Battery cabinets · Batteries and cabinets

BB6 Battery cabinet for UPS, 60 Ah

VRLA60 Ahbattery cabinet for AEC UPS

The BB6 is a square floor-standing battery cabinet, 800 × 800 × 1400 mm and 140 kg empty, for 30 to 40 batteries of 12 V 60 Ah. For IST7 UPS from 10 to 120 kVA that need more energy than a BB5 holds, in a cabinet not taller than 1400 mm.

800 × 800 × 1400 mmW × D × H
140 kg emptyWeight
30–40 × 12 V 60 AhBattery

Quick answers

BB6: quick answers

What it is
The BB6 is a square floor-standing battery cabinet, 800 × 800 × 1400 mm and 140 kg empty, for 30 to 40 batteries of 12 V 60 Ah.
Who it is for
For IST7 UPS from 10 to 120 kVA that need more energy than a BB5 holds, in a cabinet not taller than 1400 mm.
Supply and configuration
12 V VRLA AGM blocks · string split at the neutral (+, N, −)
Battery and backup
30–40 × 12 V 60 Ah
Size and weight
800 × 800 × 1400 mm · 140 kg empty
Ordering code
BB6-10k … BB6-120k

Battery cabinets

What sets apart the BB6

The BB6 has a hinged lockable door with the Q1 rotary handle on it, three battery shelves plus the Q1 level, and cables entering through a 100 × 100 mm top gland plate or the open base. Q1 has fuses on + and − (N switched), 50 to 250 A, for UPS up to 120 kW. Its largest layout stores 25.9 kWh nominal.

Loaded weights are 660 kg (30 × 60 Ah) to 760 kg (36 × 60 Ah); with 36 × 60 Ah the floor load is 1188 kg/m². It is the smallest cabinet the catalogue pairs with the IST7-80, -100 and -120.

  • Against the BB5 (one size down): W × D × H 800 × 800 × 1400 mm against 460 × 800 × 1400 mm; Weight, empty 140 kg against 110 kg; Front door with lock against screwed panel; Battery levels 3 + Q1 level against 4 + Q1 level; Internal frame 745 × 765 mm, 2–4 levels against 458 × 785 mm, 5 levels.
  • Against the BB7 (one size up): W × D × H 800 × 800 × 1400 mm against 800 × 800 × 1900 mm; Weight, empty 140 kg against 160 kg; Battery levels 3 + Q1 level against 4 + Q1 level; Internal frame 745 × 765 mm, 2–4 levels against 745 × 765 mm, 2–5 levels; Floor fixing through the feet against 4 × Ø9, centres 685 × 700.

Planning data

BB6: currents, breakers, cables, batteries

The rows and columns of the EMEA 2026 catalogue's and AEC manuals' tables that concern the BB6.

One design, four sizes

BB6 · One design, four sizes
UPS kWFuse F1/F2SizeCu mm²PE mm²BB6
1050 ANH001010●
2063 ANH001616●
40100 ANH002516●
60125 ANH003516●
80160 ANH007035●
100250 ANH112060●
120250 ANH112060●
160400 ANH2240120
200400 ANH2240120

Ventilation of the battery cabinet

BB6 · Ventilation of the battery cabinet
ExampleBB6 · 40 × 60 Ah
Q float0.72 m³/h
Q boost5.8 m³/h
Openings161 cm²

Installation

Installing the BB6: space, cables

Each figure with its source.

BB6 · installation
ItemFigureSource
Clearancesrear 100 mm, left 100 mm, right 100 mm; front and top: not givenBB user manual / drawings 2026-10-10 (MD-001, user manual §5)
Cable entryGland plate 100 × 100 mm in the roof (59 mm from the right, 99 mm from the rear)BB user manual / drawings 2026-10-10 (GA)
Operating temperature0 to 40 °C, best 20–25 °CAEC BB5–BB8 user manuals §3.3
Switches and terminalsQ1 DC fuse switch-disconnector in the top compartment, its rotary handle on the door, about 1,214 mm up.BB user manual / drawings 2026-10-10 GA (read at scale)
DoorOne leaf, hinged on the rightBB user manual / drawings 2026-10-10 (GA)

Size and floor

How big it is

800 × 800 × 1400 mm · 140 kg empty.

0.64 m²footprint
1.4 mheight

1.75 mFrontSide8008001400
AEC BB6, rendered from its 3D modelDrag to turn

In 3D

Look around the BB6

Technical data

Technical data BB6

Only this model's values, from the EMEA 2026 catalogue table.

BB6 · Technical data
Mechanical
W × D × H (mm)800 × 800 × 1400
Weight, empty140 kg
Frontdoor with lock
Battery levels3 + Q1 level
Internal frame745 × 765 mm, 2–4 levels
Cable entrytop gland 100 × 100 · bottom
Floor fixingthrough the feet
Batteries
Battery12 V 60 Ah
Configurations30–40
String voltage±180 … ±240 V
Electrical
Disconnect Q1 (3-pole)fuses on + and −
Fuses F1 / F263–160 A
UPS power (code)10–100 kW
Float · max. charge (per battery)13.5–13.7 V · 14.4 V
General
ColourRAL 9005
ProtectionIP20 · IP21–IP44 option
StandardsIEC/EN 62040-1 · EN IEC 62485-2 · CE
Warranty (cabinet)3 years

From the AEC BB5, BB6, BB7 and BB8 user manuals and installation manuals (Rev. 1.0, 2026). VRLA batteries have a 1-year warranty for 9 Ah blocks and 2 years for larger blocks. Specifications are subject to change without notice.

More technical detailsrange tables, ordering codes

Planning data

Battery cabinets range tables

Square cabinet, 60 Ah batteries

An 800 × 800 mm footprint with a hinged door and a door-mounted handle for Q1. Three battery shelves plus the Q1 level; frames with 2, 3 or 4 levels suit the battery size.

BB6 · Square cabinet, 60 Ah batteries
BatteriesTotal kgUPS kVA
30 × 60 Ah66010–100
32 × 60 Ah69510–100
34 × 60 Ah73010–100
36 × 60 Ah76010–100

Ordering codes

Ordering codes BB6

Ordering codes BB6
CodeDescription
BB6-10k … BB6-120kBB6 for UPS up to 10 · 20 · 40 · 60 · 80 · 100 · 120 kW; 2 fuse holders
OZ Power 12 V9 · 24 · 40 · 60 · 80 · 100 · 200 Ah · code on request

Questions

Questions about the BB6

Which UPS can use a BB6?

IST7 of 10, 20, 30, 40, 60, 80, 100 and 120 kVA, with codes BB6-10k to BB6-120k that set the fuses (50 to 250 A) and cables for the UPS power.

What does a full BB6 weigh?

660 kg with 30 × 60 Ah, 695 kg with 32, 730 kg with 34 and 760 kg with 36, on an 800 × 800 mm footprint. Check the floor: 1188 kg/m² with 36 × 60 Ah.

How big is the AEC BB6 and how much does it weigh?

The AEC BB6 measures 800 × 800 × 1400 mm; weight: 140 kg empty (EMEA 2026 catalogue).

Talk to an AEC engineer

Tell us the load, the supply and the backup time you need for the AEC BB6: we answer with the model and the batteries that fit. AEC International sells through distributors in about 80 countries and an agency in every Italian region: ask AEC which one serves your area.