How much power do CIRRO units give in parallel?
Units of the same model only:
| Model | Units in parallel | Total | N+1, one unit spare |
|---|---|---|---|
| CIR360-1X60 | 8 | 480 kVA | 420 kVA (420 kW) |
| CIR360-2X60 | 8 | 960 kVA | 840 kVA (840 kW) |
| CIR360-3X60 | 8 | 1,440 kVA | 1,260 kVA (1,260 kW) |
| CIR600-1X100 | 8 | 800 kVA | 700 kVA (700 kW) |
| CIR600-2X100 | 8 | 1,600 kVA | 1,400 kVA (1,400 kW) |
By the AEC US user manual of the CIRRO.
Each model's own page, linked in the table, gives its full answer and data.
What sizes does CIRRO come in?
60 to 1,600 kVA, in 21 models of the 2026 catalog for the US, from the CIR360-1X60 (60 kVA) to the CIR1600-16X100 (1,600 kVA). The datasheet on this page gives every one.
Answered on CIRRO
Runtime and batteries 1 question
What batteries does CIRRO use?
External VRLA battery bank. The battery bus is 480 V DC on every model.
Answered on CIRRO
Installation, size and connections 4 questions
What is the output current of each CIRRO model?
At full load, from the rating and the voltage:
| Model | Output current | Worked out as |
|---|---|---|
| CIR360-1X60 | 72.2 A per phase | 60 kVA ÷ (√3 × 480 V) |
| CIR360-2X60 | 144.3 A per phase | 120 kVA ÷ (√3 × 480 V) |
| CIR360-3X60 | 216.5 A per phase | 180 kVA ÷ (√3 × 480 V) |
| CIR360-4X60 | 288.7 A per phase | 240 kVA ÷ (√3 × 480 V) |
| CIR360-5X60 | 360.8 A per phase | 300 kVA ÷ (√3 × 480 V) |
| CIR360-6X60 | 433.0 A per phase | 360 kVA ÷ (√3 × 480 V) |
| CIR600-1X100 | 120.3 A per phase | 100 kVA ÷ (√3 × 480 V) |
| CIR600-2X100 | 240.6 A per phase | 200 kVA ÷ (√3 × 480 V) |
| CIR600-4X100 | 481.1 A per phase | 400 kVA ÷ (√3 × 480 V) |
| CIR600-5X100 | 601.4 A per phase | 500 kVA ÷ (√3 × 480 V) |
| CIR600-6X100 | 721.7 A per phase | 600 kVA ÷ (√3 × 480 V) |
| CIR800-7X100 | 842.0 A per phase | 700 kVA ÷ (√3 × 480 V) |
| CIR800-8X100 | 962.3 A per phase | 800 kVA ÷ (√3 × 480 V) |
| CIR1200-9X100 | 1,082.5 A per phase | 900 kVA ÷ (√3 × 480 V) |
| CIR1200-10X100 | 1,202.8 A per phase | 1,000 kVA ÷ (√3 × 480 V) |
| CIR1200-11X100 | 1,323.1 A per phase | 1,100 kVA ÷ (√3 × 480 V) |
| CIR1200-12X100 | 1,443.4 A per phase | 1,200 kVA ÷ (√3 × 480 V) |
| CIR1600-13X100 | 1,563.7 A per phase | 1,300 kVA ÷ (√3 × 480 V) |
| CIR1600-14X100 | 1,683.9 A per phase | 1,400 kVA ÷ (√3 × 480 V) |
| CIR1600-15X100 | 1,804.2 A per phase | 1,500 kVA ÷ (√3 × 480 V) |
| CIR1600-16X100 | 1,924.5 A per phase | 1,600 kVA ÷ (√3 × 480 V) |
Size the input breaker and the cables of each model from its installation manual and the local electrical code, not from this figure alone.
Each model's own page, linked in the table, gives its full answer and data.
How much heat does each CIRRO model give off?
At full load, model by model:
| Model | Heat | BTU/h | Efficiency |
|---|---|---|---|
| CIR360-1X60 | 2.6 kW | 8,980 | 95.8% |
| CIR360-2X60 | 5.3 kW | 17,950 | 95.8% |
| CIR360-3X60 | 7.9 kW | 26,930 | 95.8% |
| CIR360-4X60 | 11 kW | 35,900 | 95.8% |
| CIR360-5X60 | 13 kW | 44,880 | 95.8% |
| CIR360-6X60 | 16 kW | 53,850 | 95.8% |
| CIR600-1X100 | 3.3 kW | 11,280 | 96.8% |
| CIR600-2X100 | 6.6 kW | 22,560 | 96.8% |
| CIR600-4X100 | 13 kW | 45,120 | 96.8% |
| CIR600-5X100 | 17 kW | 56,400 | 96.8% |
| CIR600-6X100 | 20 kW | 67,680 | 96.8% |
| CIR800-7X100 | 23 kW | 78,960 | 96.8% |
| CIR800-8X100 | 26 kW | 90,230 | 96.8% |
| CIR1200-9X100 | 30 kW | 101,510 | 96.8% |
| CIR1200-10X100 | 33 kW | 112,790 | 96.8% |
| CIR1200-11X100 | 36 kW | 124,070 | 96.8% |
| CIR1200-12X100 | 40 kW | 135,350 | 96.8% |
| CIR1600-13X100 | 43 kW | 146,630 | 96.8% |
| CIR1600-14X100 | 46 kW | 157,910 | 96.8% |
| CIR1600-15X100 | 50 kW | 169,190 | 96.8% |
| CIR1600-16X100 | 53 kW | 180,470 | 96.8% |
Plan the room's cooling for a little more than that: each model is less efficient at part load and while its battery recharges.
Each model's own page, linked in the table, gives its full answer and data.
Which CIRRO models fit through a standard door?
A standard 36 × 80-inch door clears about 34 × 79 in. Upright, model by model:
| Model | Upright through the door | Narrow side, height |
|---|---|---|
| CIR360-1X60 | Yes, with little to spare in height | 23.6 in (599 mm) across, 78.7 in (1,999 mm) high |
| CIR360-2X60 | Yes, with little to spare in height | 23.6 in (599 mm) across, 78.7 in (1,999 mm) high |
| CIR360-3X60 | Yes, with little to spare in height | 23.6 in (599 mm) across, 78.7 in (1,999 mm) high |
| CIR360-4X60 | Yes, with little to spare in height | 23.6 in (599 mm) across, 78.7 in (1,999 mm) high |
| CIR360-5X60 | Yes, with little to spare in height | 23.6 in (599 mm) across, 78.7 in (1,999 mm) high |
| CIR360-6X60 | Yes, with little to spare in height | 23.6 in (599 mm) across, 78.7 in (1,999 mm) high |
| CIR600-1X100 | Yes, with little to spare in height | 31.5 in (800 mm) across, 78.7 in (1,999 mm) high |
| CIR600-2X100 | Yes, with little to spare in height | 31.5 in (800 mm) across, 78.7 in (1,999 mm) high |
| CIR600-4X100 | Yes, with little to spare in height | 31.5 in (800 mm) across, 78.7 in (1,999 mm) high |
| CIR600-5X100 | Yes, with little to spare in height | 31.5 in (800 mm) across, 78.7 in (1,999 mm) high |
| CIR600-6X100 | Yes, with little to spare in height | 31.5 in (800 mm) across, 78.7 in (1,999 mm) high |
| CIR800-7X100 | Yes, with little to spare in height | 31.5 in (800 mm) across, 78.7 in (1,999 mm) high |
| CIR800-8X100 | Yes, with little to spare in height | 31.5 in (800 mm) across, 78.7 in (1,999 mm) high |
| CIR1200-9X100 | No: needs an opening wider than 43.3 in | 43.3 in (1,100 mm) across |
| CIR1200-10X100 | No: needs an opening wider than 43.3 in | 43.3 in (1,100 mm) across |
| CIR1200-11X100 | No: needs an opening wider than 43.3 in | 43.3 in (1,100 mm) across |
| CIR1200-12X100 | No: needs an opening wider than 43.3 in | 43.3 in (1,100 mm) across |
| CIR1600-13X100 | No: needs an opening wider than 39.4 in | 39.4 in (1,001 mm) across |
| CIR1600-14X100 | No: needs an opening wider than 39.4 in | 39.4 in (1,001 mm) across |
| CIR1600-15X100 | No: needs an opening wider than 39.4 in | 39.4 in (1,001 mm) across |
| CIR1600-16X100 | No: needs an opening wider than 39.4 in | 39.4 in (1,001 mm) across |
On the way in, check corridors, elevators and the floor load (size section of each model's page).
Each model's own page, linked in the table, gives its full answer and data.
What supply does CIRRO need?
480/277 V three-phase, 4-wire, for every model of the series. Its power factor is 1.0, so each model gives its kVA rating in kW.
Answered on CIRRO
Communication and monitoring 1 question
How is CIRRO monitored over the network?
With the AEC SNMP-M network card, which reports the UPS status and alarms over SNMP to your monitoring software.
Answered on CIRRO
Warranty, service and maintenance 1 question
What warranty does CIRRO have?
3 years on UPS; 2 years on VRLA batteries, from start-up. Register the UPS with AEC after start-up.
Answered on CIRRO