Questions and answers

UPS questions answered in the AEC guides

114 questions answered in the blog and the technology articles, grouped by subject. Each answer is the one printed in its guide; the guide has the worked example, the tables and the sources.

Choosing, sizing and ordering 34 questions

What is the difference between a 208 V and a 480 V UPS?

They match the two US three-phase supplies: 208Y/120 V in most commercial buildings, 480Y/277 V in large commercial and industrial ones. At 480 V the same power draws less than half the current.

Answered on 208 V or 480 V: choosing a three-phase UPS

Can a 480 V UPS feed 208 V loads?

Yes, through a step-down transformer between the UPS and the loads, which is how most US data centers are built.

Answered on 208 V or 480 V: choosing a three-phase UPS

How many amps does a 100 kVA UPS draw?

About 278 A at 208 V and about 120 A at 480 V (kVA × 1,000 ÷ (√3 × volts)), before the input current of the charger and losses.

Answered on 208 V or 480 V: choosing a three-phase UPS

Which AEC UPS works on 208 V?

ETHERNO (lithium) and AUREON (VRLA) from 10 to 30 kVA, RADIANT modular from 15 to 90 kVA and RADIANT-IB from 20 to 100 kVA.

Answered on 208 V or 480 V: choosing a three-phase UPS

Is there a 30 kVA modular UPS for 480 V?

Yes: the AEC CIRRO-IB CIRIB150-1X30, one 30 kVA module in a 150 kVA frame at 480/277 V, with its VRLA batteries inside: 14 minutes at full load and 25 at 75 % from the catalog table.

Answered on 208 V or 480 V: choosing a three-phase UPS

How do I choose a UPS?

Answer six questions: the supply voltage, the load in kW, the minutes on battery, where it goes (rack, tower or plant room), the battery chemistry, and how it will be monitored. Together they point to one series and one model.

Answered on How to choose a UPS: six questions to one model

What size UPS does a data center need?

The IT load in kW plus growth, with redundancy on top: N+1 modules in a modular UPS, or 2N with two systems. AEC's modular range covers 15 kVA (RADIANT) to 1,600 kVA (CIRRO) per frame.

Answered on Data center UPS: modular, 480 V and lithium

What is the difference between kVA and kW on a UPS?

kVA is apparent power, volts × amps; kW is the real power the UPS can deliver. kW = kVA × power factor. Most AEC series have a power factor of 1.0, so 20 kVA means 20 kW; LUMINA has 0.9, so its 1 kVA model delivers 900 W.

Answered on kVA vs kW: what a UPS rating really means

How many watts is a 3 kVA UPS?

3,000 W at a power factor of 1.0 (AEC FERRUS 3 kVA) and 2,700 W at 0.9 (AEC LUMINA 3 kVA): watts = kVA × power factor.

Answered on kVA vs kW: what a UPS rating really means

Which comes first when sizing a UPS, kVA or kW?

kW first: add up the real watts of the load and keep it at 70 to 80 % of the UPS kW rating. Then check that the load's kVA is also within the UPS kVA rating.

Answered on kVA vs kW: what a UPS rating really means

How do I convert kW to kVA?

Divide by the power factor: kVA = kW ÷ power factor. A 7 kW load at a power factor of 0.95 is 7.37 kVA; at 0.8, 8.75 kVA.

Answered on kVA vs kW: what a UPS rating really means

Can I add L6 modules later?

Yes, with the load on. A half-full cabinet such as the INF-100+L6-CAB-10x50LI doubles its runtime with ten more modules, and up to 15 cabinets form one system.

Answered on Sizing an L6 lithium battery for an INFINITE UPS

How do you add capacity to a modular UPS?

By sliding more power modules into the empty slots of the frame. An AEC CIRRO 800 frame takes up to eight 100 kVA modules; an INFINITE 200 kVA frame takes two working modules and one spare.

Answered on Growing a modular UPS: frames, modules and N+1

When does N+1 end in a modular UPS?

When the load no longer fits on all the modules but one: with 100 kVA modules, at (modules − 1) × 100 kW. With the 80 % margin AEC's sizing method keeps, at 80 % of that: 400 kW for six modules.

Answered on Growing a modular UPS: frames, modules and N+1

Should I buy a bigger modular frame than I need today?

Yes, often: the CIRRO 600 and 800 frames are the same 31.5 × 39.4 × 78.7 in cabinet with six or eight slots, so the larger one keeps two more slots for growth in the same floor space.

Answered on Growing a modular UPS: frames, modules and N+1

What is the difference between a modular and a monolithic UPS?

A monolithic UPS is one fixed rating in one cabinet and grows by adding whole units in parallel. A modular UPS is a frame of power modules that share the load and grows, or gains N+1, by adding modules.

Answered on Modular vs monolithic UPS, 208 V: space, N+1, service

When is a monolithic UPS the better choice?

When the load fits one unit, N+1 is not required and floor load matters: an ETHERNO 30 with lithium inside stands on 3.4 ft² at about 142 lb/ft².

Answered on Modular vs monolithic UPS, 208 V: space, N+1, service

What does N+1 mean on a UPS?

One more power module or UPS unit than the load needs, so any one can fail or be serviced while the rest carry the load. A 45 kW load on 15 kVA modules needs three (N); N+1 is four.

Answered on N+1 redundancy in modular and parallel UPS, explained

What is the difference between N+1 and 2N?

N+1 adds one spare module or unit to one system. 2N duplicates the whole system, usually with separate feeds, so the load survives the loss of a complete UPS or path.

Answered on N+1 redundancy in modular and parallel UPS, explained

Is a modular UPS more reliable than a single UPS?

Yes, when it runs N+1: one power module can fail or be swapped while the others carry the load, which a single UPS of the same size cannot do. A RAD90-4X15 carries 45 kW on four 15 kVA modules where three would do. Without the spare module a modular UPS has no such margin.

Answered on N+1 redundancy in modular and parallel UPS, explained

How many amps is a 20 kVA UPS at 208 V?

55.5 A per phase at full load: 20,000 VA ÷ (1.732 × 208 V).

Answered on UPS amps: output current from kVA at 120, 208 and 480 V

How many amps does a 3 kVA UPS draw at 120 V?

25 A at full output: 3,000 VA ÷ 120 V. The input current is higher while the battery recharges.

Answered on UPS amps: output current from kVA at 120, 208 and 480 V

How do I convert kVA to amps for a three-phase UPS?

Amps per phase = VA ÷ (√3 × line-to-line voltage). At 480 V, a 500 kVA UPS carries 601.4 A per phase.

Answered on UPS amps: output current from kVA at 120, 208 and 480 V

Which UPS type is best for medical facilities?

Online double conversion: the load always runs on the inverter, so there is no transfer time when the utility fails. Every AEC UPS is online double conversion, from the 1 kVA LUMINA to the 1,600 kVA CIRRO.

Answered on UPS for hospitals and clinics: 120/240 V, 208 V and 480 V

What size UPS do I need for a small office?

Add up the watts of the network, server, phones and point of sale, keep the UPS at about 75 to 80 % of its rating, and match the outlets. A rack of network gear usually fits a 1 to 3 kVA unit such as LUMINA or FERRUS.

Answered on UPS for offices, retail and small business

What UPS protects a 120/240 V panel?

A split-phase UPS such as the FERRUS SP, 6 to 20 kVA, with an isolation transformer.

Answered on UPS for offices, retail and small business

What circuit does a 3 kVA UPS need?

At 120 V a 3 kVA UPS delivers 25 A at full output, more than a 20 A circuit carries. The AEC FERRUS 3 kVA models come with a NEMA L5-30P plug for a 30 A circuit and an L5-30R receptacle.

Answered on UPS for offices, retail and small business

What is the difference between kVA and kW?

kVA is apparent power (volts × amps); kW is the real power that does work. kW = kVA × power factor. At a power factor of 1.0, as on most AEC series, they are equal.

Answered on UPS glossary: the terms in plain English

What does N+1 mean for a UPS?

One more power module or unit than the load needs, so any one can fail or be serviced while the others carry the load.

Answered on UPS glossary: the terms in plain English

What size UPS do I need for a 15 kW load?

At least 18.75 kW, to keep the load at 80 % of the rating. With a power factor of 1.0 that is a 20 kVA UPS such as the AEC ETHERNO ETH20, where 15 kW is 75 % of the rating.

Answered on How to size a UPS: five steps to the power you need

Which rating sizes a UPS, kVA or kW?

Both: the load's kW must fit the UPS's kW, and its kVA the UPS's kVA. kW = kVA × power factor; most AEC series have a power factor of 1.0, LUMINA 0.9.

Answered on How to size a UPS: five steps to the power you need

How many amps does a 15 kW load draw at 208 V?

41.6 A per phase on the UPS output at unity power factor: 15,000 W ÷ (1.732 × 208 V). The UPS input draws more, for its losses and the battery charger.

Answered on How to size a UPS: five steps to the power you need

Which type of UPS is best?

For critical equipment, online double conversion (VFI): the load never sees the utility and there is no transfer time. Standby and line-interactive UPS cost less and suit less sensitive loads.

Answered on What is a UPS? Uninterruptible power supplies explained

Can a 480 V UPS feed 208/120 V loads?

Yes, through a transformer after the UPS (often inside a power distribution unit). A 3-wire 480 V UPS such as INFINITE has no neutral on its output, so 120 V loads always need one; a 4-wire 480 V UPS such as CIRRO carries the neutral but still needs a transformer to reach 208/120 V.

Answered on Isolation transformers

Runtime and batteries 18 questions

Does adding a redundant module add runtime?

No. With the same battery, the minutes follow the kW of the load: an AEC CIRRO-IB gives 10.5 minutes at 45 kW with two 30 kVA modules or with three.

Answered on How to choose a UPS: six questions to one model

How long does one L6 cabinet run an INFINITE?

A full cabinet of 20 modules gives 15 minutes at 200 kW and 30 minutes at 100 kW, at the start of battery life. The INF-200+L6-CAB-20x50LI runs 15 minutes at full load and 30 at half load.

Answered on Sizing an L6 lithium battery for an INFINITE UPS

Does adding UPS modules increase battery runtime?

No. Modules add power, not minutes. The battery must be sized for the frame's final power, or each module added shortens the runtime at the new load.

Answered on Growing a modular UPS: frames, modules and N+1

How long does a UPS battery last?

AEC's VRLA blocks have a design life of 10 to 12 years at 25 °C (77 °F); heat shortens it fast, about half for every 8 °C (14 °F) above. LiFePO4 lithium in LUMINA is rated for 12 to 15 years and 3,000 cycles; the L6 lithium cabinets for 15 years and over 5,000 cycles.

Answered on How long do UPS batteries last? VRLA and lithium

How do I know when to replace UPS batteries?

A failed battery test, a runtime much shorter than at commissioning, or swollen, hot or leaking VRLA blocks.

Answered on How long do UPS batteries last? VRLA and lithium

Can I replace just one battery in a UPS string?

No, general practice is to replace the whole string together, because a new block among aged ones is pushed to their condition.

Answered on How long do UPS batteries last? VRLA and lithium

Why does my UPS stay on battery when the generator is running?

Because the generator's voltage or frequency is outside the UPS input range. The UPS takes the generator only when its input is within range, so the generator must reach stable voltage and frequency first. A UPS that keeps returning to battery points to a generator too small or unstable for the step.

Answered on UPS generator sizing: input, recharge and other loads

What does a business need for hurricane season?

A UPS and a standby generator together: the UPS carries the load without a break when the utility drops and for the minutes the generator takes to start and take the load, and the generator carries the hours. Size the generator on the UPS's maximum input plus the other loads, and give the battery a margin of minutes for a generator that fails its first start.

Answered on UPS generator sizing: input, recharge and other loads

Can a UPS reduce battery charging on a generator?

Yes. RADIANT, RADIANT-IB and CIRRO-IB take a generator contact on dry-contact input IP3 and can limit the charge; CIRRO takes a generator signal on a dry-contact input; INFINITE has a generator mode that turns charging off or reduces it by a set ratio.

Answered on UPS generator sizing: input, recharge and other loads

How do I know when UPS batteries need replacing?

When tests show the capacity near 80 %, when the runtime estimate falls, or when blocks swell, leak or fail. Replace the whole VRLA string, not single blocks.

Answered on UPS maintenance checklist: monthly, quarterly, yearly

Why does halving the load double the runtime, or more?

Batteries deliver more of their energy when discharged slowly. The effect is strongest in lead-acid: an AEC AUR10-40X9A runs 7 minutes at full load and 25 at half load; a lithium ETH10-1X50A-LI runs 14 and 27.

Answered on How long will a UPS run? Battery runtime explained

Does UPS runtime drop as the battery ages?

Yes. Catalog runtimes are at the start of battery life; a VRLA battery is usually considered at end of life when its capacity reaches 80 %, and heat shortens that life.

Answered on How long will a UPS run? Battery runtime explained

How do I calculate UPS runtime?

Read it from the model's runtime table at your load; energy divided by load overstates it, most of all for lead-acid at high load. For AEC L6 lithium cabinets the rating gives it directly: modules × 2.5 kWh × 60 ÷ load in kW, with new modules.

Answered on How long will a UPS run? Battery runtime explained

How long does a 20 kVA UPS run at 15 kW?

The AEC ETH20-2X50A-LI runs 17.5 minutes at 15 kW (75 % load) and the ETH20-3X50A-LI 26.5 minutes, from the 2026 catalog runtime tables with new batteries.

Answered on How to size a UPS: five steps to the power you need

How long does a UPS last on battery?

From 4 minutes to hours: a FERRUS 3 kVA on its internal batteries runs 4.2 minutes at full load and 10 at half load, and external battery packs take a FERRUS to hours at light load. Each AEC model page shows its runtime at every load from the catalog's tables.

Answered on What is a UPS? Uninterruptible power supplies explained

What does UPS stand for in electrical terms?

Uninterruptible power supply: a device that supplies equipment from a battery when the utility fails, and conditions the power the rest of the time.

Answered on What is a UPS? Uninterruptible power supplies explained

How does a UPS battery backup work?

A charger keeps the battery full. When the utility fails, the inverter draws on the battery to keep producing AC for the load; in an online UPS it is already producing it, so there is no switch at all.

Answered on What is a UPS? Uninterruptible power supplies explained

Is a battery backup the same as a UPS?

Yes, in everyday use: battery backup is a common name for a UPS. Small units sold under that name are usually standby or line-interactive and switch to battery with a short break; an online double-conversion UPS has no break at all.

Answered on What is a UPS? Uninterruptible power supplies explained

Lithium batteries 16 questions

Are lithium batteries safe in a data center?

Yes, with the right chemistry and controls: AEC's L6 cabinets use lithium iron phosphate (LiFePO4), the chemistry chosen for stationary storage for its thermal stability, with a battery management system and smoke detector in every cabinet.

Answered on Data center UPS: modular, 480 V and lithium

How many L6 lithium modules do I need?

One 50 Ah module per 10 kW of load for 15 minutes, two for 30 minutes: the larger of load kW ÷ 10 and load kWh ÷ 2.5, rounded up. 200 kW for 15 minutes is 20 modules, one full cabinet.

Answered on Sizing an L6 lithium battery for an INFINITE UPS

How much does an L6 lithium cabinet weigh?

2,171.6 lb with 20 modules, 1,355.8 lb with 10, and 540 lb empty, on a 23.6 × 33.5 in footprint. Each 50 Ah module weighs 81.6 lb and ships in its own carton.

Answered on Sizing an L6 lithium battery for an INFINITE UPS

At what size does a lithium UPS battery fall under NFPA 855?

Above 20 kWh of lithium-ion, counted on the nameplate (rated volts × amp-hours ÷ 1,000), in both NFPA 855 (2026, Table 1.3) and the 2024 International Fire Code (Table 1207.1.3). Lead-acid has a 70 kWh threshold. Confirm the edition your authority having jurisdiction has adopted.

Answered on Lithium UPS fire code: NFPA 855, UL 9540A and 20 kWh

Is a lithium UPS exempt from UL 9540 because the UPS is UL 1778 listed?

Not under the IFC text: its exception in Section 1207.3.1 covers lead-acid battery systems in UPS listed to UL 1778 for standby power, and the scope note of UL 9540 says the fire codes do not exclude UPS that use other chemistries. The AHJ applies the adopted code.

Answered on Lithium UPS fire code: NFPA 855, UL 9540A and 20 kWh

How many kWh is one AEC 50 Ah lithium module?

2.88 kWh on the nameplate: 57.6 V × 50 Ah. An ETHERNO with three modules holds 8.64 kWh; a full L6 cabinet of 20 modules holds 57.6 kWh.

Answered on Lithium UPS fire code: NFPA 855, UL 9540A and 20 kWh

Do two lithium UPS in the same room count together?

Yes, under NFPA 855: its 20 kWh threshold is the aggregate capacity per fire area. Two ETHERNO towers with three modules each hold 17.28 kWh; a third brings the room to 25.92 kWh, above 20 kWh. Ask the AHJ how they count it.

Answered on Lithium UPS fire code: NFPA 855, UL 9540A and 20 kWh

Is a lithium rack UPS lighter than a VRLA one?

Yes. At 3 kVA the AEC LUMINA lithium weighs 37.7 lb against 61.7 lb for the VRLA FERRUS RT, and runs 11 minutes at full load against 4.2.

Answered on Rack-mount UPS: depth, weight, lithium vs VRLA

Do lithium UPS batteries last longer than lead-acid?

Yes, usually: lithium iron phosphate is rated for more years and many more cycles, and it tolerates a warm room better than VRLA.

Answered on How long do UPS batteries last? VRLA and lithium

What UPS fits a small medical practice?

On a 120/240 V split-phase panel, the FERRUS SP (6 to 20 kVA, with an isolation transformer); for a single rack at 120 V, the LUMINA lithium 2U or the FERRUS tower.

Answered on UPS for hospitals and clinics: 120/240 V, 208 V and 480 V

Do lithium UPS batteries need maintenance?

Yes, but less than VRLA: a LiFePO4 battery reports its state through its BMS and lasts longer, and the yearly technician visit still applies.

Answered on UPS maintenance checklist: monthly, quarterly, yearly

What is a lithium UPS?

A UPS whose battery is lithium-ion instead of lead-acid. For UPS use the chemistry is usually lithium iron phosphate (LiFePO4), chosen for long life and thermal stability.

Answered on Lithium UPS: lithium-ion (LiFePO4) vs VRLA, safety, codes and cost

Are lithium UPS batteries safe?

Yes, LiFePO4 is among the more stable lithium chemistries, though no lithium battery is free of risk. Safety comes from the battery management system, the module design and an installation that follows NFPA 855 and the fire code.

Answered on Lithium UPS: lithium-ion (LiFePO4) vs VRLA, safety, codes and cost

How long does a lithium UPS battery last?

AEC's LUMINA catalog gives 12 to 15 years and 3,000 cycles, and the L6 cabinet is rated for 15 years. AEC's VRLA blocks have a design life of 10 to 12 years at 77 °F (25 °C), and last less in a warm room.

Answered on Lithium UPS: lithium-ion (LiFePO4) vs VRLA, safety, codes and cost

Lithium-ion or lead-acid for a UPS?

Lithium for long life, light weight, a smaller footprint and fewer battery replacements; lead-acid for the lowest first cost and the higher fire-code threshold (70 kWh against 20 kWh).

Answered on Lithium UPS: lithium-ion (LiFePO4) vs VRLA, safety, codes and cost

Does a lithium UPS need a permit?

Yes, above 20 kWh of lithium-ion in a room: NFPA 855 and the International Fire Code apply, and the authority having jurisdiction will review the installation. Below it, the general electrical and fire rules still apply.

Answered on Lithium UPS: lithium-ion (LiFePO4) vs VRLA, safety, codes and cost

Installation, size and connections 22 questions

Does a 480 V UPS need a neutral?

Only if it feeds 277 V loads. A 4-wire 480/277 V UPS such as AEC CIRRO or CIRRO-IB takes and gives a neutral; a 3-wire UPS such as INFINITE has none, so 277 V and 120 V loads need a transformer after it.

Answered on 480 V UPS, 3-wire or 4-wire: the neutral explained

Can a 480 V UPS feed 277 V lighting directly?

Yes, if it is 4-wire: CIRRO-IB and CIRRO give 480Y/277 V at their output. A 3-wire UPS like INFINITE needs a transformer with a 480Y/277 V secondary.

Answered on 480 V UPS, 3-wire or 4-wire: the neutral explained

How big should the neutral be on a UPS feeding IT loads?

Larger than a phase: AEC's manuals ask for 1.5 to 1.73 times the phase current with non-linear loads. A 150 kVA CIRRO-IB's neutral is rated 306 A against 180 A per phase.

Answered on 480 V UPS, 3-wire or 4-wire: the neutral explained

Does an AEC UPS switch the neutral?

No. The AC breakers in the RADIANT, RADIANT-IB, CIRRO-IB and CIRRO manuals are three-pole and the neutral is not switched; main and bypass inputs share one neutral.

Answered on 480 V UPS, 3-wire or 4-wire: the neutral explained

Which UPS is best for a server room?

On a 208 V supply, a three-phase online UPS of 10 to 30 kVA such as the AEC ETHERNO (lithium) or AUREON (VRLA); for growth, a modular RADIANT. Size it so the load is about 80 % of its kW rating.

Answered on How to choose a UPS: six questions to one model

Why do data centers use 480 V UPS systems?

Higher voltage means lower current for the same power: about 120 A for 100 kVA at 480 V against about 278 A at 208 V, so cables, breakers and switchgear are smaller.

Answered on Data center UPS: modular, 480 V and lithium

What does 4W (3P+N) mean on a UPS?

Four wires: three phases and a neutral, as on a 208Y/120 V or 480Y/277 V supply. A 3-wire (delta) UPS, such as AEC INFINITE at 480 V, takes the three phases without a neutral.

Answered on How to read a UPS datasheet, line by line

Where do I find a UPS's input breaker size?

In the installation manual, not the datasheet. The input current is higher than the output current because of losses and battery charging.

Answered on How to read a UPS datasheet, line by line

Which takes less floor space, modular or monolithic?

With N+1 above one unit's rating, modular. For 60 kW at 208 V with N+1, three AEC ETHERNO 30 towers take 10.3 ft²; a RADIANT-IB cabinet with four 20 kVA modules takes 6.4 ft².

Answered on Modular vs monolithic UPS, 208 V: space, N+1, service

How do I get redundancy with tower UPS?

Run two units in parallel with a parallel kit, each sized for the whole load. AEC offers parallel kits for ETHERNO and AUREON.

Answered on N+1 redundancy in modular and parallel UPS, explained

How many rack units is a 3 kVA UPS?

AEC's 3 kVA rack UPS are 2U: the LUMINA lithium LUM3000RT-2U-LI and the FERRUS RT FER3000RT-6X9 are both 2U, 22.4 and 22.8 in deep.

Answered on Rack-mount UPS: depth, weight, lithium vs VRLA

Where should a UPS go in a rack?

At the bottom, with its battery packs: the weight low keeps the rack stable. Check the rack's usable depth and leave room for cables behind.

Answered on Rack-mount UPS: depth, weight, lithium vs VRLA

Can a rack UPS stand as a tower?

Yes, if it is built for both: the AEC FERRUS RT is a rack or tower unit, so it can stand on the floor or mount in a 19-inch rack. LUMINA is a 2U rack unit.

Answered on Rack-mount UPS: depth, weight, lithium vs VRLA

Can I size the UPS breaker from the output current?

No. The input current is higher (losses and battery charging), and US practice sizes continuous loads at 125 %. Use the installation manual and the engineer of record.

Answered on UPS amps: output current from kVA at 120, 208 and 480 V

Should a laser printer go on a UPS?

No. Its heating element draws large inrush currents that shorten runtime and can overload a small UPS, so keep it on the utility supply.

Answered on UPS for offices, retail and small business

What receptacles do AEC 120 V UPS units have?

NEMA 5-15R on the 1 kVA models and the LUMINA 1.5 kVA, NEMA 5-20R on the larger ones, plus a 30 A NEMA L5-30R twist-lock receptacle on the 3 kVA models of LUMINA and FERRUS.

Answered on UPS for offices, retail and small business

How long will a UPS run an office network?

17 to 46 minutes for an example rack drawing 1,080 W: 17 minutes on an AEC LUMINA 1.5 kVA and 42 to 46 minutes on the LUMINA 2.2 kVA, from their catalog runtime tables. A lighter load runs longer.

Answered on UPS for offices, retail and small business

How big a generator do I need for an AEC UPS?

For the UPS alone, about its maximum input in kVA: a RADIANT-IB 100 kVA draws at most 348 A at 208 V, 125.4 kVA, the input current its US manual gives at full load with the battery recharging. Add the other loads on the generator. The AEC user manuals' general rule, 1.5 times the UPS input power, is a conservative figure that needs no calculation.

Answered on UPS generator sizing: input, recharge and other loads

How do I calculate the heat output of a UPS?

Losses in kW = load in kW × (1 ÷ efficiency − 1); heat in BTU/h = losses in watts × 3.412. An AEC ETHERNO 20 kVA at 20 kW and 94 % efficiency gives off about 1.28 kW, 4,360 BTU/h.

Answered on UPS heat output: BTU/h, cooling and the cost of losses

How many BTU does a 20 kVA UPS produce?

About 4,360 BTU/h at full load for an AEC ETH20-3X50A-LI (94 % efficiency) and about 5,140 BTU/h for a FERSP20000-40X9 (93 %). Plan a little more: efficiency is lower at part load and while the battery charges.

Answered on UPS heat output: BTU/h, cooling and the cost of losses

How many tons of cooling does a server room UPS need?

Add the IT load and the UPS losses, in BTU/h, and divide by 12,000. 15 kW of servers on an AEC ETHERNO at 94 % give about 54,450 BTU/h, 4.5 tons, before lighting, people and walls.

Answered on UPS heat output: BTU/h, cooling and the cost of losses

What size UPS do I need for a 1,500 W rack?

At least 1,875 W, to keep the load at 80 %. The AEC LUMINA LUM2200RT-2U-LI gives 1,980 W and about 33 minutes at 1,500 W from its catalog runtime table; the 3 kVA LUMINA gives about 25 minutes with more room to grow.

Answered on How to size a UPS: five steps to the power you need

Efficiency and operation 19 questions

What is the most efficient AEC UPS?

INFINITE 1.5MW, with silicon-carbide modules, at up to 97.5 %; INFINITE 100–600 kVA reaches 97.3 % and CIRRO up to 97 %.

Answered on Data center UPS: modular, 480 V and lithium

What does 'efficiency up to' mean on a UPS datasheet?

The best point of the efficiency curve, usually at mid to high load. At light load the efficiency is lower; the AEC efficiency charts show the curve for each series.

Answered on How to read a UPS datasheet, line by line

What does THDi mean on a UPS datasheet?

Total harmonic distortion of the input current: how much the UPS distorts the supply it draws from. A low figure, such as the 3 % or less of AEC INFINITE 1.5MW, makes the UPS an easier load for a generator.

Answered on How to read a UPS datasheet, line by line

Is a modular UPS more efficient than a monolithic one?

Not by design alone: AEC's 208 V tower and modular curves are within 0.3 points. The gain comes from running modules nearer their best point, for example by letting spare modules sleep.

Answered on Modular vs monolithic UPS, 208 V: space, N+1, service

What is ECO mode on a UPS?

A setting in which an online UPS feeds the load from its static bypass, straight from the utility, with the inverter on standby. Efficiency rises, but the load is no longer conditioned and moves to the inverter only after a disturbance has started.

Answered on ECO mode vs double conversion: what the load gives up

Does AEC recommend ECO mode?

No. AEC designs and recommends online double conversion as the normal operating mode. The ETHERNO, AUREON, CIRRO and INFINITE manuals say the same: in ECO the load has no protection from disturbances, so use online mode for critical loads.

Answered on ECO mode vs double conversion: what the load gives up

How efficient is an AEC UPS in double conversion?

From 92.5 to 94.0 % on ETHERNO, AUREON, RADIANT and RADIANT-IB, 95.0 to 96.0 % on CIRRO-IB, up to 97.0 % on CIRRO 600 to 1600, 96.9 to 97.3 % on INFINITE and up to 97.5 % on INFINITE 1.5MW, from the catalog curves.

Answered on ECO mode vs double conversion: what the load gives up

How fast does a UPS leave ECO mode?

AEC RADIANT, RADIANT-IB and CIRRO-IB move the load to the inverters in less than 10 ms when the bypass fails. The ITI (CBEMA) curve describes a dropout of up to 20 ms as typically tolerated by most IT equipment; check motors and controls.

Answered on ECO mode vs double conversion: what the load gives up

What is the difference between ECO mode and module sleep?

ECO puts the load on the bypass. Module sleep keeps the load in double conversion and lets the modules not needed stand by, so the running ones work nearer their best efficiency.

Answered on ECO mode vs double conversion: what the load gives up

Does a hospital need a UPS if it has generators?

Yes: generators in a US hospital must take the life safety and critical branches within 10 seconds (NFPA 99, NFPA 110 Level 1). Computers, networks and controls drop in far less, so a UPS carries them through those seconds and cleans the generator's power afterwards.

Answered on UPS for hospitals and clinics: 120/240 V, 208 V and 480 V

Does a UPS need a generator twice its size?

Not with an active PFC rectifier. Factors of 1.4 to 2 come from thyristor rectifiers, 6- or 12-pulse, whose harmonic current heats the alternator. AEC's three-phase UPS draw at an input power factor of 0.99 or more, with input current distortion of 5 % or less at full load.

Answered on UPS generator sizing: input, recharge and other loads

What does online double conversion mean?

The UPS converts the utility's AC to DC and back to clean AC all the time, so the load is isolated from the utility and there is no transfer time on a failure.

Answered on UPS glossary: the terms in plain English

Does UPS efficiency matter for the electric bill?

Yes, on large systems most of all. An AEC INF15-1500 at full load loses about 337,000 kWh a year at 97.5 % efficiency; at $0.12 per kWh that is about $40,000, before the cooling.

Answered on UPS heat output: BTU/h, cooling and the cost of losses

What is a UPS used for?

To keep computers, servers, network equipment, medical devices and controls running through outages and power disturbances, long enough for the power to return, a generator to start or the equipment to shut down in order.

Answered on What is a UPS? Uninterruptible power supplies explained

What is the difference between a UPS and a generator?

A UPS takes over instantly but only for its battery runtime; a generator runs for hours but needs seconds to start. Critical sites use both.

Answered on What is a UPS? Uninterruptible power supplies explained

What does an isolation transformer do in a UPS?

It separates the output from the input galvanically: no conductor runs straight through. That lets the output have its own neutral and ground bond (a separately derived system), change the voltage (480 V in, 208/120 V out), and keeps much of the common-mode noise of the supply away from the load.

Answered on Isolation transformers

Do I need a UPS with an isolation transformer?

Not for most IT loads on a 4-wire supply: modern online UPS are transformerless and more efficient. You need one when the load needs a neutral the supply does not have, a different voltage than the supply, a separately derived system by design, or very low leakage current (some medical and laboratory equipment).

Answered on Isolation transformers

Transformer-based or transformerless UPS?

Transformerless UPS are smaller, lighter and more efficient; transformer-based UPS isolate and can change voltage inside the cabinet. Today most large UPS are transformerless and a transformer is added outside, only where the installation needs one.

Answered on Isolation transformers

Which AEC UPS has an isolation transformer?

FERRUS SP and FERRUS SP RT, the 120/240 V split-phase UPS, have an integrated isolation transformer, according to the 2026 catalog. The three-phase series are transformerless.

Answered on Isolation transformers

Warranty, service and maintenance 4 questions

What warranty do AEC UPS carry?

Five years with the lithium batteries on LUMINA and ETHERNO; three years on the other series and two on VRLA batteries; INFINITE five years when registered, with five years on its L6 lithium cabinets.

Answered on How to choose a UPS: six questions to one model

Can you hot-swap a UPS power module?

Yes, in a modular UPS such as AEC RADIANT, CIRRO and INFINITE: a power module slides out while the others carry the load.

Answered on N+1 redundancy in modular and parallel UPS, explained

How often should a UPS be serviced?

A quick check every month by the site team (display, alarms, room temperature), a battery check every quarter, and a yearly visit by a qualified technician with battery tests and a thermal scan.

Answered on UPS maintenance checklist: monthly, quarterly, yearly

Can a UPS be serviced without shutting the load down?

Yes, through the maintenance bypass: the load moves to the utility while the UPS is isolated. It has no battery behind it during that time, so the visit is scheduled at a quiet hour.

Answered on UPS maintenance checklist: monthly, quarterly, yearly

About the product and AEC 1 question

Can a UPS power MRI or CT scanners?

Not from a general-purpose UPS: imaging systems have their own power specifications from their manufacturer, and often a dedicated UPS. Follow the manufacturer's requirements and the facility engineer's design.

Answered on UPS for hospitals and clinics: 120/240 V, 208 V and 480 V