Operating guide
IST6 200–1200 kVA operating guide
The modular IST6 ranges 200–500 kVA, with 50 kW power modules, and 400–1200 kVA, with 100 kW power modules (its user manual is titled 600–1200 kVA): the checklist, start and stop, the maintenance bypass and the battery tests, from the touch screen and the switches. Where the two manuals differ, the step gives each range's own words. Every step names the manual's section and page.

The display
The display, page by page.
The real screens, recorded from AEC's display simulator. Tap a screen to enlarge it. Keys and icons as in section 5.2 of the manual (page 108 / 123).
IST6 modular
IST6 400–1200 kVA
Keys and controls
- ON combination, 3 s
- Starts the inverter when the power modules' run indicators flash green slowly; about 10 s later the system is on inverter.
- OFF combination, 3 s
- Stops the inverter: the inverter indicator goes off and the bypass indicator turns green.
- Inverter icon
- The same from the touch screen, with an OK step (§5.8).
- Ready switch
- On each power module and on the bypass module: locked (red) holds the module in the cabinet; unlocked (green) lets it be withdrawn.
- Buzzer
- The buzzer icon mutes or unmutes the alarm (§5.4).
- Passwords
- IST6 200–500 kVA: The touch screen asks for the power-on password at start-up, and settings need the administrator login: both come from AEC technical service and the manual.
IST6 400–1200 kVA: The touch screen asks for the startup password, and settings need the administrator login: both come from AEC technical service and the manual.
Passwords are not printed here: the settings pages need the administrator access that AEC technical service gives.
Procedures
Start-up, shutdown, bypass, maintenance bypass, battery test, emergency power off.
From the AEC-UM-IST6-200-500 Rev. 01 and AEC-UM-IST6-600-1200 Rev. 01 user manual. The link on each procedure opens the PDF on its page.
Checks before start-upThe manual's checklist, ticked before every first start.Manual §4.1.1 · p. 98 / 112 · 6 steps
The mains, bypass, output and maintenance bypass switches of the UPS are off, and so is the external battery switch.
The load is not inductive (motors, fans and air-conditioners stay on the mains), it is switched off and within the UPS rating.
No short circuit between live and neutral or live and earth at the UPS input, and none at the output.
With a multimeter, the AC voltage at the mains input terminals is within 187–280 V and the frequency within 40–60 Hz (50 Hz system); otherwise the UPS can only start from the battery.
The DC voltage at the battery input is above +11.5 V × the number of blocks on the positive pack and below −11.5 V × the number on the negative pack, with the right polarity.
The battery switch's auxiliary contact is wired to an input dry contact of the system monitoring card and set under Setting manage > Dry contact > Input.
IST6 200–500 kVA: Manual §4.1.1, p. 98 · IST6 400–1200 kVA: Manual §4.1.1, p. 112
Start-upFrom all switches off to the load on the inverter.Manual §4.1.2 · p. 98 / 112 · 7 steps
Set the ready switches of the bypass module and of every power module to the locked position (red: the module is locked in the cabinet).
Switch on the bypass switch, the mains switch and the external battery switch, one by one: the UPS powers up on bypass and the touch screen starts; enter the power-on password to reach the main page. (Cold start with no mains: switch on only the battery switch and hold the battery pre-start button for more than 3 s.)
Open the current fault page from the main page. If any fault alarm is shown, stop and call AEC technical support.
When the run indicators of all power modules are green and flash slowly, start the inverter: the ON button pair for 3 s, or the inverter icon on the main page and OK. About 10 s later the inverter indicator is green, the bypass indicator goes off and the system is on inverter.
Check on the main page that the system is in inverter mode and that the three-phase output voltage and frequency are normal.
IST6 200–500 kVA: Switch on the output switch and check with a multimeter: output voltage = system voltage ± 2 V, frequency = system frequency ± 0.1 Hz.
IST6 400–1200 kVA: Switch on the external output switch and check with a multimeter: output voltage = system voltage ± 2 V, frequency = system frequency ± 0.1 Hz.
Start the loads, the largest first.
IST6 200–500 kVA: Manual §4.1.2, p. 98 · IST6 400–1200 kVA: Manual §4.1.2, p. 112
ShutdownInverter off, then every switch open.Manual §4.1.3 · p. 100 / 114 · 4 steps
Switch off the load.
Stop the inverter: the OFF button pair for 3 s, or the inverter icon on the main page and OK. The inverter indicator goes off, the bypass indicator turns green.
IST6 200–500 kVA: Switch off the external battery switch, the mains switch, the bypass switch and the output switch, one by one.
IST6 400–1200 kVA: Switch off the external battery switch, the mains switch, the bypass switch and the output switch, one by one. With the optional distribution cabinet, open its switches too.
Wait until the touch screen and the panel's indicators are off: the UPS is completely shut down.
Caution With a normal bypass the system goes to bypass when the inverter stops; with an abnormal bypass it has no output. The load must be off or able to lose its supply.
IST6 200–500 kVA: Manual §4.1.3, p. 100 · IST6 400–1200 kVA: Manual §4.1.3, p. 114
Transfer to bypass and backPut the load on the static bypass without switching anything off.Manual §4.1.3 / 4.1.2 · p. 100 / 114 · 3 steps
Check on the main page that the bypass input is normal.
Stop the inverter (OFF button pair for 3 s, or the inverter icon and OK): the bypass indicator turns green and the load is on the static bypass.
To return, wait for the power modules' run indicators to flash green slowly and start the inverter (ON button pair for 3 s, or the inverter icon and OK).
Caution With an abnormal bypass, stopping the inverter leaves the load without supply: check the bypass first.
IST6 200–500 kVA: Manual §4.1.3 / 4.1.2, p. 100 · IST6 400–1200 kVA: Manual §4.1.3 / 4.1.2, p. 114
Transfer to maintenance bypassService the UPS while the load stays supplied. Qualified personnel only.Manual §6.1.1 · p. 133 / 149 · 4 steps
Stop the inverter (OFF button pair for 3 s, or the inverter icon and OK); the system goes to bypass.
IST6 200–500 kVA: Make sure the inverter is off, then switch on the maintenance bypass switch. The touch screen shows "Maintenance bypass open".
IST6 400–1200 kVA: Make sure the inverter is off, then switch on the external maintenance bypass switch. The touch screen shows "Maintenance bypass open".
IST6 200–500 kVA: Switch off the external battery switch, the mains switch, the bypass switch and the output switch, one by one.
IST6 400–1200 kVA: Switch off the external battery switch, the mains switch, the bypass switch and the output switch, one by one. With the optional distribution cabinet, open its switches too.
Wait until the touch screen and the indicators are off, then about 15 minutes before starting the maintenance.
Caution IST6 200–500 kVA: Never switch on the output switch in maintenance bypass. The input and output copper bars stay live: touching them can cause an electric shock.
IST6 400–1200 kVA: Never switch on the external output switch in maintenance bypass. The input and output copper bars stay live: touching them can cause an electric shock.IST6 200–500 kVA: Manual §6.1.1, p. 133 · IST6 400–1200 kVA: Manual §6.1.1, p. 149
Back from maintenance bypass to the inverterThe load goes back to the UPS without a break.Manual §6.1.2 · p. 134 / 150 · 6 steps
Switch on the bypass switch and the mains switch, one by one.
Set the bypass module's ready switch to the locked position and switch on the external battery switch (first check that the touch screen does not show "Not allow to connect battery").
IST6 200–500 kVA: Switch on the output switch.
IST6 400–1200 kVA: Switch on the external output switch.
IST6 200–500 kVA: When the panel's bypass indicator is green, switch off the maintenance bypass switch: the maintenance bypass message disappears and the buzzer stops.
IST6 400–1200 kVA: When the panel's bypass indicator is green, switch off the external maintenance bypass switch: the maintenance bypass message disappears and the buzzer stops.
Set the ready switches of every power module to the locked position.
When the power modules' run indicators flash green slowly, start the inverter (ON button pair for 3 s, or the inverter icon and OK). About 10 s later the system is on inverter.
Caution Make sure the bypass input is normal before you start.
IST6 200–500 kVA: Manual §6.1.2, p. 134 · IST6 400–1200 kVA: Manual §6.1.2, p. 150
Battery testA standard (shallow) or a deep discharge test, with the mains present.Manual §6.4 · p. 145 / 160 · 4 steps
Standard test: under Setting manage > Battery setting, set the battery test time to 10 (minutes).
Under Setting manage > Battery test, start the standard test.
Deep test: under Setting manage > Battery test, start the deep test; it discharges the battery to the under-voltage alarm point and tells more about its health.
Battery settings are in Setting manage, which needs the administrator login from AEC technical service.
Caution The test needs a normal mains input, the battery connected and on float charge, and at least 15 % load. It stops by itself if the battery reaches its alarm point, the mains falls below 0.9 × rated, the output is off or overloaded, or an alarm appears.
IST6 200–500 kVA: Manual §6.4, p. 145 · IST6 400–1200 kVA: Manual §6.4, p. 160
Emergency power off and recoveryOnly in an emergency: the load loses its supply.Manual §4.1.4–4.1.5 · p. 101 / 115 · 4 steps
Trigger EPO from the EPO dry contacts of the system monitoring card (the external EPO button): the touch screen shows EPO protection and the buzzer keeps sounding.
To recover, make sure the EPO dry contacts are back in the non-emergency state.
Switch off the external battery switch, the mains, bypass and output switches, and wait until the touch screen and indicators are off.
Start the UPS again as in the start-up procedure: the EPO state is cleared.
Caution After EPO the UPS has no output. In maintenance bypass the output stays live even after EPO.
IST6 200–500 kVA: Manual §4.1.4–4.1.5, p. 101 · IST6 400–1200 kVA: Manual §4.1.4–4.1.5, p. 115
What differs between the two ranges.
The two manuals give the same procedures; this table lists every point where their words, sections or pages differ.
| Point | IST6 200–500 kVA | IST6 400–1200 kVA |
|---|---|---|
| User manual | AEC-UM-IST6-200-500 Rev. 01 | AEC-UM-IST6-600-1200 Rev. 01 |
| The display: section, page | §5.2, p. 108 | §5.2, p. 123 |
| Key: Passwords | The touch screen asks for the power-on password at start-up, and settings need the administrator login: both come from AEC technical service and the manual. | The touch screen asks for the startup password, and settings need the administrator login: both come from AEC technical service and the manual. |
| Checks before start-up: section, page | §4.1.1, p. 98 | §4.1.1, p. 112 |
| Start-up: section, page | §4.1.2, p. 98 | §4.1.2, p. 112 |
| Start-up, step 6 | Switch on the output switch and check with a multimeter: output voltage = system voltage ± 2 V, frequency = system frequency ± 0.1 Hz. | Switch on the external output switch and check with a multimeter: output voltage = system voltage ± 2 V, frequency = system frequency ± 0.1 Hz. |
| Shutdown: section, page | §4.1.3, p. 100 | §4.1.3, p. 114 |
| Shutdown, step 3 | Switch off the external battery switch, the mains switch, the bypass switch and the output switch, one by one. | Switch off the external battery switch, the mains switch, the bypass switch and the output switch, one by one. With the optional distribution cabinet, open its switches too. |
| Transfer to bypass and back: section, page | §4.1.3 / 4.1.2, p. 100 | §4.1.3 / 4.1.2, p. 114 |
| Transfer to maintenance bypass: section, page | §6.1.1, p. 133 | §6.1.1, p. 149 |
| Transfer to maintenance bypass: the manual's title | Transfer to maintenance bypass | Transfer to the external maintenance bypass |
| Transfer to maintenance bypass, step 2 | Make sure the inverter is off, then switch on the maintenance bypass switch. The touch screen shows "Maintenance bypass open". | Make sure the inverter is off, then switch on the external maintenance bypass switch. The touch screen shows "Maintenance bypass open". |
| Transfer to maintenance bypass, step 3 | Switch off the external battery switch, the mains switch, the bypass switch and the output switch, one by one. | Switch off the external battery switch, the mains switch, the bypass switch and the output switch, one by one. With the optional distribution cabinet, open its switches too. |
| Transfer to maintenance bypass: caution | Never switch on the output switch in maintenance bypass. The input and output copper bars stay live: touching them can cause an electric shock. | Never switch on the external output switch in maintenance bypass. The input and output copper bars stay live: touching them can cause an electric shock. |
| Back from maintenance bypass to the inverter: section, page | §6.1.2, p. 134 | §6.1.2, p. 150 |
| Back from maintenance bypass to the inverter, step 3 | Switch on the output switch. | Switch on the external output switch. |
| Back from maintenance bypass to the inverter, step 4 | When the panel's bypass indicator is green, switch off the maintenance bypass switch: the maintenance bypass message disappears and the buzzer stops. | When the panel's bypass indicator is green, switch off the external maintenance bypass switch: the maintenance bypass message disappears and the buzzer stops. |
| Battery test: section, page | §6.4, p. 145 | §6.4, p. 160 |
| Emergency power off and recovery: section, page | §4.1.4–4.1.5, p. 101 | §4.1.4–4.1.5, p. 115 |
| Alarm classes: table, page | Table 2-13, p. 46 | Table 2-19, p. 49 |
| Troubleshooting: table, page | Table 6-1, p. 147 | Table 6-1, p. 163 |
Alarms
Alarms and what to check.
From Table 2-13 / Table 2-19 of the manual, page 46 / 49. If an alarm stays, or the cause is inside the UPS, call AEC service.
| Alarm class | Buzzer | What it covers and what to check |
|---|---|---|
| Mains fault | Slow beep | Over- or under-voltage, frequency, phase loss or sequence, neutral loss, harmonics. The UPS stops drawing on the mains and runs from the battery; the mains indicator and the mains icon turn red. Check the input supply and breakers. |
| Battery fault | Rapid beep | Battery reversed, over-voltage, charger over-current, battery circuit abnormal. Battery supply is not allowed; the battery indicator and icon turn red. Check the battery switch, polarity and cables. |
| Bypass fault | Slow beep | Bypass voltage, frequency or phase sequence out of limits. Bypass output is not allowed, so a transfer to bypass would leave the load without supply. Check the bypass switch and wiring. |
| Output fault | Long beep | Inverter output abnormal, output short circuit, inverter over- or under-voltage. The inverter output stops; the output icon turns red. Check the load and the output wiring. |
| System fault | Long beep | EPO on, overload protection, maintenance bypass on, parallel cable abnormal. Read the current fault on the touch screen and call AEC service if it does not clear. |
IST6 200–500 kVA: Manual, Table 2-13, p. 46 · IST6 400–1200 kVA: Manual, Table 2-19, p. 49
Common symptoms.
Table 6-1 of the manual, page 147 / 163: simple checks before you call service.
Mains normal, but the UPS runs on battery and beeps intermittently
A poor contact in the mains supply circuit interrupts the AC input: check connections, sockets and input switches.
The UPS runs on bypass after start-up
The load exceeds the UPS rating: reduce it. A short transfer to bypass when a large load starts, with an automatic return to the inverter, is normal.
The UPS shut down on its own after running on battery
The battery reached its under-voltage protection: normal. When the mains returns the system restarts and recharges. If the mains stays off for long, open the battery switch to protect the battery.
Output normal with mains, none without
Battery fault or badly damaged string, charger fault, battery cables loose, battery switch open, or the UPS left on bypass after a severe overload.
The FAULT indicator of a power module is on
That module is faulty and has been isolated: the system goes on with less redundancy. Have it replaced by AEC service; wait before opening it, high voltage stays inside.
Practice
The IST6 modular display simulator.
The same display, before you stand in front of the UPS: the operating states and the main pages.

IST6 modular · the real display
Normal operation

IST6 400–1200 kVA · the real display
Normal operation