Operating guide
IST7 60–200 / IST6 30–120 kVA operating guide
The IST7 of 60 to 200 kVA and the modular IST6 of 30 to 120 kVA are started, stopped and put on bypass and maintenance bypass by the same steps, from the touch screen and the ON and OFF button pairs. Where the two manuals differ, the step gives each range's own words. Every step names the manual's section and page.

The display
The display, page by page.
The real screens, recorded from AEC's display simulator. Tap a screen to enlarge it. Keys and icons as in section 4.2 of the manual (page 55 / 61).
IST7 60–120 kVA
IST7 160–200 kVA
IST6 30–120 kVA
Keys and controls
- ON pair, 3 s
- IST7 60–200 kVA: Starts the inverter when the power units' green indicators flash slowly.
IST6 30–120 kVA: Starts the inverter when the power modules' green indicators flash slowly. - OFF pair, 3 s
- Stops the inverter: the system transfers to bypass.
- ON/OFF icon
- IST7 60–200 kVA: The same from the touch screen, with a Confirm step (§4.8). The manual prefers it for the maintenance-bypass transfers.
IST6 30–120 kVA: The same from the touch screen, with a Confirm step (§4.8). - Main page icons (IST7 60–200 kVA)
- Bypass input, mains input, rectifier, inverter, battery and output: each flashes when abnormal and opens its data.
- Buzzer
- IST7 60–200 kVA: Mutes or unmutes the buzzer; a new fault after muting turns it on again (§4.4).
IST6 30–120 kVA: The buzzer icon mutes or unmutes; a new fault turns it on again (§4.4). - Login and settings
- IST7 60–200 kVA: Setting manage changes parameters after the administrator login, which AEC technical service gives.
IST6 30–120 kVA: Set manage changes parameters after the administrator login, which AEC technical service gives. - Ready switch (IST6 30–120 kVA)
- On each power module and on the bypass module: locked (red) holds the module in the cabinet; unlocked (green) lets it be withdrawn.
Passwords are not printed here: the settings pages need the administrator access that AEC technical service gives.
Procedures
Start-up, shutdown, bypass, maintenance bypass, battery test, emergency power off.
From the AEC-UM-IST7-60-200 Rev. 01 and AEC-UM-IST6-120 Rev. 01 user manual. The link on each procedure opens the PDF on its page.
Checks before start-upDo them before the first start and after a long time out of use.Manual §5.3.1 · p. 75 / 82 · 6 steps
Make sure the mains (POWER), bypass (BYPASS), output (OUTPUT) and maintenance bypass (MAINTENANCE) switches are all OFF.
Check the load: no inductive loads such as motors, fans or air-conditioners on the UPS output (supply them from the mains); the load switched off and within the UPS rating.
Check that there is no short circuit between live and neutral, or live and earth, at the input and at the output.
IST7 60–200 kVA: Measure the AC voltage at the mains input terminals: it must be within 160–280 V, otherwise the UPS can only be started from the battery.
IST6 30–120 kVA: Measure the AC voltage at the mains input terminals: it must be within 80–280 V, otherwise the UPS can only be started from the battery.
Measure the DC voltage at the battery input: above +11.5 V × the number of blocks on the positive string and below −11.5 V × the number of blocks on the negative one. Check the polarity.
Check that the battery switch's auxiliary contact is wired to an input dry contact and set on the touch screen.
IST7 60–200 kVA: Manual §5.3.1, p. 75 · IST6 30–120 kVA: Manual §5.3.1, p. 82
Start-upFrom all switches off to the load on the inverter.Manual §5.3.2 · p. 76 / 83 · 6 steps
IST7 60–200 kVA: Close the limit switch of every power unit (red: in operation).
IST6 30–120 kVA: Set the ready switches of the bypass module and of every power module to the ready position, as the manual's start-up quick guide shows.
Switch on the bypass switch, then the mains switch, then the external battery switch: the UPS starts on bypass. (Cold start with no mains: switch on only the battery switch, then press the battery cold-start button on the bypass unit for more than 3 s.)
When the green indicators of all power units flash slowly, start the inverter: press the ON button pair on the panel for 3 s, or tap the ON/OFF icon on the main page and confirm.
The UPS transfers the load to the inverter. Check on the main page that the system is on inverter, and on the monitor page that the three-phase output voltage and frequency are normal.
Switch on the output switch and check the output voltage and frequency with a multimeter.
Switch on the loads, the largest first.
IST7 60–200 kVA: Manual §5.3.2, p. 76 · IST6 30–120 kVA: Manual §5.3.2, p. 83
ShutdownInverter off, then every switch open.Manual §5.3.3 · p. 77 / 84 · 4 steps
Switch off the load.
Stop the inverter: press the OFF button pair for 3 s, or tap the ON/OFF icon and confirm. The touch screen shows bypass mode.
Switch off the external battery switch, then the mains switch, the bypass switch and the output switch.
When the touch screen and every LED indicator are off, the UPS is completely shut down.
Caution With a normal bypass the system goes to bypass when the inverter stops; with an abnormal bypass it has no output. Make sure the load is off or can lose its supply.
IST7 60–200 kVA: Manual §5.3.3, p. 77 · IST6 30–120 kVA: Manual §5.3.3, p. 84
Transfer to bypass and backPut the load on the static bypass without switching anything off.Manual §5.3.4 · p. 78 / 85 · 3 steps
Check on the main page that the bypass input is normal (its icon is not flashing).
Stop the inverter from the ON/OFF page (or the OFF button pair for 3 s): the system transfers to bypass by itself.
To return, start the inverter again from the ON/OFF page (or the ON button pair for 3 s) once the power units' green indicators flash slowly.
Caution Check first that the bypass is normal: if the bypass voltage or frequency is outside its limits, stopping the inverter leaves the load without supply.
IST7 60–200 kVA: Manual §5.3.4, p. 78 · IST6 30–120 kVA: Manual §5.3.4, p. 85
Transfer to maintenance bypassService the UPS while the load stays supplied. Qualified personnel only.Manual §5.3.5 · p. 78 / 85 · 4 steps
Stop the inverter from the ON/OFF page of the touch screen (the OFF button pair also works, but the manual does not recommend it).
When the energy flow on the touch screen shows bypass output, set the maintenance bypass switch to ON.
Switch off the mains switch, then the external battery switch, then the bypass switch.
Switch off the output switch. When the touch screen and all LED indicators are off, maintenance can begin.
Caution The maintenance bypass circuit and the terminals stay live during maintenance.
IST7 60–200 kVA: Manual §5.3.5, p. 78 · IST6 30–120 kVA: Manual §5.3.5, p. 85
Back from maintenance bypass to the inverterThe load goes back to the UPS without a break.Manual §5.3.6 · p. 78 / 86 · 3 steps
Switch on the bypass switch, then the mains switch, the external battery switch and the output switch.
When the energy flow on the touch screen shows bypass output, set the maintenance bypass switch to OFF: the load is on the static bypass.
When the power units' green indicators flash slowly, start the inverter from the ON/OFF page: the UPS transfers to inverter output.
Caution Make sure the bypass input is normal before you start.
IST7 60–200 kVA: Manual §5.3.6, p. 78 · IST6 30–120 kVA: Manual §5.3.6, p. 86
Emergency power off and recoveryOnly in an emergency: the load loses its supply.Manual §5.3.7–5.3.8 · p. 79 / 86 · 4 steps
Press the EPO button: the touch screen shows EPO protection and the buzzer sounds continuously.
To recover, make sure the EPO dry contact is no longer in the emergency state (release the external EPO switch).
IST7 60–200 kVA: Open the mains, output, bypass and battery switches and wait until every indicator is off.
IST6 30–120 kVA: Open the mains, output and battery switches and wait until every indicator is off.
Close the mains, bypass and battery switches: the system starts again and the EPO state is cleared.
Caution After EPO the UPS has no output. In maintenance bypass the output stays live even after EPO.
IST7 60–200 kVA: Manual §5.3.7–5.3.8, p. 79 · IST6 30–120 kVA: Manual §5.3.7–5.3.8, p. 86
Battery testFrom Setting manage, Battery test.Manual §4.6.3 / 4.6.6 · p. 65 / 73 · 2 steps
IST7 60–200 kVA: On the main page open Setting manage (administrator login from AEC technical service).
IST6 30–120 kVA: On the main page open Set manage (administrator login from AEC technical service).
On the display: Settings menu Open Battery test and start the test; the page shows its progress.
IST7 60–200 kVA: Manual §4.6.3, p. 65 · IST6 30–120 kVA: Manual §4.6.6, p. 73
What differs between the two ranges.
The two manuals give the same procedures; this table lists every point where their words, sections or pages differ.
| Point | IST7 60–200 kVA | IST6 30–120 kVA |
|---|---|---|
| User manual | AEC-UM-IST7-60-200 Rev. 01 | AEC-UM-IST6-120 Rev. 01 |
| The display: section, page | §4.2, p. 55 | §4.2, p. 61 |
| Key: ON pair, 3 s | Starts the inverter when the power units' green indicators flash slowly. | Starts the inverter when the power modules' green indicators flash slowly. |
| Key: ON/OFF icon | The same from the touch screen, with a Confirm step (§4.8). The manual prefers it for the maintenance-bypass transfers. | The same from the touch screen, with a Confirm step (§4.8). |
| Key: Main page icons | Bypass input, mains input, rectifier, inverter, battery and output: each flashes when abnormal and opens its data. | not on this range |
| Key: Buzzer | Mutes or unmutes the buzzer; a new fault after muting turns it on again (§4.4). | The buzzer icon mutes or unmutes; a new fault turns it on again (§4.4). |
| Key: Login and settings | Setting manage changes parameters after the administrator login, which AEC technical service gives. | Set manage changes parameters after the administrator login, which AEC technical service gives. |
| Key: Ready switch | not on this range | On each power module and on the bypass module: locked (red) holds the module in the cabinet; unlocked (green) lets it be withdrawn. |
| Checks before start-up: section, page | §5.3.1, p. 75 | §5.3.1, p. 82 |
| Checks before start-up, step 4 | Measure the AC voltage at the mains input terminals: it must be within 160–280 V, otherwise the UPS can only be started from the battery. | Measure the AC voltage at the mains input terminals: it must be within 80–280 V, otherwise the UPS can only be started from the battery. |
| Start-up: section, page | §5.3.2, p. 76 | §5.3.2, p. 83 |
| Start-up, step 1 | Close the limit switch of every power unit (red: in operation). | Set the ready switches of the bypass module and of every power module to the ready position, as the manual's start-up quick guide shows. |
| Shutdown: section, page | §5.3.3, p. 77 | §5.3.3, p. 84 |
| Transfer to bypass and back: section, page | §5.3.4, p. 78 | §5.3.4, p. 85 |
| Transfer to maintenance bypass: section, page | §5.3.5, p. 78 | §5.3.5, p. 85 |
| Back from maintenance bypass to the inverter: section, page | §5.3.6, p. 78 | §5.3.6, p. 86 |
| Emergency power off and recovery: section, page | §5.3.7–5.3.8, p. 79 | §5.3.7–5.3.8, p. 86 |
| Emergency power off and recovery, step 3 | Open the mains, output, bypass and battery switches and wait until every indicator is off. | Open the mains, output and battery switches and wait until every indicator is off. |
| Battery test: section, page | §4.6.3, p. 65 | §4.6.6, p. 73 |
| Battery test, step 1 | On the main page open Setting manage (administrator login from AEC technical service). | On the main page open Set manage (administrator login from AEC technical service). |
| Alarm classes: table, page | Table 2-12, p. 26 | Table 2-14, p. 28 |
| Troubleshooting: table, page | Table 6-1, p. 84 | Table 6-1, p. 92 |
Alarms
Alarms and what to check.
From Table 2-12 / Table 2-14 of the manual, page 26 / 28. If an alarm stays, or the cause is inside the UPS, call AEC service.
| Alarm class | Buzzer | What it covers and what to check |
|---|---|---|
| Mains fault | Slow beep | Over- or under-voltage, frequency, phase loss or sequence, neutral loss, harmonics. The UPS stops drawing on the mains and runs from the battery; the mains indicator and the mains icon turn red. Check the input supply and breakers. |
| Battery fault | Rapid beep | Battery reversed, over-voltage, charger over-current, battery circuit abnormal. Battery supply is not allowed; the battery indicator and icon turn red. Check the battery switch, polarity and cables. |
| Bypass fault | Slow beep | Bypass voltage, frequency or phase sequence out of limits. Bypass output is not allowed, so a transfer to bypass would leave the load without supply. Check the bypass switch and wiring. |
| Output fault | Long beep | Inverter output abnormal, output short circuit, inverter over- or under-voltage. The inverter output stops; the output icon turns red. Check the load and the output wiring. |
| System fault | Long beep | EPO on, overload protection, maintenance bypass on, parallel cable abnormal. Read the current fault on the touch screen and call AEC service if it does not clear. |
IST7 60–200 kVA: Manual, Table 2-12, p. 26 · IST6 30–120 kVA: Manual, Table 2-14, p. 28
Common symptoms.
Table 6-1 of the manual, page 84 / 92: simple checks before you call service.
Mains normal, but the UPS runs on battery and beeps intermittently
A poor contact in the mains supply circuit interrupts the AC input: check connections, sockets and input switches.
The UPS runs on bypass after start-up
The load exceeds the UPS rating: reduce it. A short transfer to bypass when a large load starts, with an automatic return to the inverter, is normal.
The UPS shut down on its own after running on battery
The battery reached its under-voltage protection: normal. When the mains returns the system restarts and recharges. If the mains stays off for long, open the battery switch to protect the battery.
Output normal with mains, none without
Battery fault or badly damaged string, charger fault, battery cables loose, battery switch open, or the UPS left on bypass after a severe overload.
The FAULT indicator of a power module is on
That module is faulty and has been isolated: the system goes on with less redundancy. Have it replaced by AEC service; wait before opening it, high voltage stays inside.
Practice
The IST7 60–120 kVA display simulator.
The same display, before you stand in front of the UPS: the operating states and the main pages.

IST7 60–120 kVA · the real display
Normal operation

IST7 160–200 kVA · the real display
Normal operation

IST6 30–120 kVA · the real display
Normal operation
Related:IST7 60–200 rangeIST7 60–200 kVA: User manual (PDF)IST7 60–200 kVA: Manuale d'uso (IT)IST6-120 rangeIST6 30–120 kVA: User manual (PDF)IST6 30–120 kVA: Manuale d'uso (IT)All display simulatorsAll operating guidesDownloads
Operating guides:IST3 1–10 kVAIST3-J 1–3 kVAIST3-J 6–10 kVAIST8 1–3 kVAIST7 10–40 kVAIST6 200–1200 kVA
Talk to an AEC engineer
Tell us the load, the supply and the backup time you need: we answer with the model and the batteries that fit.