OZ Power VRLA · Batteries and cabinets

OZ Power 12 V 60 Ah AGM VRLA battery for UPS

VRLA60 Ah12 V AGM VRLA battery

The OZ Power 12 V 60 Ah is a long-life sealed AGM VRLA block, 230 × 138 × 211 mm and 16.5 kg, used in the BB6 and BB7 cabinets. For IST7 UPS of 10 to 120 kVA that need roughly half an hour or more from one cabinet.

230 × 138 × 211 mmW × D × H
16.5 kgWeight
55.0 · 58.2 AhBattery
AEC OZ Power VRLA range

Range picture: AEC OZ Power VRLA.

Quick answers

OZ Power 12 V 60 Ah: quick answers

What it is
The OZ Power 12 V 60 Ah is a long-life sealed AGM VRLA block, 230 × 138 × 211 mm and 16.5 kg, used in the BB6 and BB7 cabinets.
Who it is for
For IST7 UPS of 10 to 120 kVA that need roughly half an hour or more from one cabinet.
Supply and configuration
12 V
Battery and backup
55.0 · 58.2 Ah
Size and weight
230 × 138 × 211 mm · 16.5 kg
Ordering code
OZ-1260 (OZ Power 12 V 60 Ah)

OZ Power VRLA

What sets apart the OZ Power 12 V 60 Ah

The 60 Ah block delivers 931 W for 15 minutes and 347 W for 1 hour at 1.75 V per cell; the catalogue's 15 kW / 32-block example gives about 38 minutes. Its rated capacities are 55.0 Ah at 10 hours and 58.2 Ah at 20 hours (to 1.80 V per cell), with ≤ 6.0 mΩ internal resistance and 16.5 A maximum charge current.

A BB6 takes 30 to 40 of these blocks; with 30 to 36 it weighs 660 to 760 kg in all. The BB7 also takes 60 Ah blocks. Total height is 216 mm with terminals, terminal F11 (M6), short-circuit current 1160 A.

  • Against the OZ Power 12 V 40 Ah (one size down): Capacity C10 · C20 55.0 · 58.2 Ah against 40.0 · 42.4 Ah; Capacity C3 · C5 41.4 · 46.8 Ah against 30.0 · 34.0 Ah; L × W × H 230 × 138 × 211 mm against 197 × 166 × 170 mm; Total height 216 mm against 170 mm; Weight (approx.) 16.5 kg against 11.5 kg.
  • Against the OZ Power 12 V 80 Ah (one size up): Capacity C10 · C20 55.0 · 58.2 Ah against 80.0 · 84.8 Ah; Capacity C3 · C5 41.4 · 46.8 Ah against 60.0 · 68.0 Ah; L × W × H 230 × 138 × 211 mm against 260 × 169 × 211 mm; Weight (approx.) 16.5 kg against 22.0 kg; Max. discharge (5 s) 550 A against 800 A.

Planning data

OZ Power 12 V 60 Ah: currents, breakers, cables, batteries

The rows and columns of the EMEA 2026 catalogue's and AEC manuals' tables that concern the OZ Power 12 V 60 Ah.

Power when it matters

OZ Power 12 V 60 Ah · Power when it matters
W per 12 V block, 1.75 V/cell60 Ah
15 min931
30 min593
60 min347

From load to backup time

OZ Power 12 V 60 Ah · From load to backup time
BatteryBackup time, 15 kW on 32 blocks
12 V 60 Ah≈ 38 min

Size and floor

How big it is

230 × 138 × 211 mm · 16.5 kg.

0.03 m²footprint
0.21 mheight

1.75 mFrontSide230138211

Technical data

Technical data OZ Power 12 V 60 Ah

Only this model's values, from the EMEA 2026 catalogue table.

OZ Power 12 V 60 Ah · Technical data
OZ Power 12 V
Capacity C10 · C2055.0 · 58.2 Ah
Capacity C3 · C541.4 · 46.8 Ah
L × W × H (mm)230 × 138 × 211
Total height (mm)216
Weight (approx.)16.5 kg
Internal resistance≤ 6.0 mΩ
TerminalF11 (M6)
Max. discharge (5 s)550 A
Short-circuit current1160 A
Max. charge current16.5 A
Design life (float)12 years
Used inBB6

Values at 25 °C, fully charged, from the battery data sheets; C3–C20 = capacity at 3, 5, 10 and 20 h discharge (C3, C5 and C10 to 1.80 V/cell, C20 to 1.75 V/cell). Weight tolerance ± 5%. Terminal: default type, others optional. Specifications are subject to change without notice.

More technical detailsrange tables, ordering codes

Planning data

OZ Power VRLA range tables

12 V 60 Ah · constant power, W per 12 V block, 25 °C

AGM VRLA battery · design life 12 years in float · used in BB6.

OZ Power 12 V 60 Ah · constant power, W per 12 V block, 25 °C
End V/cell · V/block5 min10 min15 min30 min1 h2 h3 h4 h5 h8 h10 h20 h
1.60 V · 9.6 V1,8201,3691,07065637922717814012081.668.435.9
1.65 V · 9.9 V1,8011,3191,03863736822117313711881.067.835.3
1.70 V · 10.2 V1,7321,23698661535821516913411579.866.635.0
1.75 V · 10.5 V1,6471,15293159334720916513111279.266.034.6
1.80 V · 10.8 V1,5261,06187257333620216012811078.065.434.3
1.85 V · 11.1 V1,36788373449930318714911910373.261.232.6

12 V 60 Ah · constant current, A, 25 °C

Constant current discharge of the 12 V 60 Ah block, by end voltage and discharge time.

OZ Power 12 V 60 Ah · constant current, A, 25 °C
End V/cell · V/block5 min10 min15 min30 min1 h2 h3 h4 h5 h8 h10 h20 h
1.60 V · 9.6 V17613410260.233.620.015.512.210.46.975.803.04
1.65 V · 9.9 V17012797.557.832.519.415.011.910.16.905.732.99
1.70 V · 10.2 V16211791.355.331.418.714.611.59.846.795.652.95
1.75 V · 10.5 V15110785.052.830.218.114.211.29.606.695.572.91
1.80 V · 10.8 V13896.878.550.529.117.413.810.99.356.585.502.89
1.85 V · 11.1 V12179.165.143.526.116.012.710.28.726.185.182.74

Ordering codes

Ordering codes OZ Power 12 V 60 Ah

Ordering codes OZ Power 12 V 60 Ah
CodeDescription
OZ-1209 · OZ-1224 · OZ-1240 · OZ-1260 · OZ-1280 · OZ-12100 · OZ-12200OZ Power 12 V AGM VRLA blocks: 9 · 24 · 40 · 60 · 80 · 100 · 200 Ah

Questions

Questions about the OZ Power 12 V 60 Ah

Why is the 60 Ah rated 55 Ah at 10 hours?

The data sheet gives 55.0 Ah at the 10-hour rate and 58.2 Ah at 20 hours, to 1.80 V per cell at 25 °C. For UPS sizing the constant-power table (W per block at 1.75 V/cell) is what counts.

How is the backup of a 60 Ah string calculated?

Power per block = load ÷ (efficiency × number of blocks); read that power in the constant-power table at the UPS end voltage, usually 1.75 V/cell. At 15 kW on 32 blocks it is 493 W per block, about 38 minutes.

How big is the AEC OZ Power 12 V 60 Ah and how much does it weigh?

The AEC OZ Power 12 V 60 Ah measures 230 × 138 × 211 mm; weight: 16.5 kg (EMEA 2026 catalogue).

Talk to an AEC engineer

Tell us the load, the supply and the backup time you need for the AEC OZ Power 12 V 60 Ah: we answer with the model and the batteries that fit. AEC International sells through distributors in about 80 countries and an agency in every Italian region: ask AEC which one serves your area.