IST7-T · Three-phase UPS
IST7T-100 Three-phase transformer UPS 100 kVA
The IST7T-100 is a 100 kVA / 90 kW three-phase online UPS with built-in output isolation transformer, in a 1000 × 800 × 2000 mm cabinet of 720 kg. For hospitals, railways, mines and process sites with 70 to 90 kW of load that need an isolated, short-circuit-resistant output.

Quick answers
IST7T-100: quick answers
- What it is
- The IST7T-100 is a 100 kVA / 90 kW three-phase online UPS with built-in output isolation transformer, in a 1000 × 800 × 2000 mm cabinet of 720 kg.
- Who it is for
- For hospitals, railways, mines and process sites with 70 to 90 kW of load that need an isolated, short-circuit-resistant output.
- Supply and configuration
- 3Φ3W + PE, no neutral needed · 45–55 or 54–66 Hz · 380 / 400 / 415 V L-L · 220 / 230 / 240 V L-N
- Battery and backup
- 348–480 V DC
- Size and weight
- 1000 × 800 × 2000 mm · 720 kg
- Ordering code
- IST7T-100
IST7-T
What sets apart the IST7T-100
The IST7T-100 is the smallest IST7-T AEC offers: a 1000 mm cabinet of 720 kg. AC currents reach 180 A and the battery 278 A, on cables up to 2 × 150 mm²; the earth cable goes up to 2 × 150 mm² too. The battery defaults to 32 blocks (window 29–40). On the 100 and 120 kVA the communication module sits behind a blanking plate.
The cabinet has an altitude limit without derating of 1500 m, and noise below 70 dB. Hoisting uses the four lifting eyes on top, with the hook at least 1 m above the cabinet; the floor must be concrete or non-flammable and level.
- Against the IST7T-120 (one size up): Rated power 100 kVA / 90 kW against 120 kVA / 108 kW; AC input / output current 180 A against 216 A; Battery current 278 A against 333 A; Weight 720 kg against 780 kg.
Planning data
IST7T-100: currents, breakers, cables, batteries
The rows and columns of the EMEA 2026 catalogue's and AEC manuals' tables that concern the IST7T-100.
One cabinet, 1000 × 800 × 2000 mm
| kVA | 100 |
|---|---|
| AC in/out (A) | 180 |
| mm² max | 2 × 150 |
| Battery (A) | 278 |
| mm² max | 2 × 150 |
Size and floor
How big it is
1000 × 800 × 2000 mm · 720 kg.
Floor load = weight ÷ footprint (720 kg).
Efficiency
AEC IST7T-100 efficiency
The IST7-T pages of the EMEA 2026 catalogue give no efficiency figure.
Technical data
Technical data IST7T-100
Only this model's values, from the EMEA 2026 catalogue table.
| General | |
|---|---|
| Rated power (kVA / kW) | 100 / 90 |
| Rectifier input | |
| Technology | current-type IGBT rectifier, three-phase PFC · input EMI filter and input contactor |
| Rated voltage · range | 380 / 400 / 415 V L-L · ± 25% (full load from −20% to +25%; −25 … −20% current-limited) |
| Connection · frequency | 3Φ3W + PE, no neutral needed · 45–55 or 54–66 Hz |
| Power factor · THDi | ≥ 0.99 · < 5% |
| AC input / output current (A) | 180 |
| Bypass input | |
| Rated voltage · connection | 380 / 400 / 415 V L-L · 3Φ4W + PE · separate bypass input as standard (jumper for single input) |
| Synchronisation range | 50 Hz ± 10% (± 5% optional) |
| Static bypass | SCR static switch · manual maintenance bypass built in |
| Battery | |
| Battery converter | bidirectional buck / boost DC/DC on the DC bus · VRLA or lithium |
| Battery voltage (V DC) | 348–480 |
| Number of 12 V batteries | 29–40 (default 32) |
| Battery current (A) | 278 |
| Battery management | patented smart charging · equalise / float · temperature compensation · hibernation · standard, depth and constant-current tests · cell data with BMS |
| Energy functions | backfeed to grid during the battery test · energy-storage UPS with lithium (plan curve, 8 periods, or EMS over Modbus) |
| Output | |
| Voltage · power factor | 220 / 230 / 240 V L-N (380 / 400 / 415 V L-L) · 0.9 (kW / kVA) |
| Waveform · frequency | sine wave, THDv < 1% (linear load) · tracks the bypass in normal mode · 50 Hz ± 0.2% in battery mode |
| Isolation | Δ/Y output transformer built in, between inverter and inverter static switch |
| Transfer time | 0 ms mains → battery · 1 ms inverter → bypass |
| Overload (inverter mode) | 101–105% alarm, continuous · 106–130% 10 min · 131–155% 1 min · > 155% 1 s, then bypass |
| Unbalanced · non-linear load | 100% three-phase unbalanced · full kVA at 100% non-linear load |
| Operating modes | normal · battery · bypass · ECO (inverter in cold standby) · maintenance bypass · self-load test |
| Output connection | copper busbar |
| System | |
| Control · display | fully digital DSP · touch screen, power-on password, user and administrator levels · 10,000 events, user log |
| Communication | RS232 / RS485 Modbus RTU · 8 output and 4 input dry contacts (24 V DC / 1 A) · SNMP card, serial server TCP/IP optional |
| Parallel · systems | master-slave adaptive digital parallel, N+x warning, online exit and add · series hot standby · dual bus with LBS (optional) |
| Protections | battery undervoltage, overload, short circuit, over-temperature, input over- and undervoltage |
| Standards | CE · EN / IEC 62040-1 (safety) · EN / IEC 62040-2 (EMC), category C3 |
| Environment and mechanics | |
| Temperature · humidity | −5 … 40 °C operating · −20 … 55 °C storage · 0–95% RH non-condensing |
| Altitude without derating · noise | 1500 m · < 70 dB |
| Protection degree | IP20 (IP21 with optional top cover) |
| Dimensions (W × D × H) | 1000 × 800 × 2000 mm |
| Weight (kg ± 5%) | 720 |
| Item | IST7T-100 |
|---|---|
| kVA / kW | 100 / 90 |
| W × D × H (mm) | 1000 × 800 × 2000 |
| kg ± 5% | 720 |
Specifications are subject to change without notice.
More technical detailsordering codes
Ordering codes
Ordering codes IST7T-100
| Code | Description |
|---|---|
| IST7T-100 · -120 · -200 | IST7-T online UPS with output isolation transformer, 100 / 120 / 200 kVA, 1000 mm cabinet, external battery |
Catalogue
This range's pages of the catalogue.
Questions
Questions about the IST7T-100
How is a 720 kg IST7T-100 moved into place?
By electric or hand forklift, kept upright and balanced, or hoisted from the four lifting eyes on top with the hook at least 1 m above the cabinet. Leave at least 700 mm free at front and rear for heat and service.
What battery voltage does the IST7T-100 use?
348 to 480 V DC, 29 to 40 blocks of 12 V per string, 32 by default. With the optional battery logger (BMS link) the voltage, internal resistance and temperature of every cell appear on the UPS screen.
How big is the AEC IST7T-100 and how much does it weigh?
The AEC IST7T-100 measures 1000 × 800 × 2000 mm; weight: 720 kg (EMEA 2026 catalogue).
Talk to an AEC engineer
Tell us the load, the supply and the backup time you need for the AEC IST7T-100: we answer with the model and the batteries that fit. AEC International sells through distributors in about 80 countries and an agency in every Italian region: ask AEC which one serves your area.