Questions and answers

CIRRO: questions and answers

9 questions about the AEC CIRRO, from its series page and its 21 model pages, grouped by subject. Each answer is the one printed on its page; follow the link for the full data, the tables and the drawings.

Choosing, sizing and ordering 2 questions

How much power do CIRRO units give in parallel?

Units of the same model only:

ModelUnits in parallelTotalN+1, one unit spare
CIR360-1X608480 kVA420 kVA (420 kW)
CIR360-2X608960 kVA840 kVA (840 kW)
CIR360-3X6081,440 kVA1,260 kVA (1,260 kW)
CIR600-1X1008800 kVA700 kVA (700 kW)
CIR600-2X10081,600 kVA1,400 kVA (1,400 kW)

By the AEC US user manual of the CIRRO.

Each model's own page, linked in the table, gives its full answer and data.

What sizes does CIRRO come in?

60 to 1,600 kVA, in 21 models of the 2026 catalog for the US, from the CIR360-1X60 (60 kVA) to the CIR1600-16X100 (1,600 kVA). The datasheet on this page gives every one.

Answered on CIRRO

Runtime and batteries 1 question

What batteries does CIRRO use?

External VRLA battery bank. The battery bus is 480 V DC on every model.

Answered on CIRRO

Installation, size and connections 4 questions

What is the output current of each CIRRO model?

At full load, from the rating and the voltage:

ModelOutput currentWorked out as
CIR360-1X6072.2 A per phase60 kVA ÷ (√3 × 480 V)
CIR360-2X60144.3 A per phase120 kVA ÷ (√3 × 480 V)
CIR360-3X60216.5 A per phase180 kVA ÷ (√3 × 480 V)
CIR360-4X60288.7 A per phase240 kVA ÷ (√3 × 480 V)
CIR360-5X60360.8 A per phase300 kVA ÷ (√3 × 480 V)
CIR360-6X60433.0 A per phase360 kVA ÷ (√3 × 480 V)
CIR600-1X100120.3 A per phase100 kVA ÷ (√3 × 480 V)
CIR600-2X100240.6 A per phase200 kVA ÷ (√3 × 480 V)
CIR600-4X100481.1 A per phase400 kVA ÷ (√3 × 480 V)
CIR600-5X100601.4 A per phase500 kVA ÷ (√3 × 480 V)
CIR600-6X100721.7 A per phase600 kVA ÷ (√3 × 480 V)
CIR800-7X100842.0 A per phase700 kVA ÷ (√3 × 480 V)
CIR800-8X100962.3 A per phase800 kVA ÷ (√3 × 480 V)
CIR1200-9X1001,082.5 A per phase900 kVA ÷ (√3 × 480 V)
CIR1200-10X1001,202.8 A per phase1,000 kVA ÷ (√3 × 480 V)
CIR1200-11X1001,323.1 A per phase1,100 kVA ÷ (√3 × 480 V)
CIR1200-12X1001,443.4 A per phase1,200 kVA ÷ (√3 × 480 V)
CIR1600-13X1001,563.7 A per phase1,300 kVA ÷ (√3 × 480 V)
CIR1600-14X1001,683.9 A per phase1,400 kVA ÷ (√3 × 480 V)
CIR1600-15X1001,804.2 A per phase1,500 kVA ÷ (√3 × 480 V)
CIR1600-16X1001,924.5 A per phase1,600 kVA ÷ (√3 × 480 V)

Size the input breaker and the cables of each model from its installation manual and the local electrical code, not from this figure alone.

Each model's own page, linked in the table, gives its full answer and data.

How much heat does each CIRRO model give off?

At full load, model by model:

ModelHeatBTU/hEfficiency
CIR360-1X602.6 kW8,98095.8%
CIR360-2X605.3 kW17,95095.8%
CIR360-3X607.9 kW26,93095.8%
CIR360-4X6011 kW35,90095.8%
CIR360-5X6013 kW44,88095.8%
CIR360-6X6016 kW53,85095.8%
CIR600-1X1003.3 kW11,28096.8%
CIR600-2X1006.6 kW22,56096.8%
CIR600-4X10013 kW45,12096.8%
CIR600-5X10017 kW56,40096.8%
CIR600-6X10020 kW67,68096.8%
CIR800-7X10023 kW78,96096.8%
CIR800-8X10026 kW90,23096.8%
CIR1200-9X10030 kW101,51096.8%
CIR1200-10X10033 kW112,79096.8%
CIR1200-11X10036 kW124,07096.8%
CIR1200-12X10040 kW135,35096.8%
CIR1600-13X10043 kW146,63096.8%
CIR1600-14X10046 kW157,91096.8%
CIR1600-15X10050 kW169,19096.8%
CIR1600-16X10053 kW180,47096.8%

Plan the room's cooling for a little more than that: each model is less efficient at part load and while its battery recharges.

Each model's own page, linked in the table, gives its full answer and data.

Which CIRRO models fit through a standard door?

A standard 36 × 80-inch door clears about 34 × 79 in. Upright, model by model:

ModelUpright through the doorNarrow side, height
CIR360-1X60Yes, with little to spare in height23.6 in (599 mm) across, 78.7 in (1,999 mm) high
CIR360-2X60Yes, with little to spare in height23.6 in (599 mm) across, 78.7 in (1,999 mm) high
CIR360-3X60Yes, with little to spare in height23.6 in (599 mm) across, 78.7 in (1,999 mm) high
CIR360-4X60Yes, with little to spare in height23.6 in (599 mm) across, 78.7 in (1,999 mm) high
CIR360-5X60Yes, with little to spare in height23.6 in (599 mm) across, 78.7 in (1,999 mm) high
CIR360-6X60Yes, with little to spare in height23.6 in (599 mm) across, 78.7 in (1,999 mm) high
CIR600-1X100Yes, with little to spare in height31.5 in (800 mm) across, 78.7 in (1,999 mm) high
CIR600-2X100Yes, with little to spare in height31.5 in (800 mm) across, 78.7 in (1,999 mm) high
CIR600-4X100Yes, with little to spare in height31.5 in (800 mm) across, 78.7 in (1,999 mm) high
CIR600-5X100Yes, with little to spare in height31.5 in (800 mm) across, 78.7 in (1,999 mm) high
CIR600-6X100Yes, with little to spare in height31.5 in (800 mm) across, 78.7 in (1,999 mm) high
CIR800-7X100Yes, with little to spare in height31.5 in (800 mm) across, 78.7 in (1,999 mm) high
CIR800-8X100Yes, with little to spare in height31.5 in (800 mm) across, 78.7 in (1,999 mm) high
CIR1200-9X100No: needs an opening wider than 43.3 in43.3 in (1,100 mm) across
CIR1200-10X100No: needs an opening wider than 43.3 in43.3 in (1,100 mm) across
CIR1200-11X100No: needs an opening wider than 43.3 in43.3 in (1,100 mm) across
CIR1200-12X100No: needs an opening wider than 43.3 in43.3 in (1,100 mm) across
CIR1600-13X100No: needs an opening wider than 39.4 in39.4 in (1,001 mm) across
CIR1600-14X100No: needs an opening wider than 39.4 in39.4 in (1,001 mm) across
CIR1600-15X100No: needs an opening wider than 39.4 in39.4 in (1,001 mm) across
CIR1600-16X100No: needs an opening wider than 39.4 in39.4 in (1,001 mm) across

On the way in, check corridors, elevators and the floor load (size section of each model's page).

Each model's own page, linked in the table, gives its full answer and data.

What supply does CIRRO need?

480/277 V three-phase, 4-wire, for every model of the series. Its power factor is 1.0, so each model gives its kVA rating in kW.

Answered on CIRRO

Communication and monitoring 1 question

How is CIRRO monitored over the network?

With the AEC SNMP-M network card, which reports the UPS status and alarms over SNMP to your monitoring software.

Answered on CIRRO

Warranty, service and maintenance 1 question

What warranty does CIRRO have?

3 years on UPS; 2 years on VRLA batteries, from start-up. Register the UPS with AEC after start-up.

Answered on CIRRO

Still a question?

Tell us the load, the voltage and the minutes you need: an AEC engineer answers.