Battery cabinets · Batteries and cabinets
BB6 Battery cabinet for UPS, 60 Ah
The BB6 is a square floor-standing battery cabinet, 800 × 800 × 1400 mm and 140 kg empty, for 30 to 40 batteries of 12 V 60 Ah. For IST7 UPS from 10 to 120 kVA that need more energy than a BB5 holds, in a cabinet not taller than 1400 mm.
Quick answers
BB6: quick answers
- What it is
- The BB6 is a square floor-standing battery cabinet, 800 × 800 × 1400 mm and 140 kg empty, for 30 to 40 batteries of 12 V 60 Ah.
- Who it is for
- For IST7 UPS from 10 to 120 kVA that need more energy than a BB5 holds, in a cabinet not taller than 1400 mm.
- Supply and configuration
- 12 V VRLA AGM blocks · string split at the neutral (+, N, −)
- Battery and backup
- 30–40 × 12 V 60 Ah
- Size and weight
- 800 × 800 × 1400 mm · 140 kg empty
- Ordering code
- BB6-10k … BB6-120k
Battery cabinets
What sets apart the BB6
The BB6 has a hinged lockable door with the Q1 rotary handle on it, three battery shelves plus the Q1 level, and cables entering through a 100 × 100 mm top gland plate or the open base. Q1 has fuses on + and − (N switched), 50 to 250 A, for UPS up to 120 kW. Its largest layout stores 25.9 kWh nominal.
Loaded weights are 660 kg (30 × 60 Ah) to 760 kg (36 × 60 Ah); with 36 × 60 Ah the floor load is 1188 kg/m². It is the smallest cabinet the catalogue pairs with the IST7-80, -100 and -120.
- Against the BB5 (one size down): W × D × H 800 × 800 × 1400 mm against 460 × 800 × 1400 mm; Weight, empty 140 kg against 110 kg; Front door with lock against screwed panel; Battery levels 3 + Q1 level against 4 + Q1 level; Internal frame 745 × 765 mm, 2–4 levels against 458 × 785 mm, 5 levels.
- Against the BB7 (one size up): W × D × H 800 × 800 × 1400 mm against 800 × 800 × 1900 mm; Weight, empty 140 kg against 160 kg; Battery levels 3 + Q1 level against 4 + Q1 level; Internal frame 745 × 765 mm, 2–4 levels against 745 × 765 mm, 2–5 levels; Floor fixing through the feet against 4 × Ø9, centres 685 × 700.
Planning data
BB6: currents, breakers, cables, batteries
The rows and columns of the EMEA 2026 catalogue's and AEC manuals' tables that concern the BB6.
One design, four sizes
| UPS kW | Fuse F1/F2 | Size | Cu mm² | PE mm² | BB6 |
|---|---|---|---|---|---|
| 10 | 50 A | NH00 | 10 | 10 | ● |
| 20 | 63 A | NH00 | 16 | 16 | ● |
| 40 | 100 A | NH00 | 25 | 16 | ● |
| 60 | 125 A | NH00 | 35 | 16 | ● |
| 80 | 160 A | NH00 | 70 | 35 | ● |
| 100 | 250 A | NH1 | 120 | 60 | ● |
| 120 | 250 A | NH1 | 120 | 60 | ● |
| 160 | 400 A | NH2 | 240 | 120 | |
| 200 | 400 A | NH2 | 240 | 120 |
Ventilation of the battery cabinet
| Example | BB6 · 40 × 60 Ah |
|---|---|
| Q float | 0.72 m³/h |
| Q boost | 5.8 m³/h |
| Openings | 161 cm² |
Installation
Installing the BB6: space, cables
Each figure with its source.
| Item | Figure | Source |
|---|---|---|
| Clearances | rear 100 mm, left 100 mm, right 100 mm; front and top: not given | BB user manual / drawings 2026-10-10 (MD-001, user manual §5) |
| Cable entry | Gland plate 100 × 100 mm in the roof (59 mm from the right, 99 mm from the rear) | BB user manual / drawings 2026-10-10 (GA) |
| Operating temperature | 0 to 40 °C, best 20–25 °C | AEC BB5–BB8 user manuals §3.3 |
| Switches and terminals | Q1 DC fuse switch-disconnector in the top compartment, its rotary handle on the door, about 1,214 mm up. | BB user manual / drawings 2026-10-10 GA (read at scale) |
| Door | One leaf, hinged on the right | BB user manual / drawings 2026-10-10 (GA) |
Size and floor
How big it is
800 × 800 × 1400 mm · 140 kg empty.
Drag to turnTechnical data
Technical data BB6
Only this model's values, from the EMEA 2026 catalogue table.
| Mechanical | |
|---|---|
| W × D × H (mm) | 800 × 800 × 1400 |
| Weight, empty | 140 kg |
| Front | door with lock |
| Battery levels | 3 + Q1 level |
| Internal frame | 745 × 765 mm, 2–4 levels |
| Cable entry | top gland 100 × 100 · bottom |
| Floor fixing | through the feet |
| Batteries | |
| Battery | 12 V 60 Ah |
| Configurations | 30–40 |
| String voltage | ±180 … ±240 V |
| Electrical | |
| Disconnect Q1 (3-pole) | fuses on + and − |
| Fuses F1 / F2 | 63–160 A |
| UPS power (code) | 10–100 kW |
| Float · max. charge (per battery) | 13.5–13.7 V · 14.4 V |
| General | |
| Colour | RAL 9005 |
| Protection | IP20 · IP21–IP44 option |
| Standards | IEC/EN 62040-1 · EN IEC 62485-2 · CE |
| Warranty (cabinet) | 3 years |
From the AEC BB5, BB6, BB7 and BB8 user manuals and installation manuals (Rev. 1.0, 2026). VRLA batteries have a 1-year warranty for 9 Ah blocks and 2 years for larger blocks. Specifications are subject to change without notice.
More technical detailsrange tables, ordering codes
Planning data
Battery cabinets range tables
Square cabinet, 60 Ah batteries
An 800 × 800 mm footprint with a hinged door and a door-mounted handle for Q1. Three battery shelves plus the Q1 level; frames with 2, 3 or 4 levels suit the battery size.
| Batteries | Total kg | UPS kVA |
|---|---|---|
| 30 × 60 Ah | 660 | 10–100 |
| 32 × 60 Ah | 695 | 10–100 |
| 34 × 60 Ah | 730 | 10–100 |
| 36 × 60 Ah | 760 | 10–100 |
Ordering codes
Ordering codes BB6
| Code | Description |
|---|---|
| BB6-10k … BB6-120k | BB6 for UPS up to 10 · 20 · 40 · 60 · 80 · 100 · 120 kW; 2 fuse holders |
| OZ Power 12 V | 9 · 24 · 40 · 60 · 80 · 100 · 200 Ah · code on request |
Catalogue
This range's pages of the catalogue.
Questions
Questions about the BB6
Which UPS can use a BB6?
IST7 of 10, 20, 30, 40, 60, 80, 100 and 120 kVA, with codes BB6-10k to BB6-120k that set the fuses (50 to 250 A) and cables for the UPS power.
What does a full BB6 weigh?
660 kg with 30 × 60 Ah, 695 kg with 32, 730 kg with 34 and 760 kg with 36, on an 800 × 800 mm footprint. Check the floor: 1188 kg/m² with 36 × 60 Ah.
How big is the AEC BB6 and how much does it weigh?
The AEC BB6 measures 800 × 800 × 1400 mm; weight: 140 kg empty (EMEA 2026 catalogue).
Talk to an AEC engineer
Tell us the load, the supply and the backup time you need for the AEC BB6: we answer with the model and the batteries that fit. AEC International sells through distributors in about 80 countries and an agency in every Italian region: ask AEC which one serves your area.