22 questions about the AEC OZ Power VRLA, from its range page and its 7 model pages, grouped by subject. Each answer is the one printed on its page; follow the link for the full data, the tables and the drawings.

Backup time and batteries 16 questions

How long do OZ Power batteries last?

The 9 and 24 Ah general purpose models have a design life of 6–8 years, and the 40–200 Ah long life models 12 years, in float service at 25 °C. Life halves about every 8 °C above 25 °C: about 43% of design life at 35 °C and 19% at 45 °C (OZ Power data).

Answered on OZ Power VRLA

What backup time do OZ Power batteries give?

In AEC's example of a 15 kW load on one string of 32 blocks, the backup is about 11 minutes with 24 Ah and 24 minutes with 40 Ah. It is 38 minutes with 60 Ah, 62 minutes with 80 Ah, 84 minutes with 100 Ah and 3.8 hours with 200 Ah; 9 Ah is not suitable for this load. Real backup depends on the UPS, temperature and battery age, and AEC checks every calculation.

Answered on OZ Power VRLA

How is a battery string sized for a UPS?

Divide the UPS load by the inverter efficiency and the number of blocks to get the power per block, then read the backup time in the constant power table at the UPS end voltage, usually 1.75 V per cell. Two identical strings in parallel halve the power per block for more backup.

Answered on OZ Power VRLA

Which AEC cabinets use which OZ Power battery?

The 9 Ah block is used inside AEC UPS and in BB1–BB5 and BBJ cabinets; 24 and 40 Ah in the BB5; 60 Ah in BB6 and BB7; 80 and 100 Ah in BB7 and BB8. The 200 Ah block is for large systems, on request.

Answered on OZ Power VRLA

How long does a 32-block string of 100 Ah last at 15 kW?

About 84 minutes in the catalogue's example (95% efficiency assumed, 25 °C, end voltage 1.75 V/cell, new batteries). AEC sizes each project on the real UPS and temperature.

Answered on OZ Power 12 V 100 Ah

How long does a 32-block string of 200 Ah last at 15 kW?

About 3.8 hours in the catalogue's example (95% efficiency assumed, 25 °C, 1.75 V/cell, new batteries). Real backup depends on the UPS, the temperature and battery age.

Answered on OZ Power 12 V 200 Ah

Is the 200 Ah safe to transport?

Yes: OZ Power AGM blocks are classed as non-dangerous goods for road, rail and air transport: the electrolyte is fully absorbed in the glass mat, with no free acid.

Answered on OZ Power 12 V 200 Ah

How long does a string of 24 Ah blocks last?

In the catalogue's example, 15 kW on one string of 32 blocks (95% efficiency assumed, 25 °C, new batteries) lasts about 11 minutes. Backup depends on the UPS, the temperature and battery age; AEC checks every calculation.

Answered on OZ Power 12 V 24 Ah

What charge voltage does the 24 Ah need?

Float at 25 °C: 13.5–13.8 V per battery, compensated −3 mV/°C/cell. Cycle use: 14.6–14.8 V, −4 mV/°C/cell. AEC UPS and cabinets charge in float mode.

Answered on OZ Power 12 V 24 Ah

How long does a 32-block string of 40 Ah last at 15 kW?

About 24 minutes in the catalogue's example (95% efficiency assumed, 25 °C, end voltage 1.75 V/cell, new batteries). Two identical strings in parallel halve the power per block and lengthen the backup.

Answered on OZ Power 12 V 40 Ah

Why is the 60 Ah rated 55 Ah at 10 hours?

The data sheet gives 55.0 Ah at the 10-hour rate and 58.2 Ah at 20 hours, to 1.80 V per cell at 25 °C. For UPS sizing the constant-power table (W per block at 1.75 V/cell) is what counts.

Answered on OZ Power 12 V 60 Ah

How is the backup of a 60 Ah string calculated?

Power per block = load ÷ (efficiency × number of blocks); read that power in the constant-power table at the UPS end voltage, usually 1.75 V/cell. At 15 kW on 32 blocks it is 493 W per block, about 38 minutes.

Answered on OZ Power 12 V 60 Ah

Which cabinets hold 80 Ah blocks?

The BB7 (28–36 blocks, one string) and the BB8 (40, 60 or 64 blocks, two strings). The BB6 also has 80 Ah layouts available, according to the catalogue.

Answered on OZ Power 12 V 80 Ah

How long does a 32-block string of 80 Ah last at 15 kW?

About 62 minutes in the catalogue's example (95% efficiency assumed, 25 °C, 1.75 V/cell, new batteries). Below 25 °C the available capacity drops; size with a reserve for ageing.

Answered on OZ Power 12 V 80 Ah

How long can a 9 Ah block be stored?

Self-discharge is below 3% a month at 25 °C: recharge every 6 months in storage, or when the open-circuit voltage falls below 12.6 V.

Answered on OZ Power 12 V 9 Ah

Can I mix new 9 Ah blocks with old ones?

No. The catalogue asks for the same model, capacity and batch across the whole string when batteries are replaced.

Answered on OZ Power 12 V 9 Ah

Installation, size and connections 4 questions

What are the dimensions and weights of the OZ Power range?

The 12 V 9 Ah block measures 151 × 65 × 94 mm and weighs 2.3 kg; the 200 Ah block 522 × 240 × 219 mm and 58.0 kg. In between, the 40 Ah is 197 × 166 × 170 mm (11.5 kg) and the 100 Ah 328 × 172 × 215 mm (28.5 kg). Weights are approximate, with ± 5% tolerance.

Answered on OZ Power VRLA

What charging voltage and temperatures do OZ Power batteries need?

At 25 °C, float charge is 13.5–13.8 V per battery (−3 mV/°C/cell) and cycle charge 14.6–14.8 V (−4 mV/°C/cell), with charge current up to about 0.3 C. They discharge from −20 to 60 °C and charge from 0 to 50 °C, with the best life at 25 ± 5 °C.

Answered on OZ Power VRLA

What does a cabinet of 100 Ah blocks weigh?

A BB7 weighs 1095 to 1275 kg with 30–36 blocks; a BB8 weighs 1495, 2095 or 2215 kg with 40, 60 or 64 blocks. Check the slab: up to 1992 kg/m².

Answered on OZ Power 12 V 100 Ah

OZ Power VRLA: how big is each model and how much does it weigh?

Width × depth × height and weight, model by model:

ModelSizeWeight
OZ Power 12 V 9 Ah151 × 65 × 94 mm2.3 kg
OZ Power 12 V 24 Ah166 × 175 × 125 mm7.0 kg
OZ Power 12 V 40 Ah197 × 166 × 170 mm11.5 kg
OZ Power 12 V 60 Ah230 × 138 × 211 mm16.5 kg
OZ Power 12 V 80 Ah260 × 169 × 211 mm22.0 kg
OZ Power 12 V 100 Ah328 × 172 × 215 mm28.5 kg
OZ Power 12 V 200 Ah522 × 240 × 219 mm58.0 kg

Size and weight from the EMEA 2026 catalogue.

Each model's own page, linked in the table, gives its full answer and data.

Warranty, service and maintenance 2 questions

Do OZ Power batteries need maintenance?

No topping up: they are sealed AGM batteries in which 99% of the gas recombines into water, with the electrolyte absorbed in the glass mat and no free acid. Self-discharge is below 3% per month at 25 °C, so they can be stored up to 6 months before recharging.

Answered on OZ Power VRLA

How long do 40 Ah blocks last in service?

The design life is 12 years in float at 25 °C. Life halves about every 8 °C above that: about 43% of design life at 35 °C, 19% at 45 °C (OZ Power data). Keep the battery room at 25 ± 5 °C.

Answered on OZ Power 12 V 40 Ah

Still a question?

Tell us the load, the supply and the backup time you need: AEC answers with the model and the batteries.