Choosing, sizing and ordering 2 questions

Which AEC UPS reach 500 kVA at 480 V?

CIRRO, 60–1,600 kVA on 4-wire supplies, and INFINITE, 100–600 kVA on 3-wire supplies. INFINITE 1.5MW starts at 750 kVA.

Answered on INFINITE

How is INFINITE built up to 600 kVA?

100 to 600 kVA: one 100 or 200 kVA frame, or up to three 200 kVA frames in parallel; above 600 kVA, INFINITE 1.5MW. The power modules are 100 kVA; one module more than the load needs gives N+1 redundancy.

Answered on INFINITE

Runtime and batteries 2 questions

How long does each INFINITE model run on battery?

At the start of battery life, model by model:

Model100 % load50 % load10 % load
INF-100+1+L6-CAB-20x50LI30 min (100 kW)60 min (50 kW)5 h 0 min (10 kW)
INF-100+L6-CAB-10x50LI15 min (100 kW)30 min (50 kW)2 h 30 min (10 kW)
INF-100+L6-CAB-20x50LI30 min (100 kW)60 min (50 kW)5 h 0 min (10 kW)
INF-200+1+L6-CAB-20x50LI15 min (200 kW)30 min (100 kW)2 h 30 min (20 kW)
INF-200+L6-CAB-20x50LI15 min (200 kW)30 min (100 kW)2 h 30 min (20 kW)
INF-400+2xL6-CAB-20x50LI15 min (400 kW)30 min (200 kW)2 h 30 min (40 kW)
INF-600+3xL6-CAB-20x50LI15 min (600 kW)30 min (300 kW)2 h 30 min (60 kW)

From the rating of its 50 Ah lithium modules, 10 kW for 15 minutes each, at the start of battery life.

These minutes divide the modules' energy by the load; a battery gives less in a fast discharge, so take the light-load figures as an upper bound. The chart on each model's page gives the minutes at any load in between.

Each model's own page, linked in the table, gives its full answer and data.

What batteries does INFINITE use?

External, lead-acid (30–50 blocks) or AEC L6 lithium cabinets. With L6 lithium the catalog lists 7 set-ups, from the INF-100+1+L6-CAB-20x50LI to the INF-600+3xL6-CAB-20x50LI.

Answered on INFINITE

Installation, size and connections 4 questions

What is the output current of each INFINITE model?

At full load, from the rating and the voltage:

ModelOutput currentWorked out as
INF-100120.3 A per phase100 kVA ÷ (√3 × 480 V)
INF-100+1120.3 A per phase100 kVA ÷ (√3 × 480 V)
INF-100+1+L6-CAB-20x50LI120.3 A per phase100 kVA ÷ (√3 × 480 V)
INF-100+L6-CAB-10x50LI120.3 A per phase100 kVA ÷ (√3 × 480 V)
INF-100+L6-CAB-20x50LI120.3 A per phase100 kVA ÷ (√3 × 480 V)
INF-200240.6 A per phase200 kVA ÷ (√3 × 480 V)
INF-200+1240.6 A per phase200 kVA ÷ (√3 × 480 V)
INF-200+1+L6-CAB-20x50LI240.6 A per phase200 kVA ÷ (√3 × 480 V)
INF-200+L6-CAB-20x50LI240.6 A per phase200 kVA ÷ (√3 × 480 V)
INF-400481.1 A per phase400 kVA ÷ (√3 × 480 V)
INF-400+2xL6-CAB-20x50LI481.1 A per phase400 kVA ÷ (√3 × 480 V)
INF-600721.7 A per phase600 kVA ÷ (√3 × 480 V)
INF-600+3xL6-CAB-20x50LI721.7 A per phase600 kVA ÷ (√3 × 480 V)

Size the input breaker and the cables of each model from its installation manual and the local electrical code, not from this figure alone.

Each model's own page, linked in the table, gives its full answer and data.

How much heat does each INFINITE model give off?

At full load, model by model:

ModelHeatBTU/hEfficiency
INF-1002.8 kW9,47097.3%
INF-100+12.8 kW9,47097.3%
INF-100+1+L6-CAB-20x50LI2.8 kW9,47097.3%
INF-100+L6-CAB-10x50LI2.8 kW9,47097.3%
INF-100+L6-CAB-20x50LI2.8 kW9,47097.3%
INF-2005.5 kW18,94097.3%
INF-200+15.5 kW18,94097.3%
INF-200+1+L6-CAB-20x50LI5.5 kW18,94097.3%
INF-200+L6-CAB-20x50LI5.5 kW18,94097.3%
INF-40011 kW37,87097.3%
INF-400+2xL6-CAB-20x50LI11 kW37,87097.3%
INF-60017 kW56,81097.3%
INF-600+3xL6-CAB-20x50LI17 kW56,81097.3%

Plan the room's cooling for a little more than that: each model is less efficient at part load and while its battery recharges.

Each model's own page, linked in the table, gives its full answer and data.

Which INFINITE models fit through a standard door?

A standard 36 × 80-inch door clears about 34 × 79 in. Upright, model by model:

ModelUpright through the doorNarrow side, height
INF-100No: needs an opening taller than 81.4 in81.4 in (2,068 mm) high
INF-100+1No: needs an opening taller than 81.4 in81.4 in (2,068 mm) high
INF-200No: needs an opening taller than 81.4 in81.4 in (2,068 mm) high
INF-200+1No: needs an opening taller than 81.4 in81.4 in (2,068 mm) high
INF-400No: needs an opening taller than 81.4 in81.4 in (2,068 mm) high
INF-600No: needs an opening taller than 81.4 in81.4 in (2,068 mm) high

On the way in, check corridors, elevators and the floor load (size section of each model's page).

Each model's own page, linked in the table, gives its full answer and data.

What does silicon carbide (SiC) change in INFINITE?

INFINITE's power modules use silicon carbide (SiC) semiconductors, where AEC's other three-phase series use 3-level IGBTs. The 2026 catalog gives INFINITE up to 97.3% efficiency: less loss, so less heat for the room's cooling to remove.

Answered on INFINITE

Warranty, service and maintenance 1 question

What warranty does INFINITE have?

3 years on UPS, 5 if registered; 5 years on lithium cabinets including batteries. To get the 5 years, register the UPS with its serial number and invoice.

Answered on INFINITE