Battery cabinets · Batteries and cabinets

BB8 Battery cabinet for UPS, 80 · 100 Ah, 2 strings

VRLA80 · 100 Ah, 2 stringsbattery cabinet for AEC UPS

The BB8 is a double floor-standing battery cabinet, 1400 × 800 × 1900 mm and 250 kg empty, for 40, 60 or 64 batteries of 12 V 80 or 100 Ah in two strings. For IST7 UPS up to 200 kVA and long backup times: one or two BB8 per UPS.

1400 × 800 × 1900 mmW × D × H
250 kg emptyWeight
40 · 60 · 64 × 80 / 100 AhBattery

Quick answers

BB8: quick answers

What it is
The BB8 is a double floor-standing battery cabinet, 1400 × 800 × 1900 mm and 250 kg empty, for 40, 60 or 64 batteries of 12 V 80 or 100 Ah in two strings.
Who it is for
For IST7 UPS up to 200 kVA and long backup times: one or two BB8 per UPS.
Supply and configuration
12 V VRLA AGM blocks · string split at the neutral (+, N, −)
Battery and backup
40 · 60 · 64 × 80 / 100 Ah
Size and weight
1400 × 800 × 1900 mm · 250 kg empty
Ordering code
BB8-10k … BB8-200k

Battery cabinets

What sets apart the BB8

The BB8 has two bays and two doors, with Q1 in the right bay. Most configurations hold two identical strings in parallel at Q1, each with its own +, N and − cables: 40 = 2 × 20 (±120 V), 60 = 2 × 30 (±180 V), 64 = 2 × 32 (±192 V). Measure each string separately at commissioning. The largest layout stores 76.8 kWh nominal, 153.6 kWh with two BB8.

Full, it weighs from 1195 kg (40 × 80 Ah) to 2215 kg (64 × 100 Ah), 1978 kg/m² on the floor. It is the only cabinet the catalogue pairs with the IST7-200, and the one in the example code IST7-160-64X100.

  • Against the BB7 (one size down): W × D × H 1400 × 800 × 1900 mm against 800 × 800 × 1900 mm; Weight, empty 250 kg against 160 kg; Front two doors with lock against door with lock; Battery levels 4 in two bays + Q1 against 4 + Q1 level; Internal frame 1350 × 765 mm, 2–5 levels against 745 × 765 mm, 2–5 levels.

Planning data

BB8: currents, breakers, cables, batteries

The rows and columns of the EMEA 2026 catalogue's and AEC manuals' tables that concern the BB8.

One design, four sizes

BB8 · One design, four sizes
UPS kWFuse F1/F2SizeCu mm²PE mm²BB8
1050 ANH001010●
2063 ANH001616●
40100 ANH002516●
60125 ANH003516●
80160 ANH007035●
100250 ANH112060●
120250 ANH112060●
160400 ANH2240120●
200400 ANH2240120●

Ventilation of the battery cabinet

BB8 · Ventilation of the battery cabinet
ExampleBB8 · 64 × 100 Ah
Q float1.92 m³/h
Q boost15.4 m³/h
Openings430 cm²

Installation

Installing the BB8: space, cables

Each figure with its source.

BB8 · installation
ItemFigureSource
Clearancesrear 100 mm, left 100 mm, right 100 mm; front and top: not givenBB user manual / drawings 2026-10-10 (MD-001, user manual §5)
Cable entryGland plate 100 × 100 mm in the roof (59 mm from the right, 99 mm from the rear)BB user manual / drawings 2026-10-10 (GA)
Operating temperature0 to 40 °C, best 20–25 °CAEC BB5–BB8 user manuals §3.3
Switches and terminalsQ1 in the right bay, its handle on the right door, about 1,668 mm up.BB user manual / drawings 2026-10-10 GA (read at scale)
DoorTwo leaves, hinged at the outer edgesBB user manual / drawings 2026-10-10 (GA)

Size and floor

How big it is

1400 × 800 × 1900 mm · 250 kg empty.

1.12 m²footprint
1.9 mheight

1.75 mFrontSide14008001900
AEC BB8, rendered from its 3D modelDrag to turn

In 3D

Look around the BB8

Technical data

Technical data BB8

Only this model's values, from the EMEA 2026 catalogue table.

BB8 · Technical data
Mechanical
W × D × H (mm)1400 × 800 × 1900
Weight, empty250 kg
Fronttwo doors with lock
Battery levels4 in two bays + Q1
Internal frame1350 × 765 mm, 2–5 levels
Cable entrytop gland 100 × 100 · bottom
Floor fixingthrough the feet
Batteries
Battery12 V 80 / 100 Ah
Configurations40 · 60 · 64 (×2 strings)
String voltage±120 … ±192 V
Electrical
Disconnect Q1 (3-pole)fuses on + and −
Fuses F1 / F263–400 A
UPS power (code)10–200 kW
Float · max. charge (per battery)13.5–13.7 V · 14.4 V
General
ColourRAL 9005
ProtectionIP20 · IP21–IP44 option
StandardsIEC/EN 62040-1 · EN IEC 62485-2 · CE
Warranty (cabinet)3 years

From the AEC BB5, BB6, BB7 and BB8 user manuals and installation manuals (Rev. 1.0, 2026). VRLA batteries have a 1-year warranty for 9 Ah blocks and 2 years for larger blocks. Specifications are subject to change without notice.

More technical detailsrange tables, ordering codes

Planning data

Battery cabinets range tables

Double cabinet, two strings in parallel

Two bays, two doors, Q1 on the right. Most configurations hold two identical strings in parallel at Q1, each with its own +, N and − cables.

BB8 · Double cabinet, two strings in parallel
BatteriesTotal kgUPS kVA
40 × 80 Ah119510–160
60 × 80 Ah165010–200
64 × 80 Ah173560–200
40 × 100 Ah149510–200
60 × 100 Ah209510–200
64 × 100 Ah221560–200

Ordering codes

Ordering codes BB8

Ordering codes BB8
CodeDescription
BB8-10k … BB8-200kBB8 for UPS up to 10 · 20 · 40 · 60 · 80 · 100 · 120 · 160 · 200 kW
OZ Power 12 V9 · 24 · 40 · 60 · 80 · 100 · 200 Ah · code on request

Questions

Questions about the BB8

Why does the BB8 hold two strings?

Two identical strings in parallel halve the power each battery delivers, so the same blocks give longer backup; the catalogue's sizing method notes that BB8 cabinets hold two strings as standard.

Which UPS can a BB8 serve?

IST7 from 10 to 200 kVA (codes BB8-10k to BB8-200k): 40 × 80 Ah for 10–160 kVA, 60 × 80 / 100 Ah for 10–200 kVA, 64 × 80 / 100 Ah for 60–200 kVA.

How big is the AEC BB8 and how much does it weigh?

The AEC BB8 measures 1400 × 800 × 1900 mm; weight: 250 kg empty (EMEA 2026 catalogue).

Talk to an AEC engineer

Tell us the load, the supply and the backup time you need for the AEC BB8: we answer with the model and the batteries that fit. AEC International sells through distributors in about 80 countries and an agency in every Italian region: ask AEC which one serves your area.