3/1 · 10 to 40 kVA

3/1 UPS: three-phase in, single-phase out

A 3/1 UPS takes a 400 V three-phase supply and feeds the load on one 230 V phase. It is used where the load is single-phase but too large for a single-phase supply: the input current is shared by three phases, the output stays one circuit. AEC builds it from 10 to 40 kVA, in three ranges.

AEC IST9AEC All-in-OneAEC IST7 10–40

Comparison

Which of the three for your load?

From each range's data in the EMEA 2026 catalogue. On all three the single-phase output is 220, 230 or 240 V.

AEC 3/1 UPS side by side
RangeRatings in 3/1Form, size and weightHow 3/1 is setWhen to choose it
IST910, 15, 20, 30, 40 kVA19-inch rack, 3U: 438 × 535 × 130 mm, 18.4 kg (10–20 kVA); 438 × 720 × 130 mm, 34.1 kg / 34.2 kg (30–40 kVA)The mode is set with connector jumpers on the rear terminals and on the touchscreen.When the UPS goes into a rack.
IST7 10–4010, 20, 30, 40 kVATower: 250 × 806 × 880 mm, 64 kg (10–20 kVA); 300 × 842 × 1250 mm, 102.5 kg (30–40 kVA)Wiring, the optional connector jumpers, the screen and, on 30–40 kVA, the mode connector.When a floor-standing tower is wanted, also with the batteries in the cabinet (S models).
All-in-One20 kVAFootprint 600 × 1000 mm (W × D); height 1110 mm on castors, 1000 mm without castors.As the IST9 20 kVA inside it.When UPS, switches and lithium battery must arrive as one cabinet: 15 to 60 minutes at 20 kW, by the number of modules.

IST9

How a unit is changed from 3/3 to 3/1

10–20 kVA work in 3/3, 3/1 or 1/1 mode; 30–40 kVA in 3/3 or 3/1 mode. The mode is set with connector jumpers on the rear terminals and on the touchscreen.

  • 3/1 mode: three in, one out (10–40 kVA).
  • Connector jumpers, 10–20 kVA: four jumper types (types 1–2 two-pin, 3–4 three-pin) for 3/3, 3/1 or 1/1 mode.
  • Connector jumpers, 30–40 kVA: one 3-pin jumper type, used only in 3/1 mode; it short-circuits the three-phase bypass input and the three-phase output terminals.
  • Set on the screen: work mode on the System management page. Output 3W + N + PE, settable to 1W + N + PE; input 3W + N + PE (on 10–20 kVA settable to 1W + N + PE).

IST7 10–40

In 3/1 the output carries all the current on one phase

Single-phase bypass and output carry up to three times the phase current: neutral and output cables are larger.

IST7 10–40: Single-phase output · 3/1 and 1/1
ModelAC input (A) (3/1)Bypass input (A)AC output (A)Bypass · output breakerN, bypass, output (mm²)PE (mm²)
IST7-1019.558.645.680 A 1P · 80 A 1P162 × 10
IST7-2035.5106.490.9100 A 3P · 100 A 3P252 × 10
IST7-3065.7197.1136.4250 A 1P · 200 A 1P2 × 2525
IST7-4081.7245.0181.8300 A 1P · 250 A 1P2 × 2525

Input breaker and input live cable as 3/3. 1/1 on 10–20 kVA: input 58.6 A (10) and 106.4 A (20), cables 16 and 25 mm².