IST6-120 · Modular UPS

IST6-120, 2 × 30 kVA Modular UPS, 30 kVA modules

VRLA60 kVAmodular online UPS, 30 kVA modules

The IST6-120 with two 30 kVA power modules is a 60 kVA / 60 kW modular online UPS in a 0.52 m² cabinet, with room for two more modules and a redundancy slot. For server rooms and telecom or banking sites of 30 to 60 kW that want hot-swap modules and room to grow.

60 kVA / 60 kWRating
600 × 860 × 2000 mmW × D × H
195 kg + 2 × 24 kg modulesWeight

Quick answers

IST6-120, 2 × 30 kVA: quick answers

What it is
The IST6-120 with two 30 kVA power modules is a 60 kVA / 60 kW modular online UPS in a 0.52 m² cabinet, with room for two more modules and a redundancy slot.
Who it is for
For server rooms and telecom or banking sites of 30 to 60 kW that want hot-swap modules and room to grow.
Supply and configuration
3 ph + N + PE · 220 / 230 / 240 V L-N · 220 / 230 / 240 V L-N · 380 / 400 / 415 V L-L
Size and weight
600 × 860 × 2000 mm · 195 kg + 2 × 24 kg modules
Ordering code
IST6-120 + 2 × IST6-30-J (3 × for N+1)

IST6-120

What sets apart the IST6-120, 2 × 30 kVA

Two modules share a 60 kVA load equally, under digital control with no master and no slave. Add a third for N+1: with 60 kVA of load and three modules, any one of them can fail or be pulled out for service and the load stays on the inverter. The charger gives up to 20 A with two modules.

At light load, the redundancy sleep function (Smart mode › Sleep redundancy) lets spare modules rest within a sleep safety load set on the screen, with an alarm if the load goes above it. The cabinet is the same as at 120 kVA, so cables and switchgear are sized once.

Planning data

IST6-120, 2 × 30 kVA: currents, breakers, cables, batteries

The rows and columns of the EMEA 2026 catalogue's and AEC manuals' tables that concern the IST6-120, 2 × 30 kVA.

Power added one 30 kVA module at a time

IST6-120, 2 × 30 kVA · Power added one 30 kVA module at a time
Load up toModules (N)Modules for N+1
60 kVA23

Installation

Installing the IST6-120, 2 × 30 kVA: space, heat, cables

Each figure with its source. Heat is the power lost at the peak efficiency stated.

IST6-120, 2 × 30 kVA · installation
ItemFigureSource
Clearancesfront 800 mm, rear 800 mm, top 500 mm; left and right: not givenIST6 user manual Fig. 3-2 p.44
Cable entryBottom (standard); Top, with the top wiring accessory (cables up to 120 mm²)IST6 user manual Fig. 3-2 p.44
Heat at full load1.86 kW at 60 kW load, 97 % efficiencyEMEA 2026 catalogue p.109, 122; output PF 1 (EMEA 2026 catalogue)
Operating temperature−5 to 40 °CIST6 30–120 user manual
Switches and terminalsMains, SPD and output switches (796 mm up) and bypass and maintenance bypass (549 mm up) inside the front door.IST6 user manual Fig. 2-3 p.13, Fig. 3-2 p.44
DoorOne leaf, hinged on the rightIST6 user manual Fig. 2-3 p.13, Fig. 3-2 p.44
Module withdrawal700 mm in front of the cabinet to withdraw a moduleIST6 user manual Fig. 2-6 p.15; EMEA 2026 catalogue p.125–126

Size and floor

How big it is

600 × 860 × 2000 mm · 195 kg + 2 × 24 kg modules.

0.52 m²footprint
471 kg/m²floor load
2 mheight

Floor load = weight ÷ footprint: cabinet and modules, 195 + 2 × 24 = 243 kg.

1.75 mFrontSide6008602000

Efficiency

How efficient is the AEC IST6-120, 2 × 30 kVA at your load?

IST6-120, 2 × 30 kVA, 60 kW at its rating, online, double conversion (typical curve, AEC's method). Heat to remove on this curve: 25%: 0.56 kW (η 96.4%) · 50%: 0.93 kW (η 97%) · 75%: 1.54 kW (η 96.7%) · 100%: 2.24 kW (η 96.4%). At 50% load, 24/7, it loses about 8,128 kWh a year.

97%50% · Typical curve, derived from the datasheet efficiency of 97% (AEC method)

How the curve is drawn and where each figure comes from: the IST6-120 range page.

Load
—
Lost as heat
—
Energy lost in a year, 24/7
—
Its cost in a year at € per kWh
—
The catalogue's examples use €0.20 per kWh.
Where each figure comes from
ModeEfficiencyKindModelsSource
Online, double conversion25%: 96.4% · 50%: 97% · 75%: 96.7% · 100%: 96.4%Typical curve, derived from the datasheet efficiency of 97% (AEC method)allAEC datasheet: AC/AC efficiency of the IST6-PM100 100 kW power module (the curve's shape)
ECO99%Datasheet figure, load not statedall

EMEA 2026 catalogue figures: Online, double conversion up to 97% · ECO up to 99%.

AEC IST6 120 kVA, rendered from its 3D modelDrag to turn

In 3D

Look around the IST6-120, 2 × 30 kVA

The turntable shows the IST6 120 kVA; the full 3D view opens on the IST6 60 kVA.

Technical data

Technical data IST6-120, 2 × 30 kVA

Only this model's values, from the EMEA 2026 catalogue table.

IST6-120, 2 × 30 kVA · Technical data
General
ModelIST6-120 with IST6-30-J power modules
Rated power30 to 120 kVA / kW in 30 kVA steps (1–4 modules) + 1 redundancy slot
Topologyonline double conversion, modular, hot-swap power modules, removable bypass module
Input
Connection · voltage3 ph + N + PE · 220 / 230 / 240 V L-N
Voltage range176–280 V full power · 80–176 V derated (linear load)
Frequency · power factor · THDi40–70 Hz · ≥ 0.99 · ≤ 2% resistive, ≤ 3% non-linear full load
Bypass220 / 230 / 240 V L-N; synchronisation 50 / 60 Hz ± 6 Hz
Battery
Voltage · blocks±168 … ±276 V DC · ±14 … ±23 × 12 V (default ±16; below ±16 load 80%)
Charging current10 A × number of modules (max.)
Functionscold start · standard / deep test · common battery · lithium with BMS card
Output
Connection · voltage3 ph + N + PE · 220 / 230 / 240 V L-N, 380 / 400 / 415 V L-L
Power factor · THDv1 · ≤ 1% linear, ≤ 4% non-linear
Frequency · phase errortracks the bypass; 50 / 60 Hz ± 0.2% without mains · ≤ 1° (balanced load)
Transfer · dynamic response0 ms synchronised, < 15 ms not synchronised · < 5% for 0↔100% step
Inverter overload (PF 1)≤ 105% continuous · 106–110% 60 min · 111–125% 10 min · 126–150% 1 min · > 151% to bypass
Bypass overload< 130% continuous · 131–150% 5 min · 151–200% 1 s · 201–300% 100 ms
Unbalanced load100%
System
Efficiency97% double conversion · up to 99% ECO
Display · records7" colour touch screen · 10,000 events · 5 LEDs · status light bar
CommunicationModbus · RS232 · RS485 · 4 dry-contact inputs, 3 outputs · options: SNMP, dry-contact expansion, BMS card
Parallelwith parallel kit, ring cables; BSC dual bus
Environment−5 … 40 °C · 0–95% RH · ≤ 2000 m · IP20 · < 65 dB · EMC class C3
Dimensions W × D × H600 × 860 × 2000 mm · cable entry bottom (top with accessory)
Weightcabinet without power modules 195 kg · power module 24 kg · bypass module 17 kg
IST6-120, 2 × 30 kVA · Models
ItemIST6-120, 2 × 30 kVA
Modules (N)2
Modules for N+13

Specifications are subject to change without notice.

More technical detailshow it works, ordering codes

Diagrams

How the power flows: AEC IST6-120, 2 × 30 kVA

Pick an operating mode: the path the power takes to the load lights up.

Power module × NMaintenance bypassMainsRectifierDC busBatteryInverterStatic switchLoadStatic bypassPower module × NMaintenance bypassMainsRectifierDC busBatteryInverterStatic switchLoadStatic bypass

Normal. Double conversion: the rectifier feeds the DC bus, the inverter rebuilds a clean voltage and the load always runs on the inverter. The battery stays on charge. Efficiency up to 97%.

Modules and redundancy

Move the slider: the modules the load needs light up, and the spare slot holds the N+1 redundancy. Each slot takes one 30 kVA module.

modules working · redundant · free slot

Ordering codes

Ordering codes IST6-120, 2 × 30 kVA

Ordering codes IST6-120, 2 × 30 kVA
CodeDescription
IST6-120Modular cabinet, max. 4 × 30 kVA power modules, supplied without modules
IST6-30-J30 kVA / 30 kW power module
PAR - IST6Parallel kit

Questions

Questions about the IST6-120, 2 × 30 kVA

How many modules for 60 kVA with redundancy?

Three: two carry the load (N = 2) and the third is the redundant one (N+1), as in the catalogue's table. Each module is 30 kVA / 30 kW, 2U and 24 kg.

Can a module be replaced with the load on?

Yes. Each module has a ready switch and RUN / ALARM / FAULT LEDs; a faulty module is isolated automatically and replaced online. Wait at least 10 minutes after removal before opening it; replacement by AEC or authorised personnel.

How big is the AEC IST6-120, 2 × 30 kVA and how much does it weigh?

The AEC IST6-120, 2 × 30 kVA measures 600 × 860 × 2000 mm; weight: 195 kg + 2 × 24 kg modules (EMEA 2026 catalogue).

Talk to an AEC engineer

Tell us the load, the supply and the backup time you need for the AEC IST6-120, 2 × 30 kVA: we answer with the model and the batteries that fit. AEC International sells through distributors in about 80 countries and an agency in every Italian region: ask AEC which one serves your area.