OZ Power VRLA · Batteries and cabinets
OZ Power 12 V 200 Ah AGM VRLA battery for UPS
The OZ Power 12 V 200 Ah is the largest long-life AGM VRLA block of the range: 522 × 240 × 219 mm, 58.0 kg, supplied for large systems on request. For long backup on large UPS, where a few hours are needed and the battery is installed on racks or in a battery room.

Quick answers
OZ Power 12 V 200 Ah: quick answers
- What it is
- The OZ Power 12 V 200 Ah is the largest long-life AGM VRLA block of the range: 522 × 240 × 219 mm, 58.0 kg, supplied for large systems on request.
- Who it is for
- For long backup on large UPS, where a few hours are needed and the battery is installed on racks or in a battery room.
- Supply and configuration
- 12 V
- Battery and backup
- 200 · 212 Ah
- Size and weight
- 522 × 240 × 219 mm · 58.0 kg
- Ordering code
- OZ-12200 (OZ Power 12 V 200 Ah)
OZ Power VRLA
What sets apart the OZ Power 12 V 200 Ah
The 200 Ah delivers 3217 W per block for 15 minutes and 1263 W for 1 hour at 1.75 V per cell; in the catalogue's 15 kW / 32-block example it lasts about 3.8 hours. It is not listed in the BB cabinets: the catalogue gives it for large systems, on request.
Its ratings are 200 Ah at 10 hours and 212 Ah at 20 hours, ≤ 3.5 mΩ internal resistance, up to 60.0 A of charge and 2000 A for 5 s; terminal F10 (M8). At 58 kg per block, handling and shelving need planning.
- Against the OZ Power 12 V 100 Ah (one size down): Capacity C10 · C20 200 · 212 Ah against 100 · 106 Ah; Capacity C3 · C5 150 · 170 Ah against 75.0 · 85.0 Ah; L × W × H 522 × 240 × 219 mm against 328 × 172 × 215 mm; Total height 224 mm against 220 mm; Weight (approx.) 58.0 kg against 28.5 kg.
Planning data
OZ Power 12 V 200 Ah: currents, breakers, cables, batteries
The rows and columns of the EMEA 2026 catalogue's and AEC manuals' tables that concern the OZ Power 12 V 200 Ah.
Power when it matters
| W per 12 V block, 1.75 V/cell | 200 Ah |
|---|---|
| 15 min | 3217 |
| 30 min | 2137 |
| 60 min | 1263 |
From load to backup time
| Battery | Backup time, 15 kW on 32 blocks |
|---|---|
| 12 V 200 Ah | ≈ 3.8 h |
Size and floor
How big it is
522 × 240 × 219 mm · 58.0 kg.
Technical data
Technical data OZ Power 12 V 200 Ah
Only this model's values, from the EMEA 2026 catalogue table.
| OZ Power 12 V | |
|---|---|
| Capacity C10 · C20 | 200 · 212 Ah |
| Capacity C3 · C5 | 150 · 170 Ah |
| L × W × H (mm) | 522 × 240 × 219 |
| Total height (mm) | 224 |
| Weight (approx.) | 58.0 kg |
| Internal resistance | ≤ 3.5 mΩ |
| Terminal | F10 (M8) |
| Max. discharge (5 s) | 2000 A |
| Short-circuit current | 3430 A |
| Max. charge current | 60.0 A |
| Design life (float) | 12 years |
| Used in | on request |
Values at 25 °C, fully charged, from the battery data sheets; C3–C20 = capacity at 3, 5, 10 and 20 h discharge (C3, C5 and C10 to 1.80 V/cell, C20 to 1.75 V/cell). Weight tolerance ± 5%. Terminal: default type, others optional. Specifications are subject to change without notice.
More technical detailsrange tables, ordering codes
Planning data
OZ Power VRLA range tables
12 V 200 Ah · constant power, W per 12 V block, 25 °C
AGM VRLA battery · design life 12 years in float · used in large systems, on request.
| End V/cell · V/block | 10 min | 15 min | 30 min | 1 h | 2 h | 3 h | 4 h | 5 h | 8 h | 10 h | 20 h |
|---|---|---|---|---|---|---|---|---|---|---|---|
| 1.60 V · 9.6 V | 4,481 | 3,695 | 2,363 | 1,378 | 828 | 646 | 511 | 436 | 297 | 249 | 130 |
| 1.65 V · 9.9 V | 4,316 | 3,585 | 2,293 | 1,338 | 805 | 629 | 499 | 427 | 295 | 246 | 128 |
| 1.70 V · 10.2 V | 4,046 | 3,408 | 2,213 | 1,303 | 783 | 615 | 487 | 417 | 290 | 243 | 127 |
| 1.75 V · 10.5 V | 3,770 | 3,217 | 2,137 | 1,263 | 759 | 599 | 476 | 408 | 287 | 240 | 126 |
| 1.80 V · 10.8 V | 3,472 | 3,013 | 2,063 | 1,222 | 736 | 583 | 464 | 399 | 283 | 237 | 125 |
| 1.85 V · 11.1 V | 2,888 | 2,536 | 1,795 | 1,102 | 678 | 541 | 433 | 373 | 266 | 224 | 118 |
12 V 200 Ah · constant current, A, 25 °C
Constant current discharge of the 12 V 200 Ah block, by end voltage and discharge time.
| End V/cell · V/block | 10 min | 15 min | 30 min | 1 h | 2 h | 3 h | 4 h | 5 h | 8 h | 10 h | 20 h |
|---|---|---|---|---|---|---|---|---|---|---|---|
| 1.60 V · 9.6 V | 439 | 352 | 217 | 122 | 72.8 | 56.4 | 44.3 | 37.7 | 25.4 | 21.1 | 11.0 |
| 1.65 V · 9.9 V | 415 | 337 | 208 | 118 | 70.5 | 54.7 | 43.1 | 36.8 | 25.1 | 20.8 | 10.9 |
| 1.70 V · 10.2 V | 382 | 315 | 199 | 114 | 68.2 | 53.2 | 42.0 | 35.8 | 24.7 | 20.5 | 10.7 |
| 1.75 V · 10.5 V | 350 | 294 | 190 | 110 | 65.8 | 51.6 | 40.9 | 34.9 | 24.3 | 20.3 | 10.6 |
| 1.80 V · 10.8 V | 317 | 271 | 182 | 106 | 63.4 | 50.0 | 39.7 | 34.0 | 23.9 | 20.0 | 10.5 |
| 1.85 V · 11.1 V | 259 | 225 | 156 | 94.9 | 58.1 | 46.2 | 36.9 | 31.7 | 22.5 | 18.8 | 10.0 |
Ordering codes
Ordering codes OZ Power 12 V 200 Ah
| Code | Description |
|---|---|
| OZ-1209 · OZ-1224 · OZ-1240 · OZ-1260 · OZ-1280 · OZ-12100 · OZ-12200 | OZ Power 12 V AGM VRLA blocks: 9 · 24 · 40 · 60 · 80 · 100 · 200 Ah |
Catalogue
This range's pages of the catalogue.
Questions
Questions about the OZ Power 12 V 200 Ah
How long does a 32-block string of 200 Ah last at 15 kW?
About 3.8 hours in the catalogue's example (95% efficiency assumed, 25 °C, 1.75 V/cell, new batteries). Real backup depends on the UPS, the temperature and battery age.
Is the 200 Ah safe to transport?
Yes: OZ Power AGM blocks are classed as non-dangerous goods for road, rail and air transport: the electrolyte is fully absorbed in the glass mat, with no free acid.
How big is the AEC OZ Power 12 V 200 Ah and how much does it weigh?
The AEC OZ Power 12 V 200 Ah measures 522 × 240 × 219 mm; weight: 58.0 kg (EMEA 2026 catalogue).
Talk to an AEC engineer
Tell us the load, the supply and the backup time you need for the AEC OZ Power 12 V 200 Ah: we answer with the model and the batteries that fit. AEC International sells through distributors in about 80 countries and an agency in every Italian region: ask AEC which one serves your area.