Battery sets · 10 or 15 years · no prices

Lithium or VRLA: how many battery sets in 10 or 15 years?

Over 15 years at 25 °C a UPS needs 2–3 sets of OZ Power 9 or 24 Ah VRLA blocks (6–8-year design life) or 2 sets of 40–200 Ah blocks (12 years); at 35 °C that becomes 4–5 and 3. On the lithium side IST8 is given up to 8 years, the All-in-One cells more than 10. Set your own years and room below.

Your count

Years, room temperature, battery

Type the temperature in °C or °F; a decimal comma is read too. The answer and its working update as you change a value, and the page address keeps them, so you can share a link.

15 years
= 95 °F

VRLA at 35 °C (95 °F): 3–4 years. The design life at 25 °C is 6–8 years; above 25 °C it halves for about every 10 °C, so 50% of it is left.

Over 15 years: 4–5 sets of VRLA blocks, 3–4 replacements. Sets = years ÷ life, rounded up: 15 ÷ 4 = 3.75 · 15 ÷ 3 = 5.

All-in-One (LFP cells): at most 2 sets over 15 years. From: more than 10 years and 5,000 cycles at 50% depth of discharge, EMEA 2026 data. The data give no change of the lithium life with temperature.

Each VRLA replacement is a site visit, a string out of service while the blocks are changed, and a full set of lead-acid blocks to recycle.

Worked out

10 and 15 years at 25 °C and 35 °C

The same rule as the calculator, for the cases asked most. Where the life is a range of years, so is the count: the longer life gives the fewest sets, the shorter one the most.

Battery sets over 10 and 15 years, VRLA against lithium
VRLA · Years · Battery roomVRLA lifeVRLA setsVRLA replacementsAll-in-One (LFP cells)IST8 (built-in battery)L6 cabinet
9–24 Ah (6–8 years)
10 years, 25 °C (77 °F)
6–8 years21at most 1at least 2cycles only
9–24 Ah (6–8 years)
10 years, 35 °C (95 °F)
3–4 years3–42–3at most 1at least 2cycles only
9–24 Ah (6–8 years)
15 years, 25 °C (77 °F)
6–8 years2–31–2at most 2at least 2cycles only
9–24 Ah (6–8 years)
15 years, 35 °C (95 °F)
3–4 years4–53–4at most 2at least 2cycles only
40–200 Ah (12 years)
10 years, 25 °C (77 °F)
12 years10at most 1at least 2cycles only
40–200 Ah (12 years)
10 years, 35 °C (95 °F)
6 years21at most 1at least 2cycles only
40–200 Ah (12 years)
15 years, 25 °C (77 °F)
12 years21at most 2at least 2cycles only
40–200 Ah (12 years)
15 years, 35 °C (95 °F)
6 years32at most 2at least 2cycles only

Each replacement

What a VRLA replacement means on site

A visit by a technician. The string out of service while its blocks are changed: until the new blocks are in, that string gives the UPS no backup. A full set of lead-acid blocks to send for recycling. L6 and All-in-One modules are changed one at a time with the system running.

Same rating, same 2U

Weight and backup of two 3 kVA UPS

IST8 and IST3-J 3 kVA, EMEA data
ModelBattery insideBackup timeWeightW × D × H
IST8-3LFP lithium12 min at full load, 3,000 W (AEC data; the catalogue prints 11 min without a load)16.1 kg438 × 570 × 87 mm (2U)
IST3-J 3 kVAVRLA3 min at full load, 2,700 W26 kg438 × 572 × 86 mm (2U)

Both times are at full load, but the loads differ: 3,000 W on the IST8-3, 2,700 W on the IST3-J 3 kVA. The data give no time for the IST3-J at 3,000 W.

Method and sources

How the count is made, and its limits

VRLA: the design life in float at 25 °C of the OZ Power blocks in the EMEA 2026 catalogue, 6–8 years for 9 and 24 Ah, 12 years for 40–200 Ah, halved for about every 10 °C above 25 °C, the rule of AEC's user manuals. Below 25 °C the page keeps the 25 °C life. Lithium: what the EMEA 2026 data give each product, up to 8 years and 1,000 cycles for IST8, more than 10 years and 5,000 cycles at 50% DoD for the All-in-One cells; for L6 cycles only, so no count in years. Sets = years ÷ life, rounded up.

It is a rule of thumb, not a guarantee: real life depends on the number and depth of discharges, the charging, the maintenance and the room. Design life is the maker's figure in float; in service a block often lasts less. For the minutes of a VRLA string new and at end of life, use battery runtime.

Further reading: UPS batteries: VRLA or lithium · battery maintenance · every AEC lithium UPS

Questions

Questions people ask

How many times are VRLA batteries replaced in 15 years?

With OZ Power 9 or 24 Ah blocks (6–8-year design life at 25 °C), 2 or 3 sets, so 1 or 2 replacements; with 40–200 Ah blocks (12 years), 2 sets. At 35 °C the life halves: 4–5 sets and 3 sets.

Does lithium need replacing in 15 years?

It depends on the product: IST8 is given up to 8 years, so at least 2 sets in 15 years; the All-in-One cells more than 10 years, so at most 2 sets. For L6 the data give 5,000 cycles at 50% depth of discharge and no life in years.

Why does temperature matter so much for lead-acid?

As a rule of thumb a VRLA block's life halves for about every 10 °C above 25 °C. At 35 °C the count uses half the life: over 15 years the 40–200 Ah blocks go from 2 to 3 sets, the 9 and 24 Ah blocks from 2–3 to 4–5.

Is this count a guarantee?

No. It is a rule of thumb on design lives. Real life also depends on how often the battery discharges, how deep, the charging and the maintenance.

Where are the costs?

Not on this page. Give each set its price, add each visit and the cooling of the room, and set the total beside the price of the lithium.

Talk to an AEC engineer