LiFePO4 · single-phase, three-phase, modular
Lithium UPS: IST8, All-in-One 20 kVA and L6 cabinets
A lithium UPS stores its backup energy in lithium-ion cells instead of lead-acid blocks. AEC's lithium ranges for EMEA all use LFP cells: IST8, 1 to 3 kVA single-phase, with the battery in the 2U chassis; the All-in-One, a 20 kVA three-phase UPS with the lithium in the same cabinet; L6 cabinets of 41, 58 or 69 kWh for IST7 and IST6 up to 1,200 kVA.
EMEA 2026 data
Every AEC lithium configuration
Figures from each range's EMEA 2026 data; where a value is not published, the table says so.
| Range, model | Power | Voltage, phases | Where the battery sits | Chemistry, energy | Backup time | Recharge | Life, cycles | Warranty | Footprint, weight |
|---|---|---|---|---|---|---|---|---|---|
| IST8-1, IST8-2, IST8-3 | 1 / 2 / 3 kVA, 1,000 / 2,000 / 3,000 W | single-phase 208 / 220 / 230 / 240 V | built in, 2U rack or tower | LFP | 12 min at full load, 42 at half load (AEC data; the catalogue prints 11 min without a load) | not published (4 A charge) | up to 8 years, up to 1,000 cycles | 3 years UPS, 5 years lithium battery | 438 × 423 × 86 mm (1 kVA), 438 × 570 × 87 mm (2–3 kVA); 8.9 / 13.6 / 16.1 kg |
| All-in-One, 50 Ah modules | 20 kVA / 20 kW (IST9 20 kVA, 3U rack, inside) | three-phase 380 / 400 / 415 V, output 3/3 or 3/1 | in the same cabinet, 2 to 8 modules | LFP, 5.76–23.0 kWh | 15–60 min at 20 kW | not published (10 A charger) | cells: more than 10 years, 5,000 cycles at 50% DoD | 3 years UPS, 5 years lithium modules | cabinet 600 × 1000 × 1110 mm on castors; system 232 to 460 kg |
| All-in-One, 100 Ah modules | 20 kVA / 20 kW | three-phase 380 / 400 / 415 V, output 3/3 or 3/1 | in the cabinet, 4 modules | LFP, 23.0 kWh | 60 min at 20 kW, 200 min at 6 kW | not published | cells: more than 10 years, 5,000 cycles at 50% DoD | 3 years UPS, 5 years lithium modules | 600 × 1000 × 1110 mm; 352 kg |
| L6-40 | up to 200 kW discharge | 240 / ±240 / 480 V DC, for IST7 and IST6 | external cabinet, 20 × 40 Ah modules | LFP, 41 kWh | 10 min at rated power | not published | 5,000 cycles at 50% DoD | 5 years | 600 × 850 × 2000 mm; 965 kg |
| L6-50 | up to 200 kW discharge | 240 / ±240 / 480 V DC, for IST7 and IST6 | external cabinet, 20 × 50 Ah modules | LFP, 58 kWh | 14 min at rated power | not published | 5,000 cycles at 50% DoD | 5 years | 600 × 850 × 2000 mm; 985 kg |
| L6-100 | up to 60 kW discharge | 240 / ±240 / 480 V DC, for IST7 and IST6 | external cabinet, 12 × 100 Ah modules | LFP, 69 kWh | 57 min at rated power | not published | 5,000 cycles at 50% DoD | 5 years | 600 × 850 × 2000 mm; 810 kg |
DoD: depth of discharge. L6 backup times are at the cabinet's rated discharge power; for your own load use the backup time tool.
By load
Which one carries your load?
Up to 3 kW single-phase in a rack: IST8. 20 kW three-phase with the lithium inside, on castors: the All-in-One. Above that, an IST7 or IST6 three-phase or modular UPS with L6 cabinets. The UPS finder proposes the range and the rating; the "Lithium or VRLA" tool counts the battery sets over the years of service you plan.
20 kVA three-phase with the lithium built in
The All-in-One is a 600 × 1000 × 1110 mm cabinet holding the IST9 20 kVA (3/3 or 3/1), the distribution with maintenance bypass and the LFP modules. With 2 × 50 Ah the system weighs 232 kg, with 8 it weighs 460; with 4 × 100 Ah it gives 200 minutes at 6 kW. Efficiency up to 96% in double conversion, 99% in ECO.
Rack
Lithium in a 19-inch rack
IST8 carries its LFP battery in the same 2U chassis, 1 to 3 kVA, AC/AC efficiency up to 93%. It runs from 0 to 60 °C (best 0–40 °C).
Three-phase and modular
L6 cabinets beside IST7 and IST6
L6 takes 40, 50 or 100 Ah modules, hot-swappable, with a three-layer BMS; up to 15 cabinets in parallel. These AEC UPS also work with external lithium batteries, as their data state:
| Range | Power | Battery, from the range's data |
|---|---|---|
| IST9 | 10–40 kVA | lead-acid or the approved lithium system, through the RS485 protocol card |
| IST7 10–40 | 10–40 kVA | RS485 reserved for lithium battery communication |
| IST7 60–200 | 60–200 kVA | VRLA or lithium with the BMS card |
| IST7-T | 100–200 kVA | VRLA or lithium; with lithium also an energy-storage UPS |
| IST6-120 | 30–120 kVA | lead-acid or lithium with the BMS card |
| IST6 200–500 | 200–500 kVA | lithium with the BMS card, ±256 V nominal |
| IST6 400–1200 | 400–1,200 kVA | lithium with the BMS card, 512 V nominal |
The room
What changes in the room
Weight. A full L6-50 cabinet weighs 985 kg on 600 × 850 mm, about 1,931 kg/m² over its footprint: the figure for the structural engineer. The L6-100 weighs 810.
Temperature. The L6 cabinet runs from 0 to 40 °C; the All-in-One's batteries from 0 to 40 °C, 15–30 °C recommended; IST8 from 0 to 60 °C.
Fire safety and ventilation. The rules for lithium batteries in a room depend on the country and its authorities: this page does not interpret them. Battery room ventilation and UPS installation clearances have their own guides.
Further reading
The lithium guides
UPS batteries: VRLA or lithium · sizing L6 lithium batteries · UPS backup time · UPS sizing · LiFePO4 lithium
Questions
Questions people ask
What is a lithium UPS?
A UPS that stores its backup energy in lithium-ion cells instead of lead-acid blocks. AEC's lithium UPS use lithium iron phosphate cells (LFP, LiFePO4) with their battery management: inside the UPS on IST8, in the same cabinet on the All-in-One, in external L6 cabinets with IST7 and IST6.
Is there a 20 kVA three-phase UPS with the lithium built in?
Yes: the All-in-One, one 600 × 1000 mm cabinet on castors holding the IST9 20 kVA, the distribution breakers and 2 to 8 lithium modules of 50 Ah, or 4 of 100 Ah. It gives 15 to 60 minutes at 20 kW with the 50 Ah modules.
Which single-phase lithium UPS fits a rack?
IST8, 1 to 3 kVA in 2U, with the LFP battery inside: 12 minutes of backup at full load and 42 at half load in AEC's data, and an output of 208, 220, 230 or 240 V set from the panel.
How long do the lithium batteries last?
The EMEA 2026 data give IST8 up to 8 years and up to 1,000 cycles, the All-in-One cells more than 10 years and 5,000 cycles at 50% depth of discharge, the L6 cells 5,000 cycles at 50% DoD. No life in years is given for L6.
Do L6 cabinets fit my UPS?
They are designed for AEC IST7 and IST6 UPS, 6 to 1,200 kVA, with up to 15 cabinets in parallel. New and old modules work together, so capacity can be added over the years.
What warranty do they carry?
3 years on the UPS electronics and 5 years on the lithium batteries of IST8 and the All-in-One; 5 years on the L6 cabinets.
Talk to an AEC engineer
Tell us the load, the supply and the backup time you need: we answer with the model and the batteries that fit.