IST6-120 · Modular UPS
IST6-120, 3 × 30 kVA Modular UPS, 30 kVA modules
The IST6-120 with three 30 kVA power modules is a 90 kVA / 90 kW modular online UPS; with a fourth module it becomes 90 kVA N+1 in the same cabinet. For data rooms and public buildings of 60 to 90 kW that need redundancy without a second UPS.
Quick answers
IST6-120, 3 × 30 kVA: quick answers
- What it is
- The IST6-120 with three 30 kVA power modules is a 90 kVA / 90 kW modular online UPS; with a fourth module it becomes 90 kVA N+1 in the same cabinet.
- Who it is for
- For data rooms and public buildings of 60 to 90 kW that need redundancy without a second UPS.
- Supply and configuration
- 3 ph + N + PE · 220 / 230 / 240 V L-N · 220 / 230 / 240 V L-N · 380 / 400 / 415 V L-L
- Size and weight
- 600 × 860 × 2000 mm · 195 kg + 3 × 24 kg modules
- Ordering code
- IST6-120 + 3 × IST6-30-J (4 × for N+1)
IST6-120
What sets apart the IST6-120, 3 × 30 kVA
With three modules the charger reaches 30 A and the cabinet keeps one power slot plus the redundancy slot free. The usual way to run it is 90 kVA N+1 with four modules: redundancy inside one cabinet, on the same 600 × 860 mm footprint, where a monolithic design would need a second UPS of the same size.
The input accepts full power from 176 to 280 V phase voltage and keeps working from the mains down to 80 V with derated power; the efficiency is 97% in double conversion and up to 99% in ECO mode, with Timing ECO for scheduled operation.
Planning data
IST6-120, 3 × 30 kVA: currents, breakers, cables, batteries
The rows and columns of the EMEA 2026 catalogue's and AEC manuals' tables that concern the IST6-120, 3 × 30 kVA.
Power added one 30 kVA module at a time
| Load up to | Modules (N) | Modules for N+1 |
|---|---|---|
| 90 kVA | 3 | 4 |
Installation
Installing the IST6-120, 3 × 30 kVA: space, heat, cables
Each figure with its source. Heat is the power lost at the peak efficiency stated.
| Item | Figure | Source |
|---|---|---|
| Clearances | front 800 mm, rear 800 mm, top 500 mm; left and right: not given | IST6 user manual Fig. 3-2 p.44 |
| Cable entry | Bottom (standard); Top, with the top wiring accessory (cables up to 120 mm²) | IST6 user manual Fig. 3-2 p.44 |
| Heat at full load | 2.78 kW at 90 kW load, 97 % efficiency | EMEA 2026 catalogue p.109, 122; output PF 1 (EMEA 2026 catalogue) |
| Operating temperature | −5 to 40 °C | IST6 30–120 user manual |
| Switches and terminals | Mains, SPD and output switches (796 mm up) and bypass and maintenance bypass (549 mm up) inside the front door. | IST6 user manual Fig. 2-3 p.13, Fig. 3-2 p.44 |
| Door | One leaf, hinged on the right | IST6 user manual Fig. 2-3 p.13, Fig. 3-2 p.44 |
| Module withdrawal | 700 mm in front of the cabinet to withdraw a module | IST6 user manual Fig. 2-6 p.15; EMEA 2026 catalogue p.125–126 |
Size and floor
How big it is
600 × 860 × 2000 mm · 195 kg + 3 × 24 kg modules.
Floor load = weight ÷ footprint: cabinet and modules, 195 + 3 × 24 = 267 kg.
Efficiency
How efficient is the AEC IST6-120, 3 × 30 kVA at your load?
IST6-120, 3 × 30 kVA, 90 kW at its rating, online, double conversion (typical curve, AEC's method). Heat to remove on this curve: 25%: 0.84 kW (η 96.4%) · 50%: 1.39 kW (η 97%) · 75%: 2.30 kW (η 96.7%) · 100%: 3.36 kW (η 96.4%). At 50% load, 24/7, it loses about 12,192 kWh a year.
How the curve is drawn and where each figure comes from: the IST6-120 range page.
- Load
- —
- Lost as heat
- —
- Energy lost in a year, 24/7
- —
- Its cost in a year at € per kWh
- —
- The catalogue's examples use €0.20 per kWh.
Where each figure comes from
| Mode | Efficiency | Kind | Models | Source |
|---|---|---|---|---|
| Online, double conversion | 25%: 96.4% · 50%: 97% · 75%: 96.7% · 100%: 96.4% | Typical curve, derived from the datasheet efficiency of 97% (AEC method) | all | AEC datasheet: AC/AC efficiency of the IST6-PM100 100 kW power module (the curve's shape) |
| ECO | 99% | Datasheet figure, load not stated | all |
EMEA 2026 catalogue figures: Online, double conversion up to 97% · ECO up to 99%.
Drag to turnIn 3D
Look around the IST6-120, 3 × 30 kVA
The turntable shows the IST6 120 kVA; the full 3D view opens on the IST6 90 kVA.
Technical data
Technical data IST6-120, 3 × 30 kVA
Only this model's values, from the EMEA 2026 catalogue table.
| General | |
|---|---|
| Model | IST6-120 with IST6-30-J power modules |
| Rated power | 30 to 120 kVA / kW in 30 kVA steps (1–4 modules) + 1 redundancy slot |
| Topology | online double conversion, modular, hot-swap power modules, removable bypass module |
| Input | |
| Connection · voltage | 3 ph + N + PE · 220 / 230 / 240 V L-N |
| Voltage range | 176–280 V full power · 80–176 V derated (linear load) |
| Frequency · power factor · THDi | 40–70 Hz · ≥ 0.99 · ≤ 2% resistive, ≤ 3% non-linear full load |
| Bypass | 220 / 230 / 240 V L-N; synchronisation 50 / 60 Hz ± 6 Hz |
| Battery | |
| Voltage · blocks | ±168 … ±276 V DC · ±14 … ±23 × 12 V (default ±16; below ±16 load 80%) |
| Charging current | 10 A × number of modules (max.) |
| Functions | cold start · standard / deep test · common battery · lithium with BMS card |
| Output | |
| Connection · voltage | 3 ph + N + PE · 220 / 230 / 240 V L-N, 380 / 400 / 415 V L-L |
| Power factor · THDv | 1 · ≤ 1% linear, ≤ 4% non-linear |
| Frequency · phase error | tracks the bypass; 50 / 60 Hz ± 0.2% without mains · ≤ 1° (balanced load) |
| Transfer · dynamic response | 0 ms synchronised, < 15 ms not synchronised · < 5% for 0↔100% step |
| Inverter overload (PF 1) | ≤ 105% continuous · 106–110% 60 min · 111–125% 10 min · 126–150% 1 min · > 151% to bypass |
| Bypass overload | < 130% continuous · 131–150% 5 min · 151–200% 1 s · 201–300% 100 ms |
| Unbalanced load | 100% |
| System | |
| Efficiency | 97% double conversion · up to 99% ECO |
| Display · records | 7" colour touch screen · 10,000 events · 5 LEDs · status light bar |
| Communication | Modbus · RS232 · RS485 · 4 dry-contact inputs, 3 outputs · options: SNMP, dry-contact expansion, BMS card |
| Parallel | with parallel kit, ring cables; BSC dual bus |
| Environment | −5 … 40 °C · 0–95% RH · ≤ 2000 m · IP20 · < 65 dB · EMC class C3 |
| Dimensions W × D × H | 600 × 860 × 2000 mm · cable entry bottom (top with accessory) |
| Weight | cabinet without power modules 195 kg · power module 24 kg · bypass module 17 kg |
| Item | IST6-120, 3 × 30 kVA |
|---|---|
| Modules (N) | 3 |
| Modules for N+1 | 4 |
Specifications are subject to change without notice.
More technical detailshow it works, ordering codes
Diagrams
How the power flows: AEC IST6-120, 3 × 30 kVA
Pick an operating mode: the path the power takes to the load lights up.
Normal. Double conversion: the rectifier feeds the DC bus, the inverter rebuilds a clean voltage and the load always runs on the inverter. The battery stays on charge. Efficiency up to 97%.
Battery. The mains fails: the battery feeds the DC bus and the inverter carries on without a break. The load does not notice. Transfer: mains → battery with no break; inverter ↔ bypass 0 ms synchronised.
Bypass. Overload or internal fault: the static switch moves the load to the bypass line, fed by the mains.
ECO. The load runs on the bypass and the inverter stands ready: if the mains leaves the set window, the load goes back to the inverter. Higher efficiency, less protection. Efficiency up to 99%.
Maintenance. The maintenance bypass feeds the load straight from the mains, so the UPS can be isolated for service without switching the load off.
Modules and redundancy
Move the slider: the modules the load needs light up, and the spare slot holds the N+1 redundancy. Each slot takes one 30 kVA module.
modules working · redundant · free slot
Ordering codes
Ordering codes IST6-120, 3 × 30 kVA
| Code | Description |
|---|---|
| IST6-120 | Modular cabinet, max. 4 × 30 kVA power modules, supplied without modules |
| IST6-30-J | 30 kVA / 30 kW power module |
| PAR - IST6 | Parallel kit |
Questions
Questions about the IST6-120, 3 × 30 kVA
What is the best way to get 90 kVA N+1?
Four IST6-30-J modules in one IST6-120 cabinet: three carry the load, one is redundant. The catalogue's scalability table lists exactly this: 90 kVA, 3 modules, 4 for N+1.
What charging current does the IST6-120 give with three modules?
Up to 30 A: the charging current is 10 A per power module (maximum), 40 A with four. Lead-acid or lithium with the BMS expansion card.
How big is the AEC IST6-120, 3 × 30 kVA and how much does it weigh?
The AEC IST6-120, 3 × 30 kVA measures 600 × 860 × 2000 mm; weight: 195 kg + 3 × 24 kg modules (EMEA 2026 catalogue).
Talk to an AEC engineer
Tell us the load, the supply and the backup time you need for the AEC IST6-120, 3 × 30 kVA: we answer with the model and the batteries that fit. AEC International sells through distributors in about 80 countries and an agency in every Italian region: ask AEC which one serves your area.