Questions and answers

FERRUS SP RT: questions and answers

7 questions about the AEC FERRUS SP RT, from its series page and its 2 model pages, grouped by subject. Each answer is the one printed on its page; follow the link for the full data, the tables and the drawings.

Choosing, sizing and ordering 2 questions

What sizes does FERRUS SP RT come in?

6 to 10 kVA, in 2 models of the 2026 catalog for the US, from the FERSPRT6000-16X9 (6 kVA) to the FERSPRT10000-16X9 (10 kVA). The datasheet on this page gives every one.

Answered on FERRUS SP RT

What supply does FERRUS SP RT need?

120/240 V, split-phase, for every model of the series. Its power factor is 1.0, so each model gives its kVA rating in kW.

Answered on FERRUS SP RT

Runtime and batteries 1 question

What batteries does FERRUS SP RT use?

VRLA: each UPS comes with a 3U rack cabinet of 16 × 12 V 9 Ah blocks; more cabinets can be added. The battery bus is 192 V DC on every model.

Answered on FERRUS SP RT

Installation, size and connections 2 questions

What is the output current of each FERRUS SP RT model?

At full load, from the rating and the voltage:

ModelOutput currentWorked out as
FERSPRT6000-16X925.0 A on each line at 240 V6.0 kVA ÷ 240 V
FERSPRT10000-16X941.7 A on each line at 240 V10 kVA ÷ 240 V

Size the input breaker and the cables of each model from its installation manual and the local electrical code, not from this figure alone.

Each model's own page, linked in the table, gives its full answer and data.

How much heat does each FERRUS SP RT model give off?

At full load, model by model:

ModelHeatBTU/hEfficiency
FERSPRT6000-16X9466 W1,59092.8%
FERSPRT10000-16X9776 W2,65092.8%

Plan the room's cooling for a little more than that: each model is less efficient at part load and while its battery recharges.

Each model's own page, linked in the table, gives its full answer and data.

Communication and monitoring 1 question

How is FERRUS SP RT monitored over the network?

With the AEC SNMP-M network card, which reports the UPS status and alarms over SNMP to your monitoring software.

Answered on FERRUS SP RT

Warranty, service and maintenance 1 question

What warranty does FERRUS SP RT have?

3 years on UPS; 2 years on VRLA batteries, from start-up. Register the UPS with AEC after start-up.

Answered on FERRUS SP RT

Still a question?

Tell us the load, the voltage and the minutes you need: an AEC engineer answers.