficiency stated.

IST6-120, 1 × 30 kVA · installation
ItemFigureSource
Clearancesfront 800 mm, rear 800 mm, top 500 mm; left and right: not givenIST6 user manual Fig. 3-2 p.44
Cable entryBottom (standard); Top, with the top wiring accessory (cables up to 120 mm²)IST6 user manual Fig. 3-2 p.44
Heat at full load0.93 kW at 30 kW load, 97 % efficiencyEMEA 2026 catalogue p.109, 122; output PF 1 (EMEA 2026 catalogue)
Operating temperature−5 to 40 °CIST6 30–120 user manual
Switches and terminalsMains, SPD and output switches (796 mm up) and bypass and maintenance bypass (549 mm up) inside the front door.IST6 user manual Fig. 2-3 p.13, Fig. 3-2 p.44
DoorOne leaf, hinged on the rightIST6 user manual Fig. 2-3 p.13, Fig. 3-2 p.44
Module withdrawal700 mm in front of the cabinet to withdraw a moduleIST6 user manual Fig. 2-6 p.15; EMEA 2026 catalogue p.125–126

Size and floor

How big it is

600 × 860 × 2000 mm · 195 kg + 1 × 24 kg module.

0.52 m²footprint
424 kg/m²floor load
2 mheight

Floor load = weight ÷ footprint: cabinet and modules, 195 + 1 × 24 = 219 kg.

1.75 mFrontSide6008602000

Efficiency

How efficient is the AEC IST6-120, 1 × 30 kVA at your load?

IST6-120, 1 × 30 kVA, 30 kW at its rating, online, double conversion (typical curve, AEC's method). Heat to remove on this curve: 25%: 0.28 kW (η 96.4%) · 50%: 0.46 kW (η 97%) · 75%: 0.77 kW (η 96.7%) · 100%: 1.12 kW (η 96.4%). At 50% load, 24/7, it loses about 4,064 kWh a year.

97%50% · Typical curve, derived from the datasheet efficiency of 97% (AEC method)

How the curve is drawn and where each figure comes from: the IST6-120 range page.

Load
—
Lost as heat
—
Energy lost in a year, 24/7
—
Its cost in a year at € per kWh
—
The catalogue's examples use €0.20 per kWh.
Where each figure comes from
ModeEfficiencyKindModelsSource
Online, double conversion25%: 96.4% · 50%: 97% · 75%: 96.7% · 100%: 96.4%Typical curve, derived from the datasheet efficiency of 97% (AEC method)allAEC datasheet: AC/AC efficiency of the IST6-PM100 100 kW power module (the curve's shape)
ECO99%Datasheet figure, load not statedall

EMEA 2026 catalogue figures: Online, double conversion up to 97% · ECO up to 99%.

AEC IST6 120 kVA, rendered from its 3D modelDrag to turn

In 3D

Look around the IST6-120, 1 × 30 kVA

The turntable shows the IST6 120 kVA; the full 3D view opens on the IST6 30 kVA.

Technical data

Technical data IST6-120, 1 × 30 kVA

Only this model's values, from the EMEA 2026 catalogue table.

IST6-120, 1 × 30 kVA · Technical data
General
ModelIST6-120 with IST6-30-J power modules
Rated power30 to 120 kVA / kW in 30 kVA steps (1–4 modules) + 1 redundancy slot
Topologyonline double conversion, modular, hot-swap power modules, removable bypass module
Input
Connection · voltage3 ph + N + PE · 220 / 230 / 240 V L-N
Voltage range176–280 V full power · 80–176 V derated (linear load)
Frequency · power factor · THDi40–70 Hz · ≥ 0.99 · ≤ 2% resistive, ≤ 3% non-linear full load
Bypass220 / 230 / 240 V L-N; synchronisation 50 / 60 Hz ± 6 Hz
Battery
Voltage · blocks±168 … ±276 V DC · ±14 … ±23 × 12 V (default ±16; below ±16 load 80%)
Charging current10 A × number of modules (max.)
Functionscold start · standard / deep test · common battery · lithium with BMS card
Output
Connection · voltage3 ph + N + PE · 220 / 230 / 240 V L-N, 380 / 400 / 415 V L-L
Power factor · THDv1 · ≤ 1% linear, ≤ 4% non-linear
Frequency · phase errortracks the bypass; 50 / 60 Hz ± 0.2% without mains · ≤ 1° (balanced load)
Transfer · dynamic response0 ms synchronised, < 15 ms not synchronised · < 5% for 0↔100% step
Inverter overload (PF 1)≤ 105% continuous · 106–110% 60 min · 111–125% 10 min · 126–150% 1 min · > 151% to bypass
Bypass overload< 130% continuous · 131–150% 5 min · 151–200% 1 s · 201–300% 100 ms
Unbalanced load100%
System
Efficiency97% double conversion · up to 99% ECO
Display · records7" colour touch screen · 10,000 events · 5 LEDs · status light bar
CommunicationModbus · RS232 · RS485 · 4 dry-contact inputs, 3 outputs · options: SNMP, dry-contact expansion, BMS card
Parallelwith parallel kit, ring cables; BSC dual bus
Environment−5 … 40 °C · 0–95% RH · ≤ 2000 m · IP20 · < 65 dB · EMC class C3
Dimensions W × D × H600 × 860 × 2000 mm · cable entry bottom (top with accessory)
Weightcabinet without power modules 195 kg · power module 24 kg · bypass module 17 kg
IST6-120, 1 × 30 kVA · Models
ItemIST6-120, 1 × 30 kVA
Modules (N)1
Modules for N+12

Specifications are subject to change without notice.

More technical detailshow it works, ordering codes

Diagrams

How the power flows: AEC IST6-120, 1 × 30 kVA

Pick an operating mode: the path the power takes to the load lights up.

Power module × NMaintenance bypassMainsRectifierDC busBatteryInverterStatic switchLoadStatic bypassPower module × NMaintenance bypassMainsRectifierDC busBatteryInverterStatic switchLoadStatic bypass

Normal. Double conversion: the rectifier feeds the DC bus, the inverter rebuilds a clean voltage and the load always runs on the inverter. The battery stays on charge. Efficiency up to 97%.

Modules and redundancy

Move the slider: the modules the load needs light up, and the spare slot holds the N+1 redundancy. Each slot takes one 30 kVA module.

modules working · redundant · free slot

Ordering codes

Ordering codes IST6-120, 1 × 30 kVA

Ordering codes IST6-120, 1 × 30 kVA
CodeDescription
IST6-120Modular cabinet, max. 4 × 30 kVA power modules, supplied without modules
IST6-30-J30 kVA / 30 kW power module
PAR - IST6Parallel kit

Questions

Questions about the IST6-120, 1 × 30 kVA

Is one module enough for a 30 kVA load?

Yes: one IST6-30-J carries 30 kVA / 30 kW. For redundancy the catalogue's table gives two modules (N+1) for loads up to 30 kVA: a module can then stop or be replaced while the other keeps the load on the inverter.

How is power added later?

By sliding further 30 kVA modules into the free slots, numbered 1 to 5 from the bottom, with the load running. Modules are added and configured by AEC service; beyond 120 kVA, more cabinets join with the parallel kit PAR-IST6.

How big is the AEC IST6-120, 1 × 30 kVA and how much does it weigh?

The AEC IST6-120, 1 × 30 kVA measures 600 × 860 × 2000 mm; weight: 195 kg + 1 × 24 kg module (EMEA 2026 catalogue).