Questions and answers

FERRUS SP: questions and answers

9 questions about the AEC FERRUS SP, from its series page and its 3 model pages, grouped by subject. Each answer is the one printed on its page; follow the link for the full data, the tables and the drawings.

Choosing, sizing and ordering 3 questions

How much power do 3 FERSP6000-16X9 give in parallel?

18 kVA: up to 3 units of the same model run in parallel, by the AEC US user manual of the FERRUS SP. Kept as N+1, with one unit spare, 3 FERSP6000-16X9 carry 12 kVA (12 kW).

Answered on FERSP6000-16X9

What sizes does FERRUS SP come in?

6 to 20 kVA, in 3 models of the 2026 catalog for the US, from the FERSP6000-16X9 (6 kVA) to the FERSP20000-40X9 (20 kVA). The datasheet on this page gives every one.

Answered on FERRUS SP

What supply does FERRUS SP need?

120/240 V, split-phase, for every model of the series. Its power factor is 1.0, so each model gives its kVA rating in kW.

Answered on FERRUS SP

Runtime and batteries 1 question

What batteries does FERRUS SP use?

VRLA batteries. The battery bus runs from 192 V DC to 240 V DC, by model.

Answered on FERRUS SP

Installation, size and connections 3 questions

What is the output current of each FERRUS SP model?

At full load, from the rating and the voltage:

ModelOutput currentWorked out as
FERSP6000-16X925.0 A on each line at 240 V6.0 kVA ÷ 240 V
FERSP10000-16X941.7 A on each line at 240 V10 kVA ÷ 240 V
FERSP20000-40X983.3 A on each line at 240 V20 kVA ÷ 240 V

Size the input breaker and the cables of each model from its installation manual and the local electrical code, not from this figure alone.

Each model's own page, linked in the table, gives its full answer and data.

How much heat does each FERRUS SP model give off?

At full load, model by model:

ModelHeatBTU/hEfficiency
FERSP6000-16X9466 W1,59092.8%
FERSP10000-16X9776 W2,65092.8%
FERSP20000-40X91.6 kW5,29092.8%

Plan the room's cooling for a little more than that: each model is less efficient at part load and while its battery recharges.

Each model's own page, linked in the table, gives its full answer and data.

Will the FERSP20000-40X9 fit through a standard door?

Yes: 15.8 in (401 mm) across its narrow side and 38.7 in (983 mm) high, it passes a standard 36 × 80-inch door upright. On the way in, check corridors, elevators and the floor load of the FERSP20000-40X9 (size section above).

Answered on FERSP20000-40X9

Communication and monitoring 1 question

How is FERRUS SP monitored over the network?

With the AEC SNMP-M network card, which reports the UPS status and alarms over SNMP to your monitoring software.

Answered on FERRUS SP

Warranty, service and maintenance 1 question

What warranty does FERRUS SP have?

3 years on UPS; 2 years on VRLA batteries, from start-up. Register the UPS with AEC after start-up.

Answered on FERRUS SP

Still a question?

Tell us the load, the voltage and the minutes you need: an AEC engineer answers.