Operating guide

IST7 10–40 kVA operating guide

The three-phase IST7 of 10 to 40 kVA: a touch screen for readings and settings, two ON and two OFF keys for start and stop, and a maintenance bypass behind a cover. Every step names the manual's section and page.

AEC IST7 10–40

The display

The display, page by page.

The real screens, recorded from AEC's display simulator. Tap a screen to enlarge it. Keys and icons as in section 4.2 of the manual (page 49).

IST7 10–20 kVA

Normal operationMain page, inverter output: the energy flow runs from the mains through the rectifier (REC.) and the inverter (INV.) to the output, the battery kept charged. The bottom bar gives the output voltage of each phase and the frequency.
Mains inputMains information: voltage, current and frequency of the input. The mains icon on the main page turns red when the mains is abnormal.
OutputOutput information: voltage, current, load, active and apparent power, power factor and frequency.
BatteryBattery information: the charge or discharge current, the battery status (discharge, equalising or float charge), the remaining capacity and the remaining time.
Mains failure: on batteryMains failure: the mains block turns red and the battery feeds the inverter, the load without a break.
On bypassBypass output: the inverter is off and the load runs on the static bypass. This is the state after the inverter is switched off with a normal bypass.
Information menuInformation management: run information, history record, user log and device information.
Settings menuSetting management: system, battery, battery test, dry contacts, screen, password and device configuration. Settings change only after the administrator login, which AEC technical service gives.

IST7 30–40 kVA

Normal operationMain page, inverter output: the energy flow runs from the mains through the rectifier (REC.) and the inverter (INV.) to the output, the battery kept charged. The bottom bar gives the output voltage of each phase and the frequency.
Mains inputMains information: voltage, current and frequency of the input. The mains icon on the main page turns red when the mains is abnormal.
OutputOutput information: voltage, current, load, active and apparent power, power factor and frequency.
BatteryBattery information: the charge or discharge current, the battery status (discharge, equalising or float charge), the remaining capacity and the remaining time.
Mains failure: on batteryMains failure: the mains block turns red and the battery feeds the inverter, the load without a break.
On bypassBypass output: the inverter is off and the load runs on the static bypass. This is the state after the inverter is switched off with a normal bypass.
Information menuInformation management: run information, history record, user log and device information.
Settings menuSetting management: system, battery, battery test, dry contacts, screen, password and device configuration. Settings change only after the administrator login, which AEC technical service gives.

Keys and controls

ON + ON, 1 s
Both ON keys of the front panel together: start the UPS once the touch screen is lit.
OFF + OFF, 1 s
Both OFF keys together: shut the UPS down.
BATT. Start, 7 s
Cold start with no mains: hold the battery start key, then press both ON keys until a beep.
Home, information, settings
The icons on the left: back to the main page, information management, setting management.
Login
Settings change only after login. The common user level reads the parameters; the administrator level, from AEC technical service, sets them (§4.3).
Alarm and buzzer
The fault icon opens the current faults; the buzzer icon mutes or unmutes the buzzer. A continuous beep cannot be muted (§4.6–4.7).
ON/OFF icon
Starts or stops the UPS from the screen, after "Confirm to power on?" or "Confirm to power off?" (§4.8).

Passwords are not printed here: the settings pages need the administrator access that AEC technical service gives.

Procedures

Start-up, shutdown, bypass, maintenance bypass, battery test, battery care.

From the AEC-UM-IST7-10-40 Rev. 01 user manual. The link on each procedure opens the PDF on its page.

Checks before start-upWiring, earth, battery cabinet and load.Manual §5.1 · p. 76 · 4 steps
  1. Check that all connections are tight and the AC cable colours follow the standard.

  2. Check that the UPS is earthed and the voltage between neutral and earth is below 5 V AC.

  3. With a remote monitoring device, check the RS485 wiring; on long-backup models, the wiring to the battery cabinet.

  4. Check that the output has no short circuit and the load is within the UPS rating.

    Manual §5.1, p. 76

Start-upBreakers, both ON keys, then the loads.Manual §5.2 · p. 76 · 3 steps
  1. Close the mains, bypass and battery breakers.

    On the display: Normal operation
  2. When the touch screen lights up, press both ON keys on the front panel together for 1 s.

  3. After about 10 s, when the UPS runs steadily, switch on the loads.

    Caution Switch on the loads from the largest to the smallest, so that a large starting load does not trip the overload protection.

    Manual §5.2, p. 76

ShutdownLoads off, 10 minutes to cool, both OFF keys.Manual §5.3 · p. 76 · 3 steps
  1. Switch off the loads and let the UPS run without load for about 10 minutes to cool down.

  2. Press both OFF keys on the front panel together for 1 s.

  3. Open the battery, bypass and mains breakers.

    Manual §5.3, p. 76

Bypass modeWhen the UPS feeds the load from the bypass, and how it comes back.Manual §2.2 · p. 21 · 3 steps
  1. With a normal bypass voltage, the UPS feeds the load from the bypass while the inverter is off, or when a fault occurs while it is on (inverter overload, over-current surge, over-temperature).

    On the display: On bypass
  2. When the fault has cleared, the UPS returns to inverter output by itself.

  3. If the same fault occurs more than 5 times in a short time, the UPS stays on bypass until it is switched off: remove the cause and start it again with both ON keys.

    Manual §2.2, p. 21

Maintenance bypass and backService the UPS while the load stays supplied.Manual §2.1 · p. 11 · 4 steps
  1. Remove the maintenance breaker cover plate: its interlock switch opens, the UPS switches off the inverter and transfers to bypass.

  2. Switch on the maintenance bypass breaker, then switch off the input, bypass and output breakers. The load runs through the maintenance bypass and the UPS is isolated from its input and output.

  3. To return: switch on the input, bypass and output breakers in turn. When the touch screen shows the bypass output voltage, switch off the maintenance bypass breaker.

  4. Refit the cover plate, then press both ON keys to start the inverter.

    Caution The maintenance bypass circuit stays live. Work inside the UPS is for qualified personnel only.

    Manual §2.1, p. 11

Battery testStandard or deep test, from Setting management.Manual §4.5.3 · p. 65 · 3 steps
  1. Open Setting management, then Battery test (the page needs the administrator login from AEC technical service).

    On the display: Settings menu
  2. Choose a standard or a deep test; a running test can be cancelled.

  3. The page shows the test status, battery current, consumed capacity and test time.

    Manual §4.5.3, p. 65

Battery care (models with internal batteries)First charge, periodic discharge, long storage.Manual §5.6 · p. 78 · 3 steps
  1. Charge the battery for 10 hours before first use.

  2. Every 4 to 6 months discharge the battery until the UPS shuts down at low voltage, then recharge it; every 2 months in hot climates.

  3. If the UPS is not used for a long time, charge the battery for more than 10 hours every three months. Service life is generally 3 to 5 years.

    Manual §5.6, p. 78

Alarms

Alarms and what to check.

From Table 5-2 of the manual, page 79. If an alarm stays, or the cause is inside the UPS, call AEC service.

IST7 10–40 kVA: Alarms and what to check.
ShownBuzzerMeaning and what to check
EPOLong beepEmergency power off active: bypass and inverter outputs are off.
Mode faultLong beepThe mode set on the screen does not match the wiring: check the mains and bypass wiring and set the matching mode.
Maintenance bypass faultLong beepMaintenance bypass protection, inverter output off: check that the maintenance-bypass detection port on the rear panel is shorted.
Output faultLong beepCheck the output for a short circuit or overload.
Parallel mismatchesLong beepMode, voltage, frequency, bypass, power, battery number or other settings of this UPS differ from the rest of the parallel system.
Parallel cable faultLong or slow beepThe parallel cable is disconnected at both ends (long beep) or at one end (slow beep).
Auxiliary power supply failureLong beepInternal auxiliary supply failed: if it does not recover by itself, call service.
Fan failureUrgent beep (every 0.2 s)Check the fans for damage or obstruction.
No redundancySlow beep (every 2 s)The parallel system's load exceeds one UPS's full load: check the output load.
Mains abnormalLong beep, or 3 beeps every 10 sWrong phase sequence (long beep); or missing neutral, power failure, voltage or frequency out of range: check the mains input.
Bypass abnormalSlow beep (every 2 s)In mains mode, bypass voltage, frequency or phase sequence abnormal: check that the bypass breaker is closed and the wiring matches the mode.
Battery abnormalSlow or urgent beepSlow: battery over-voltage or charging fuse failure. Urgent: battery wiring fault, charger short circuit or under-voltage. Check the battery wiring and condition.
Rectifier or inverter abnormalUrgent or long beepUPS rectifier fault (urgent) or inverter fault (long): call AEC service.

Manual, Table 5-2, p. 79

Common symptoms.

Table 5-1 of the manual, page 79: simple checks before you call service.

Mains normal, but the UPS runs on battery and beeps intermittently

Check the contactors and terminals of the input circuit, whether the input voltage or frequency on the touch screen is outside the UPS range, and whether the mains input breaker is open (close it again).

The output stops as soon as the load is switched on

Severe overload or a short circuit on the output (often a faulty power strip or load). Or the loads were not started largest first: restart the UPS and, once it runs steadily, switch on the largest load first.

Long beep, fault icon on, UPS on bypass

Output overload: reduce the load. A short transfer to bypass when a load starts, with a return on its own, is normal. Or over-temperature: check that the air inlets and outlets are free and the room within its limits.

At a mains failure there is no output, or the UPS shuts down soon on low battery

Aged batteries with lost capacity, a charger fault, or a battery cable loose or not connected. Replacement is for authorised personnel.

Practice

The IST7 10–20 kVA display simulator.

The same display, before you stand in front of the UPS: the operating states and the main pages.

UPS state
IST7 10–20 kVA: Normal operation

IST7 10–20 kVA · the real display

Normal operation

Main pages
UPS state
IST7 30–40 kVA: Normal operation

IST7 30–40 kVA · the real display

Normal operation

Main pages