IST7-T · Three-phase UPS

IST7T-120 Three-phase transformer UPS 120 kVA

VRLA120 kVAonline UPS with isolation transformer

The IST7T-120 is a 120 kVA / 108 kW three-phase online UPS with built-in output isolation transformer, 1000 mm wide and 780 kg. For industrial sites and medical buildings of 90 to 108 kW, alone, in parallel or in dual-bus systems.

120 kVA / 108 kWRating
1000 × 800 × 2000 mmW × D × H
780 kgWeight
348–480 V DCBattery
AEC IST7T-120 120 kVA, three-phase UPS

Quick answers

IST7T-120: quick answers

What it is
The IST7T-120 is a 120 kVA / 108 kW three-phase online UPS with built-in output isolation transformer, 1000 mm wide and 780 kg.
Who it is for
For industrial sites and medical buildings of 90 to 108 kW, alone, in parallel or in dual-bus systems.
Supply and configuration
3Φ3W + PE, no neutral needed · 45–55 or 54–66 Hz · 380 / 400 / 415 V L-L · 220 / 230 / 240 V L-N
Battery and backup
348–480 V DC
Size and weight
1000 × 800 × 2000 mm · 780 kg
Ordering code
IST7T-120

IST7-T

What sets apart the IST7T-120

The IST7T-120 adds 20 kVA to the 100 kVA in the same 1000 × 800 × 2000 mm cabinet for 60 kg more (780 kg). It draws 216 A AC and 333 A from the battery, within the 2 × 150 mm² cable maximums of the cabinet.

For loads with two power inputs, two systems A and B (single units or parallel systems, two or four UPS) can be phase- and frequency-synchronised through the optional LBS interface, and a common battery pack can serve a parallel system.

  • Against the IST7T-100 (one size down): Rated power 120 kVA / 108 kW against 100 kVA / 90 kW; AC input / output current 216 A against 180 A; Battery current 333 A against 278 A; Weight 780 kg against 720 kg.
  • Against the IST7T-200 (one size up): Rated power 120 kVA / 108 kW against 200 kVA / 180 kW; AC input / output current 216 A against 355 A; Battery current 333 A against 499 A; Weight 780 kg against 1280 kg.

Planning data

IST7T-120: currents, breakers, cables, batteries

The rows and columns of the EMEA 2026 catalogue's and AEC manuals' tables that concern the IST7T-120.

One cabinet, 1000 × 800 × 2000 mm

IST7T-120 · One cabinet, 1000 × 800 × 2000 mm
kVA120
AC in/out (A)216
mm² max2 × 150
Battery (A)333
mm² max2 × 150

Size and floor

How big it is

1000 × 800 × 2000 mm · 780 kg.

0.8 m²footprint
975 kg/m²floor load
2 mheight

Floor load = weight ÷ footprint (780 kg).

1.75 mFrontSide10008002000

Efficiency

AEC IST7T-120 efficiency

The IST7-T pages of the EMEA 2026 catalogue give no efficiency figure.

Technical data

Technical data IST7T-120

Only this model's values, from the EMEA 2026 catalogue table.

IST7T-120 · Technical data
General
Rated power (kVA / kW)120 / 108
Rectifier input
Technologycurrent-type IGBT rectifier, three-phase PFC · input EMI filter and input contactor
Rated voltage · range380 / 400 / 415 V L-L · ± 25% (full load from −20% to +25%; −25 … −20% current-limited)
Connection · frequency3Φ3W + PE, no neutral needed · 45–55 or 54–66 Hz
Power factor · THDi≥ 0.99 · < 5%
AC input / output current (A)216
Bypass input
Rated voltage · connection380 / 400 / 415 V L-L · 3Φ4W + PE · separate bypass input as standard (jumper for single input)
Synchronisation range50 Hz ± 10% (± 5% optional)
Static bypassSCR static switch · manual maintenance bypass built in
Battery
Battery converterbidirectional buck / boost DC/DC on the DC bus · VRLA or lithium
Battery voltage (V DC)348–480
Number of 12 V batteries29–40 (default 32)
Battery current (A)333
Battery managementpatented smart charging · equalise / float · temperature compensation · hibernation · standard, depth and constant-current tests · cell data with BMS
Energy functionsbackfeed to grid during the battery test · energy-storage UPS with lithium (plan curve, 8 periods, or EMS over Modbus)
Output
Voltage · power factor220 / 230 / 240 V L-N (380 / 400 / 415 V L-L) · 0.9 (kW / kVA)
Waveform · frequencysine wave, THDv < 1% (linear load) · tracks the bypass in normal mode · 50 Hz ± 0.2% in battery mode
IsolationΔ/Y output transformer built in, between inverter and inverter static switch
Transfer time0 ms mains → battery · 1 ms inverter → bypass
Overload (inverter mode)101–105% alarm, continuous · 106–130% 10 min · 131–155% 1 min · > 155% 1 s, then bypass
Unbalanced · non-linear load100% three-phase unbalanced · full kVA at 100% non-linear load
Operating modesnormal · battery · bypass · ECO (inverter in cold standby) · maintenance bypass · self-load test
Output connectioncopper busbar
System
Control · displayfully digital DSP · touch screen, power-on password, user and administrator levels · 10,000 events, user log
CommunicationRS232 / RS485 Modbus RTU · 8 output and 4 input dry contacts (24 V DC / 1 A) · SNMP card, serial server TCP/IP optional
Parallel · systemsmaster-slave adaptive digital parallel, N+x warning, online exit and add · series hot standby · dual bus with LBS (optional)
Protectionsbattery undervoltage, overload, short circuit, over-temperature, input over- and undervoltage
StandardsCE · EN / IEC 62040-1 (safety) · EN / IEC 62040-2 (EMC), category C3
Environment and mechanics
Temperature · humidity−5 … 40 °C operating · −20 … 55 °C storage · 0–95% RH non-condensing
Altitude without derating · noise1500 m · < 70 dB
Protection degreeIP20 (IP21 with optional top cover)
Dimensions (W × D × H)1000 × 800 × 2000 mm
Weight (kg ± 5%)780
IST7T-120 · Models
ItemIST7T-120
kVA / kW120 / 108
W × D × H (mm)1000 × 800 × 2000
kg ± 5%780

Specifications are subject to change without notice.

More technical detailsordering codes

Ordering codes

Ordering codes IST7T-120

Ordering codes IST7T-120
CodeDescription
IST7T-100 · -120 · -200IST7-T online UPS with output isolation transformer, 100 / 120 / 200 kVA, 1000 mm cabinet, external battery

Questions

Questions about the IST7T-120

Can two IST7T-120 feed a dual-bus system?

Yes. With the optional LBS interface two independent systems A and B are kept in phase and frequency, so dual-corded loads can be fed from both. Each side can be a single unit or a parallel system.

What currents does the IST7T-120 draw?

216 A on the AC input and output and 333 A on the battery, with cables up to 2 × 150 mm² in the catalogue table. A bipolar disconnect switch is required on the external DC circuit.

How big is the AEC IST7T-120 and how much does it weigh?

The AEC IST7T-120 measures 1000 × 800 × 2000 mm; weight: 780 kg (EMEA 2026 catalogue).