L6 Lithium · Batteries and cabinets

L6-40 LiFePO4 lithium battery cabinet, 40 Ah modules

Lithium40 AhLFP lithium battery cabinet

The L6-40 is a lithium iron phosphate battery cabinet for up to twenty hot-swappable 40 Ah modules: 41 kWh and 200 kW rated in 600 × 850 × 2000 mm. For AEC IST7 and IST6 UPS that need high power for a short time, 10 to 20 minutes, typically data centres riding through to a generator.

200 kW per cabinetRating
600 × 850 × 2000 mmW × D × H
965 ± 20 kg with 20 modulesWeight
41 kWh · 20 × 40 AhBattery

Quick answers

L6-40: quick answers

What it is
The L6-40 is a lithium iron phosphate battery cabinet for up to twenty hot-swappable 40 Ah modules: 41 kWh and 200 kW rated in 600 × 850 × 2000 mm.
Who it is for
For AEC IST7 and IST6 UPS that need high power for a short time, 10 to 20 minutes, typically data centres riding through to a generator.
Supply and configuration
240 / ±240 / 480 V DC
Battery and backup
41 kWh · 20 × 40 Ah · 10 / 20 min
Size and weight
600 × 850 × 2000 mm · 965 ± 20 kg with 20 modules
Ordering code
L6-40 cabinet, M or M1, master or slave · code on request

L6 Lithium

What sets apart the L6-40

The 40 Ah module uses 6C cells, the highest discharge rate of the three: sixteen LFP cells in series give 51.2 V and 2.05 kWh per module, and each module's DC/DC converter delivers 10 kW. A full cabinet of twenty modules gives 41 kWh and runs 10 minutes at its 200 kW rating. That makes the L6-40 the module for short, high-power backup.

AEC's sizing tables give, for 10 minutes, one module per 10 kW of UPS power up to a full cabinet at 200 kW and four cabinets (80 modules) at 800 kW; for 20 minutes, twice as many. The figures already hold a 10% reserve and 95% battery and inverter efficiency. Version M1, with one battery breaker, is for UPS below 100 kVA and backup within 30 minutes (955 kg full).

  • Against the L6-50 (one size up): Nominal capacity 41 kWh against 58 kWh; Capacity · cell discharge rate 40 Ah · 6C against 50 Ah · 4C; Rated voltage · energy 51.2 V · 2.05 kWh against 57.6 V · 2.88 kWh; Weight 36 ± 1 kg against 37 ± 1 kg; Weight with full modules 965 ± 20 kg (M1: 955) against 985 ± 20 kg (M1: 975).

Planning data

L6-40: currents, breakers, cables, batteries

The rows and columns of the EMEA 2026 catalogue's and AEC manuals' tables that concern the L6-40.

One footprint, two module sizes

L6-40 · One footprint, two module sizes
ModuleEnergy per cabinetRated power per cabinet
40 Ah41 kWh200 kW

Two capacities, one drawer size

L6-40 · Two capacities, one drawer size
Item40 Ah · 6C
CellsLFP, 3.2 V · 18 in series
Module voltage57.6 V
Energy per module2.05 kWh
Cell discharge rate6C
DC/DC output240 / ±240 / 480 V · 10 kW
Current unbalance≤ 3%
Full cabinet, 20 modules41 kWh · 10 min at rated power
Size (W × D × H)223 × 665 × 152 mm
Weight36 ± 1 kg
Noise58 dB

Installation

Installing the L6-40: space, cables

Each figure with its source.

L6-40 · installation
ItemFigureSource
Clearancesfront 800 mm, rear 800 mm, left 0 mm, right 0 mm, top 500 mmL6 user manual App. A; EMEA 2026 catalogue p.177–178; EMEA 2026 catalogue p.177
Cable entryDC cables from the topEMEA 2026 catalogue p.177
Operating temperature0 to 40 °C, best 20–30 °CL6 user manual App. A; EMEA 2026 catalogue p.177
Switches and terminalsBattery breakers behind the front door; 10" touch screen on the master's door.EMEA 2026 catalogue p.177
DoorOne leaf, hinged on the rightEMEA 2026 catalogue p.177
Module withdrawal665 mm in front of the cabinet to withdraw a moduleEMEA 2026 catalogue p.177–178

Size and floor

How big it is

600 × 850 × 2000 mm · 965 ± 20 kg with 20 modules.

0.51 m²footprint
1,892 kg/m²floor load
2 mheight

Floor load = weight ÷ footprint (965 kg).

1.75 mFrontSide6008502000
AEC L6-40, rendered from its 3D modelDrag to turn

In 3D

Look around the L6-40

Technical data

Technical data L6-40

Only this model's values, from the EMEA 2026 catalogue table.

L6-40 · Technical data
Cabinet
Nominal capacity41 kWh
Max. modules per cabinet20
Rated output power (discharge)200 kW
Rated output voltage (discharge)240 / ±240 / 480 V DC (three output systems)
Rated input voltage (charge)265 / ±265 / 530 V DC
Cell charge currentmax. 40 A, default 20 A
Discharge overload125–135%: 1 min · 135–150%: 30 s · > 150%: 500 ms
Current unbalance (module / cabinet)≤ 3%
Max. cabinets in parallel15
SOC · SOHmodule SOC accuracy ≥ 95% · SOH estimate accuracy ≥ 90%
Functionsdischarge SOC balance, battery cold start, self-start after power recovery, EPO, module-level fire control, cell insulation detection
Protectionover-temperature, over-current, short circuit, battery over- and under-voltage, low SOC
Module
Capacity · cell discharge rate40 Ah · 6C
Rated voltage · energy51.2 V · 2.05 kWh
Cell cycle life5,000 cycles at 50% depth of discharge
DC/DC output per module10 kW
Size (W × D × H)223 × 665 × 152 mm
Weight36 ± 1 kg
General
CommunicationTCP/IP, RS485 (CAN reserved)
Display10-inch touch screen (master cabinet) · indicators (slave cabinet)
Operating · storage temperature0 … +40 °C · −10 … +45 °C
Humidity · altitude5–95% non-condensing · < 4000 m, derating above 2000 m (IEC 62040-3)
Noise · protection< 65 dB · IP20 · battery-side overvoltage level 2
Cabinet size (W × D × H)600 × 850 × 2000 mm
Weight with full modules965 ± 20 kg (M1: 955)
L6-40 · Models
ItemL6-40
Module capacity40 Ah
Cell discharge rate6C
Modules per cabinet20
Energy per cabinet41 kWh
Rated power per cabinet200 kW
Typical backup10 / 20 min

Cabinet energy and other cabinet and system data from the L6 user manual; module voltage, energy and DC/DC power from AEC lithium documentation. Specifications are subject to change without notice.

More technical detailsrange tables, ordering codes

Planning data

L6 Lithium range tables

10 and 20 minutes

Cabinets and modules for each UPS power (cabinets · modules), from the L6 sizing table (2026): new modules, 95% battery and inverter efficiency, the 10% reserve included, never fewer modules than carry the UPS rating.

L6-40 · 10 and 20 minutes
UPS kW10 min20 min
≤ 601 · 61 · 12
≤ 801 · 81 · 16
≤ 1001 · 101 · 20
≤ 2001 · 202 · 40
≤ 3002 · 303 · 60
≤ 4002 · 404 · 80
≤ 5003 · 505 · 100
≤ 6003 · 606 · 120
≤ 8004 · 808 · 160

Ordering codes

Ordering codes L6-40

Ordering codes L6-40
CodeDescription
L6-40 cabinetCabinet for up to 20 × 40 Ah modules, master (touch screen) or slave (indicators), M or M1. Code on request.
Modules40 Ah · 50 Ah · 100 Ah lithium modules, hot-swappable. Code on request.
L6-C-2000 · L6-C-4000Combiner cabinet: L6-C-2000 (up to 4 cabinets) · L6-C-4000 (up to 8 cabinets). Code on request.
AccessoriesNetworking device · blank panels · in-row rear frame. Code on request.

Questions

Questions about the L6-40

How many L6-40 modules for 10 minutes at 100 kW?

From AEC's sizing table: one cabinet with 10 modules for UPS up to 100 kW at 10 minutes, and one cabinet with 20 modules for 20 minutes. The 10% reserve is included; AEC confirms the number for each project.

Can L6-40 modules be replaced with the UPS running?

Yes. A faulty module leaves the system on its own and the others keep supplying the UPS; it is replaced online in about 5 minutes. New and old modules work together, so capacity can also be added later.

How big is the AEC L6-40 and how much does it weigh?

The AEC L6-40 measures 600 × 850 × 2000 mm; weight: 965 ± 20 kg with 20 modules (EMEA 2026 catalogue).

Talk to an AEC engineer

Tell us the load, the supply and the backup time you need for the AEC L6-40: we answer with the model and the batteries that fit. AEC International sells through distributors in about 80 countries and an agency in every Italian region: ask AEC which one serves your area.