IST7-T · Three-phase UPS

IST7T-200 Three-phase transformer UPS 200 kVA

VRLA200 kVAonline UPS with isolation transformer

The IST7T-200 is a 200 kVA / 180 kW three-phase online UPS with built-in output isolation transformer, the largest IST7-T, at 1280 kg. For heavy industry, mining, railways and large medical sites with 120 to 180 kW of load that must be isolated from the grid.

200 kVA / 180 kWRating
1000 × 800 × 2000 mmW × D × H
1280 kgWeight
348–480 V DCBattery
AEC IST7T-200 200 kVA, three-phase UPS

Quick answers

IST7T-200: quick answers

What it is
The IST7T-200 is a 200 kVA / 180 kW three-phase online UPS with built-in output isolation transformer, the largest IST7-T, at 1280 kg.
Who it is for
For heavy industry, mining, railways and large medical sites with 120 to 180 kW of load that must be isolated from the grid.
Supply and configuration
3Φ3W + PE, no neutral needed · 45–55 or 54–66 Hz · 380 / 400 / 415 V L-L · 220 / 230 / 240 V L-N
Battery and backup
348–480 V DC
Size and weight
1000 × 800 × 2000 mm · 1280 kg
Ordering code
IST7T-200

IST7-T

What sets apart the IST7T-200

The IST7T-200 keeps the 1000 × 800 × 2000 mm cabinet of the 100–120 kVA but weighs 1280 kg ± 5%, 500 kg more than the 120 kVA. AC currents reach 355 A and the battery 499 A, the highest of the range, on cables up to 2 × 150 mm²; output on copper busbar.

Matched to the inverter, the built-in transformer removes the excitation inrush that an external transformer of this size would cause at start-up. The UPS keeps 10,000 events, watches its capacitors' health and offers a self-load test, so commissioning can be done before the real load is connected.

  • Against the IST7T-120 (one size down): Rated power 200 kVA / 180 kW against 120 kVA / 108 kW; AC input / output current 355 A against 216 A; Battery current 499 A against 333 A; Weight 1280 kg against 780 kg.

Planning data

IST7T-200: currents, breakers, cables, batteries

The rows and columns of the EMEA 2026 catalogue's and AEC manuals' tables that concern the IST7T-200.

One cabinet, 1000 × 800 × 2000 mm

IST7T-200 · One cabinet, 1000 × 800 × 2000 mm
kVA200
AC in/out (A)355
mm² max2 × 150
Battery (A)499
mm² max2 × 150

Size and floor

How big it is

1000 × 800 × 2000 mm · 1280 kg.

0.8 m²footprint
1,600 kg/m²floor load
2 mheight

Floor load = weight ÷ footprint (1,280 kg).

1.75 mFrontSide10008002000

Efficiency

AEC IST7T-200 efficiency

The IST7-T pages of the EMEA 2026 catalogue give no efficiency figure.

Technical data

Technical data IST7T-200

Only this model's values, from the EMEA 2026 catalogue table.

IST7T-200 · Technical data
General
Rated power (kVA / kW)200 / 180
Rectifier input
Technologycurrent-type IGBT rectifier, three-phase PFC · input EMI filter and input contactor
Rated voltage · range380 / 400 / 415 V L-L · ± 25% (full load from −20% to +25%; −25 … −20% current-limited)
Connection · frequency3Φ3W + PE, no neutral needed · 45–55 or 54–66 Hz
Power factor · THDi≥ 0.99 · < 5%
AC input / output current (A)355
Bypass input
Rated voltage · connection380 / 400 / 415 V L-L · 3Φ4W + PE · separate bypass input as standard (jumper for single input)
Synchronisation range50 Hz ± 10% (± 5% optional)
Static bypassSCR static switch · manual maintenance bypass built in
Battery
Battery converterbidirectional buck / boost DC/DC on the DC bus · VRLA or lithium
Battery voltage (V DC)348–480
Number of 12 V batteries29–40 (default 32)
Battery current (A)499
Battery managementpatented smart charging · equalise / float · temperature compensation · hibernation · standard, depth and constant-current tests · cell data with BMS
Energy functionsbackfeed to grid during the battery test · energy-storage UPS with lithium (plan curve, 8 periods, or EMS over Modbus)
Output
Voltage · power factor220 / 230 / 240 V L-N (380 / 400 / 415 V L-L) · 0.9 (kW / kVA)
Waveform · frequencysine wave, THDv < 1% (linear load) · tracks the bypass in normal mode · 50 Hz ± 0.2% in battery mode
IsolationΔ/Y output transformer built in, between inverter and inverter static switch
Transfer time0 ms mains → battery · 1 ms inverter → bypass
Overload (inverter mode)101–105% alarm, continuous · 106–130% 10 min · 131–155% 1 min · > 155% 1 s, then bypass
Unbalanced · non-linear load100% three-phase unbalanced · full kVA at 100% non-linear load
Operating modesnormal · battery · bypass · ECO (inverter in cold standby) · maintenance bypass · self-load test
Output connectioncopper busbar
System
Control · displayfully digital DSP · touch screen, power-on password, user and administrator levels · 10,000 events, user log
CommunicationRS232 / RS485 Modbus RTU · 8 output and 4 input dry contacts (24 V DC / 1 A) · SNMP card, serial server TCP/IP optional
Parallel · systemsmaster-slave adaptive digital parallel, N+x warning, online exit and add · series hot standby · dual bus with LBS (optional)
Protectionsbattery undervoltage, overload, short circuit, over-temperature, input over- and undervoltage
StandardsCE · EN / IEC 62040-1 (safety) · EN / IEC 62040-2 (EMC), category C3
Environment and mechanics
Temperature · humidity−5 … 40 °C operating · −20 … 55 °C storage · 0–95% RH non-condensing
Altitude without derating · noise1500 m · < 70 dB
Protection degreeIP20 (IP21 with optional top cover)
Dimensions (W × D × H)1000 × 800 × 2000 mm
Weight (kg ± 5%)1280
IST7T-200 · Models
ItemIST7T-200
kVA / kW200 / 180
W × D × H (mm)1000 × 800 × 2000
kg ± 5%1280

Specifications are subject to change without notice.

More technical detailsordering codes

Ordering codes

Ordering codes IST7T-200

Ordering codes IST7T-200
CodeDescription
IST7T-100 · -120 · -200IST7-T online UPS with output isolation transformer, 100 / 120 / 200 kVA, 1000 mm cabinet, external battery

Questions

Questions about the IST7T-200

Why not a transformerless UPS plus an external transformer at 200 kVA?

The IST7T-200's transformer is matched to the inverter: no external unit to size and install, and no excitation inrush on the inverter at start-up. It also gives full kVA at 100% non-linear load and 100% unbalanced load.

What floor and space does the IST7T-200 need?

A concrete or non-flammable level floor for 1280 kg on 0.8 m², at least 700 mm free at front and rear, and front and rear vents kept clear. Units can be combined in a row.

How big is the AEC IST7T-200 and how much does it weigh?

The AEC IST7T-200 measures 1000 × 800 × 2000 mm; weight: 1280 kg (EMEA 2026 catalogue).

Talk to an AEC engineer

Tell us the load, the supply and the backup time you need for the AEC IST7T-200: we answer with the model and the batteries that fit. AEC International sells through distributors in about 80 countries and an agency in every Italian region: ask AEC which one serves your area.