OZ Power VRLA · Batteries and cabinets

OZ Power 12 V 200 Ah AGM VRLA battery for UPS

VRLA200 Ah12 V AGM VRLA battery

The OZ Power 12 V 200 Ah is the largest long-life AGM VRLA block of the range: 522 × 240 × 219 mm, 58.0 kg, supplied for large systems on request. For long backup on large UPS, where a few hours are needed and the battery is installed on racks or in a battery room.

522 × 240 × 219 mmW × D × H
58.0 kgWeight
200 · 212 AhBattery
AEC OZ Power 12 V 200 Ah

Quick answers

OZ Power 12 V 200 Ah: quick answers

What it is
The OZ Power 12 V 200 Ah is the largest long-life AGM VRLA block of the range: 522 × 240 × 219 mm, 58.0 kg, supplied for large systems on request.
Who it is for
For long backup on large UPS, where a few hours are needed and the battery is installed on racks or in a battery room.
Supply and configuration
12 V
Battery and backup
200 · 212 Ah
Size and weight
522 × 240 × 219 mm · 58.0 kg
Ordering code
OZ-12200 (OZ Power 12 V 200 Ah)

OZ Power VRLA

What sets apart the OZ Power 12 V 200 Ah

The 200 Ah delivers 3217 W per block for 15 minutes and 1263 W for 1 hour at 1.75 V per cell; in the catalogue's 15 kW / 32-block example it lasts about 3.8 hours. It is not listed in the BB cabinets: the catalogue gives it for large systems, on request.

Its ratings are 200 Ah at 10 hours and 212 Ah at 20 hours, ≤ 3.5 mΩ internal resistance, up to 60.0 A of charge and 2000 A for 5 s; terminal F10 (M8). At 58 kg per block, handling and shelving need planning.

  • Against the OZ Power 12 V 100 Ah (one size down): Capacity C10 · C20 200 · 212 Ah against 100 · 106 Ah; Capacity C3 · C5 150 · 170 Ah against 75.0 · 85.0 Ah; L × W × H 522 × 240 × 219 mm against 328 × 172 × 215 mm; Total height 224 mm against 220 mm; Weight (approx.) 58.0 kg against 28.5 kg.

Planning data

OZ Power 12 V 200 Ah: currents, breakers, cables, batteries

The rows and columns of the EMEA 2026 catalogue's and AEC manuals' tables that concern the OZ Power 12 V 200 Ah.

Power when it matters

OZ Power 12 V 200 Ah · Power when it matters
W per 12 V block, 1.75 V/cell200 Ah
15 min3217
30 min2137
60 min1263

From load to backup time

OZ Power 12 V 200 Ah · From load to backup time
BatteryBackup time, 15 kW on 32 blocks
12 V 200 Ah≈ 3.8 h

Size and floor

How big it is

522 × 240 × 219 mm · 58.0 kg.

0.13 m²footprint
0.22 mheight

1.75 mFrontSide522240219

Technical data

Technical data OZ Power 12 V 200 Ah

Only this model's values, from the EMEA 2026 catalogue table.

OZ Power 12 V 200 Ah · Technical data
OZ Power 12 V
Capacity C10 · C20200 · 212 Ah
Capacity C3 · C5150 · 170 Ah
L × W × H (mm)522 × 240 × 219
Total height (mm)224
Weight (approx.)58.0 kg
Internal resistance≤ 3.5 mΩ
TerminalF10 (M8)
Max. discharge (5 s)2000 A
Short-circuit current3430 A
Max. charge current60.0 A
Design life (float)12 years
Used inon request

Values at 25 °C, fully charged, from the battery data sheets; C3–C20 = capacity at 3, 5, 10 and 20 h discharge (C3, C5 and C10 to 1.80 V/cell, C20 to 1.75 V/cell). Weight tolerance ± 5%. Terminal: default type, others optional. Specifications are subject to change without notice.

More technical detailsrange tables, ordering codes

Planning data

OZ Power VRLA range tables

12 V 200 Ah · constant power, W per 12 V block, 25 °C

AGM VRLA battery · design life 12 years in float · used in large systems, on request.

OZ Power 12 V 200 Ah · constant power, W per 12 V block, 25 °C
End V/cell · V/block10 min15 min30 min1 h2 h3 h4 h5 h8 h10 h20 h
1.60 V · 9.6 V4,4813,6952,3631,378828646511436297249130
1.65 V · 9.9 V4,3163,5852,2931,338805629499427295246128
1.70 V · 10.2 V4,0463,4082,2131,303783615487417290243127
1.75 V · 10.5 V3,7703,2172,1371,263759599476408287240126
1.80 V · 10.8 V3,4723,0132,0631,222736583464399283237125
1.85 V · 11.1 V2,8882,5361,7951,102678541433373266224118

12 V 200 Ah · constant current, A, 25 °C

Constant current discharge of the 12 V 200 Ah block, by end voltage and discharge time.

OZ Power 12 V 200 Ah · constant current, A, 25 °C
End V/cell · V/block10 min15 min30 min1 h2 h3 h4 h5 h8 h10 h20 h
1.60 V · 9.6 V43935221712272.856.444.337.725.421.111.0
1.65 V · 9.9 V41533720811870.554.743.136.825.120.810.9
1.70 V · 10.2 V38231519911468.253.242.035.824.720.510.7
1.75 V · 10.5 V35029419011065.851.640.934.924.320.310.6
1.80 V · 10.8 V31727118210663.450.039.734.023.920.010.5
1.85 V · 11.1 V25922515694.958.146.236.931.722.518.810.0

Ordering codes

Ordering codes OZ Power 12 V 200 Ah

Ordering codes OZ Power 12 V 200 Ah
CodeDescription
OZ-1209 · OZ-1224 · OZ-1240 · OZ-1260 · OZ-1280 · OZ-12100 · OZ-12200OZ Power 12 V AGM VRLA blocks: 9 · 24 · 40 · 60 · 80 · 100 · 200 Ah

Questions

Questions about the OZ Power 12 V 200 Ah

How long does a 32-block string of 200 Ah last at 15 kW?

About 3.8 hours in the catalogue's example (95% efficiency assumed, 25 °C, 1.75 V/cell, new batteries). Real backup depends on the UPS, the temperature and battery age.

Is the 200 Ah safe to transport?

Yes: OZ Power AGM blocks are classed as non-dangerous goods for road, rail and air transport: the electrolyte is fully absorbed in the glass mat, with no free acid.

How big is the AEC OZ Power 12 V 200 Ah and how much does it weigh?

The AEC OZ Power 12 V 200 Ah measures 522 × 240 × 219 mm; weight: 58.0 kg (EMEA 2026 catalogue).

Talk to an AEC engineer

Tell us the load, the supply and the backup time you need for the AEC OZ Power 12 V 200 Ah: we answer with the model and the batteries that fit. AEC International sells through distributors in about 80 countries and an agency in every Italian region: ask AEC which one serves your area.