Battery cabinets · Batteries and cabinets
BBJ2 Battery cabinet for UPS, 3U · 16 × 9 Ah
The BBJ2 is a 3U rack battery cabinet for the IST3-J 6–10 kVA and the IST9 20 kVA: 438 × 500 mm, 10 kg empty, for up to sixteen 12 V 9 Ah batteries. For long backup on rack UPS of 6 to 20 kVA, with everything in one 19-inch rack.
Quick answers
BBJ2: quick answers
- What it is
- The BBJ2 is a 3U rack battery cabinet for the IST3-J 6–10 kVA and the IST9 20 kVA: 438 × 500 mm, 10 kg empty, for up to sixteen 12 V 9 Ah batteries.
- Who it is for
- For long backup on rack UPS of 6 to 20 kVA, with everything in one 19-inch rack.
- Supply and configuration
- 12 V 9 Ah VRLA AGM blocks, at the UPS battery voltage
- Battery and backup
- up to 16 × 12 V 9 Ah
- Size and weight
- 438 × 500 mm, 3U · 10 kg empty
- Ordering code
- BBJ2
Battery cabinets
What sets apart the BBJ2
The BBJ2 is the battery for the external-battery rack models: up to eight per IST3-J 6–10 kVA (16 to 128 batteries, codes IST3J-6/10-[n]X9) and up to ten per IST9 20 kVA (32 to 160 batteries, codes IST9-20-[n]X9). The catalogue's rack example is an IST3-J 6–10 kVA with two BBJ2 of 16 × 9 Ah each, 3U apiece, below the UPS.
On the IST3-J 6–10 kVA the battery is 192 V by default, 12 to 20 blocks of 12 V set through communication, drawing up to 39 A (6 kVA) or 65 A (10 kVA). On the IST9 the catalogue asks for the battery box below the UPS and a DC battery switch between battery and UPS.
In 3D
Look around the BBJ2
The BBJ2 is drawn beside the IST3-J 10 kVA it is sold with: the full 3D view opens on the pair, and its "Battery cabinet" menu changes how many and on which side.
Technical data
Technical data BBJ2
Only this model's values, from the EMEA 2026 catalogue table.
| Item | BBJ2 |
|---|---|
| For UPS | IST3-J 6–10 kVA, IST9, rack |
| W × D × H (mm) | 438 × 500 × 3U |
| kg, empty | 10 |
| Batteries (12 V) | up to 16 × 9 Ah |
Figures from the AEC UPS Catalogue EMEA 2026. 1.0, 2026). VRLA batteries have a 1-year warranty for 9 Ah blocks and 2 years for larger blocks. Specifications are subject to change without notice.
More technical detailsordering codes
Ordering codes
Ordering codes BBJ2
| Code | Description |
|---|---|
| BBJ · BBJ2 | Rack cabinets 2U (max 8 × 9 Ah) and 3U (max 16 × 9 Ah) |
| OZ Power 12 V | 9 · 24 · 40 · 60 · 80 · 100 · 200 Ah · code on request |
Catalogue
This range's pages of the catalogue.
Questions
Questions about the BBJ2
How many BBJ2 can an IST9 20 kVA take?
2, 4, 6, 8 or 10 cabinets, that is 32, 64, 96, 128 or 160 × 12 V 9 Ah (codes IST9-20-[n]X9). A DC battery switch goes between battery and UPS.
Where does the BBJ2 go, above or below the UPS?
Always below: battery cabinets are the heavy units of the rack. On the IST9 the optional distribution module goes above the UPS and the battery box below it.
How big is the AEC BBJ2 and how much does it weigh?
The AEC BBJ2 measures 438 × 500 mm, 3U; weight: 10 kg empty (EMEA 2026 catalogue).
Talk to an AEC engineer
Tell us the load, the supply and the backup time you need for the AEC BBJ2: we answer with the model and the batteries that fit. AEC International sells through distributors in about 80 countries and an agency in every Italian region: ask AEC which one serves your area.