Questions and answers

LUMINA: questions and answers

8 questions about the AEC LUMINA, from its series page and its 5 model pages, grouped by subject. Each answer is the one printed on its page; follow the link for the full data, the tables and the drawings.

Choosing, sizing and ordering 1 question

How many watts does LUMINA deliver?

Its power factor is 0.9, so watts are 90 % of the VA: 1,000 VA gives 900 W, 1,500 VA gives 1,350 W, 2,000 VA gives 1,800 W, 2,200 VA gives 1,980 W, 3,000 VA gives 2,700 W.

Answered on LUMINA

Runtime and batteries 2 questions

How long does each LUMINA model run on battery?

At the start of battery life, model by model:

Model100 % load50 % load10 % load
LUM1000RT-2U-LI11 min (900 W)27 min (450 W)2 h 5 min (90 W)
LUM1500RT-2U-LI111 min (1.4 kW)27 min (675 W)2 h 5 min (135 W)
LUM2000RT-2U-LI11 min (1.8 kW)27 min (900 W)2 h 5 min (180 W)
LUM2200RT-2U-LI23 min (2.0 kW)46 min (990 W)3 h 56 min (198 W)
LUM3000RT-2U-LI11 min (2.7 kW)27 min (1.4 kW)2 h 5 min (270 W)

Unless marked: from the catalog runtime table at the start of battery life.

1 At the start of battery life: the full-load figure published, the other points an AEC estimate.

Runtime falls faster than the load rises: the chart on each model's page gives the minutes at any load in between.

Each model's own page, linked in the table, gives its full answer and data.

How long does LUMINA run on battery?

The LUM1000RT-2U-LI, LUM2000RT-2U-LI and LUM3000RT-2U-LI run 11 min at full load and 27 min at half load. The LUM1500RT-2U-LI runs 11 min at full load and 27 min at half load (AEC estimate). The LUM2200RT-2U-LI runs 23 min at full load and 46 min at half load. Figures from the 2026 catalog runtime tables, with new batteries.

Answered on LUMINA

Installation, size and connections 4 questions

What is the output current of each LUMINA model?

At full load, from the rating and the voltage:

ModelOutput currentWorked out as
LUM1000RT-2U-LI8.3 A at 120 V1.0 kVA ÷ 120 V
LUM1500RT-2U-LI12.5 A at 120 V1.5 kVA ÷ 120 V
LUM2000RT-2U-LI16.7 A at 120 V2.0 kVA ÷ 120 V
LUM2200RT-2U-LI18.3 A at 120 V2.2 kVA ÷ 120 V
LUM3000RT-2U-LI25.0 A at 120 V3.0 kVA ÷ 120 V

Size the input breaker and the cables of each model from its installation manual and the local electrical code, not from this figure alone.

Each model's own page, linked in the table, gives its full answer and data.

How much heat does each LUMINA model give off?

At full load, model by model:

ModelHeatBTU/hEfficiency
LUM1000RT-2U-LI81 W28091.7%
LUM1500RT-2U-LI111 W38092.4%
LUM2000RT-2U-LI148 W51092.4%
LUM2200RT-2U-LI163 W56092.4%
LUM3000RT-2U-LI222 W76092.4%

Plan the room's cooling for a little more than that: each model is less efficient at part load and while its battery recharges.

Each model's own page, linked in the table, gives its full answer and data.

How many rack units does each LUMINA model take?

In a 19-inch rack:

ModelRack unitsHeightDepth
LUM1000RT-2U-LI2U3.4 in16.5 in
LUM1500RT-2U-LI2U3.4 in22.6 in
LUM2000RT-2U-LI2U3.4 in22.4 in
LUM2200RT-2U-LI2U3.4 in24.2 in
LUM3000RT-2U-LI2U3.4 in22.4 in

Check the rack's usable depth, rails and rear clearance for the cables.

Each model's own page, linked in the table, gives its full answer and data.

How much rack space does LUMINA take?

2U of a 19-inch rack: 3.4 in high, 16.5 to 24.2 in deep depending on the model, with a telescopic rail kit available. Check the rack's usable depth before you order.

Answered on LUMINA

Warranty, service and maintenance 1 question

What warranty does LUMINA have?

5 years including the lithium batteries, from start-up. LUMINA is ETL Listed, as the 2026 catalog shows.

Answered on LUMINA

Still a question?

Tell us the load, the voltage and the minutes you need: an AEC engineer answers.