8 questions about the AEC FERRUS RT, from its series page and its 4 model pages, grouped by subject. Each answer is the one printed on its page; follow the link for the full data, the tables and the drawings.

Choosing, sizing and ordering 2 questions

What sizes does FERRUS RT come in?

1 to 3 kVA, in 4 models of the 2026 catalog for the US, from the FER1000RT-2X9 (1 kVA) to the FER3000RT-6X9 (3 kVA). The datasheet on this page gives every one.

Answered on FERRUS RT

What supply does FERRUS RT need?

110/120 V, 50–60 Hz, single-phase, for every model of the series. Its power factor is 1.0, so each model gives its kVA rating in kW.

Answered on FERRUS RT

Runtime and batteries 1 question

What batteries does FERRUS RT use?

Internal VRLA batteries. The battery bus runs from 24 V DC to 72 V DC, by model.

Answered on FERRUS RT

Installation, size and connections 3 questions

What is the output current of each FERRUS RT model?

At full load, from the rating and the voltage:

ModelOutput currentWorked out as
FER1000RT-2X98.3 A at 120 V1.0 kVA ÷ 120 V
FER1500RT-4X912.5 A at 120 V1.5 kVA ÷ 120 V
FER2000RT-4X916.7 A at 120 V2.0 kVA ÷ 120 V
FER3000RT-6X925.0 A at 120 V3.0 kVA ÷ 120 V

Size the input breaker and the cables of each model from its installation manual and the local electrical code, not from this figure alone.

Each model's own page, linked in the table, gives its full answer and data.

How much heat does each FERRUS RT model give off?

At full load, model by model:

ModelHeatBTU/hEfficiency
FER1000RT-2X978 W26092.8%
FER1500RT-4X9116 W40092.8%
FER2000RT-4X9155 W53092.8%
FER3000RT-6X9233 W79092.8%

Plan the room's cooling for a little more than that: each model is less efficient at part load and while its battery recharges.

Each model's own page, linked in the table, gives its full answer and data.

How many rack units does each FERRUS RT model take?

In a 19-inch rack:

ModelRack unitsHeightDepth
FER1000RT-2X92U3.4 in17.3 in
FER1500RT-4X92U3.4 in17.3 in
FER2000RT-4X92U3.4 in17.8 in
FER3000RT-6X92U3.4 in22.8 in

Check the rack's usable depth, rails and rear clearance for the cables.

Each model's own page, linked in the table, gives its full answer and data.

Communication and monitoring 1 question

How is FERRUS RT monitored over the network?

With the AEC SNMP-M network card, which reports the UPS status and alarms over SNMP to your monitoring software.

Answered on FERRUS RT

Warranty, service and maintenance 1 question

What warranty does FERRUS RT have?

3 years on UPS; 2 years on VRLA batteries, from start-up. Register the UPS with AEC after start-up.

Answered on FERRUS RT

Still a question?

Tell us the load, the voltage and the minutes you need: an AEC engineer answers.