CIRRO · 480V three-phase UPS
CIR1200-9X100 CIRRO 900 kVA, 480V three-phase UPS
The AEC CIRRO CIR1200-9X100 is a 900 kVA / 900 kW online double-conversion UPS for 480 V three-phase loads, built on nine 100 kVA power modules, with external battery cabinets. Kept at 80 % of its rating, it carries loads up to 720 kW.
Nine of the frame's 12 module slots are fitted and three are free; with one module held as a spare (N+1) it carries 800 kVA. As configured it weighs 2,308.1 lb (1,046.9 kg) net.
4-wire · 3P+N480 V 4-wire, wye: three phases, neutral and ground (277/480 V)
The same on every CIRRO:The CIRRO display
Load by load
The CIR1200-9X100 at 25, 50, 75 and 100 % load.
Its 900 kW rating in four steps, worked out from its own catalog figures.
| Load | Output current per phase, at 480 V | Load on each of its 9 power modules | Efficiency | Heat to remove | Heat to remove (BTU/h) |
|---|---|---|---|---|---|
| 25 % of the CIR1200-9X100, 225 kW | 271 A per phase | 25 % on each module | 96.2 % efficient | 8.9 kW of heat | 30,320 BTU/h to cool |
| 50 % of the CIR1200-9X100, 450 kW | 541 A per phase | 50 % on each module | 96.9 % efficient | 14 kW of heat | 49,120 BTU/h to cool |
| 75 % of the CIR1200-9X100, 675 kW | 812 A per phase | 75 % on each module | 97.0 % efficient | 21 kW of heat | 71,230 BTU/h to cool |
| 100 % of the CIR1200-9X100, 900 kW | 1,083 A per phase | 100 % on each module | 96.8 % efficient | 30 kW of heat | 101,510 BTU/h to cool |
Current = kVA × load ÷ (√3 × volts).
Module load = load ÷ the kVA of the power modules fitted.
Heat = load × (100 ÷ efficiency − 1); 1 kW is 3,412 BTU/h.
Efficiency
How efficient is the CIR1200-9X100 at your load?
The CIR1200-9X100 in normal double-conversion mode, from the 2026 catalog's efficiency curve. Drag along it to see the heat lost and its yearly cost.
- Load
- —
- Lost as heat
- —
- Heat to remove
- —
- Energy lost in a year, 24/7
- —
- Its cost in a year at per kWh
- —
From the 2026 catalog
What is the CIR1200-9X100?
The code CIR1200-9X100 orders these catalog items:
- 1 × CIR1200-FRAME: 1,200 kVA frame, without power modules, 47.2 × 43.3 × 78.7 in (1,199 × 1,100 × 1,999 mm)
- 9 × CIR-PWR-100: 100 kVA hot-swappable power module, 103.6 lb (47 kg) each
- Architecture: 9 × 100 kVA hot-swappable power modules in a 1,200 kVA / 1,200 kW frame (12 slots, scalable to 12 modules / 1,200 kVA); parallel up to 8 units.
- Battery: external VRLA (battery bank sized separately). DC bus ±240 Vdc (480 Vdc total), 40 × 12 V blocks by default; selectable 30 to 50 blocks (±15 to ±25 per pole).
- Switchgear: no breakers in the frame — external switchgear required for main input, output, bypass input and maintenance bypass.
- Efficiency: up to 97%.
The lines every CIRRO shares, from technology to warranty, are in the CIRRO key facts and in the datasheet below.
9 × 100 kVA power modules fitted in a 12-slot frame: 3 free slots to grow or add redundancy.
Size and floor
How big it is
47.2" W × 43.3" D × 78.7" H (1,199 × 1,100 × 1,999 mm); 2,308.1 lb (1,046.9 kg) net.
Floor load = net weight ÷ footprint, without batteries outside the cabinet.
Installation
What does the CIRRO need in the room?
From the AEC US user manual of the CIRRO. Where the manual gives no distance, none is printed here: ask AEC.
- Clearances
- Front 36 in (914 mm), rear 31.5 in (800 mm), top 19.7 in (500 mm) on the 600, 800 and 1200 frames. Sides: not given.
- Wiring
- Hardwired: an electrician connects it to the panel.
- Cable entry
- Top, through the cable entry plate; Bottom (Only with the optional side wiring cabinet beside the UPS: its size from AEC)
- Breakers and terminals
- Switchgear by others: no breakers in the frame. Terminals under the top cover. Battery breaker external.
- Door
- Two front doors; hinge sides not given.
- Space to pull a module
- Keep at least 27.8 in (705 mm) free in front to slide a module out.
- Units in parallel
- Up to 8 of the same model.
Datasheet
CIR1200-9X100 datasheet.
The CIR1200-9X100 in the AEC 2026 catalog, figure by figure. Compare it with every CIRRO model.
| Parameter | CIR1200-9X100 |
|---|---|
| Power | |
| Rated power (kVA) | 900 |
| Active power (kW) | 900 |
| Output power factor | 1.0 |
| Electrical | |
| Input / output | 480 V three-phase, 4-wire (3P+N) |
| Topology | Online double conversion, modular N+X |
| Efficiency, up to | 97% |
| Battery DC bus | 480 V DC |
| Battery and runtime | |
| Battery type | VRLA (sealed lead-acid) |
| Battery configuration | External battery bank |
| Mechanical | |
| Form factor | Modular |
| Dimensions W × D × H | 47.2 × 43.3 × 78.7 in (1,199 × 1,100 × 1,999 mm) |
| Net weight | 2,308.1 lb (1,046.9 kg) |
| Footprint | 14.2 ft² (1.32 m²) |
| Common to every CIRRO | |
| Technology | 3-level IGBT; unity power factor (kVA = kW); 80 A settable charger |
| Display | personalized AEC red color touchscreen |
| Comms | RS232, RS485, USB, dry contacts, intelligent slot and EPO standard; battery cold start |
| Battery, CIR1200-9X100 | external VRLA (battery bank sized separately). DC bus ±240 Vdc (480 Vdc total), 40 x 12 V blocks by default; selectable 30 to 50 blocks (±15 to ±25 per pole) |
| Network card | SNMP-M (SNMP) |
| Warranty | 3 years on UPS · 2 years on VRLA batteries |
| Quality system | ISO 9001:2015, the group's quality system (SGS) |
From the AEC 2026 catalog. Figures can change: the order confirmation rules.
Downloads
Manuals and catalogs.
The CIRRO documents cover every model of the series, this one included. PDF, in English.
Catalogs and datasheets
Quick answers
CIR1200-9X100: what people ask
What is the output current of the CIR1200-9X100?
1,082.5 A per phase at full load: 900 kVA ÷ (√3 × 480 V). Size the input breaker and the cables of the CIR1200-9X100 from its installation manual and the local electrical code, not from this figure alone.
How much heat does the CIR1200-9X100 give off?
About 30 kW, 101,510 BTU/h, at full load, where it is 96.8% efficient. Plan the room's cooling for a little more than that: the CIR1200-9X100 is less efficient at part load and while its battery recharges.
Will the CIR1200-9X100 fit through a standard door?
Not upright through a standard 36 × 80-inch door, which clears about 34 in: at 43.3 in (1,100 mm) across it needs an opening wider than 43.3 in. Check elevators and the floor load on the way in too.
The method, for any UPS: runtime explained · amps from kVA · heat output in BTU/h
CIRRO
Other CIRRO models
By power, the CIR1200-9X100 is number 14 of 21 in the CIRRO series, which runs from 60 to 1,600 kVA. One size down is the CIR800-8X100 (100 kVA less and 406 lb lighter). One size up is the CIR1200-10X100 (100 kVA more and 104 lb heavier).
Every CIRRO model side by side (21)
| Model | Power | Power against this model | Net weight | Weight against this model |
|---|---|---|---|---|
| CIR360-1X60 | 60 kVA | 840 kVA less | 636 lb | 1,672 lb lighter |
| CIR600-1X100 | 100 kVA | 800 kVA less | 997 lb | 1,312 lb lighter |
| CIR360-2X60 | 120 kVA | 780 kVA less | 727 lb | 1,581 lb lighter |
| CIR360-3X60 | 180 kVA | 720 kVA less | 817 lb | 1,491 lb lighter |
| CIR600-2X100 | 200 kVA | 700 kVA less | 1,100 lb | 1,208 lb lighter |
| CIR360-4X60 | 240 kVA | 660 kVA less | 908 lb | 1,401 lb lighter |
| CIR360-5X60 | 300 kVA | 600 kVA less | 998 lb | 1,310 lb lighter |
| CIR360-6X60 | 360 kVA | 540 kVA less | 1,088 lb | 1,220 lb lighter |
| CIR600-4X100 | 400 kVA | 500 kVA less | 1,307 lb | 1,001 lb lighter |
| CIR600-5X100 | 500 kVA | 400 kVA less | 1,411 lb | 897 lb lighter |
| CIR600-6X100 | 600 kVA | 300 kVA less | 1,515 lb | 794 lb lighter |
| CIR800-7X100 | 700 kVA | 200 kVA less | 1,799 lb | 509 lb lighter |
| CIR800-8X100 | 800 kVA | 100 kVA less | 1,902 lb | 406 lb lighter |
| CIR1200-9X100 | 900 kVA | this page | 2,308 lb | this page |
| CIR1200-10X100 | 1,000 kVA | 100 kVA more | 2,412 lb | 104 lb heavier |
| CIR1200-11X100 | 1,100 kVA | 200 kVA more | 2,515 lb | 207 lb heavier |
| CIR1200-12X100 | 1,200 kVA | 300 kVA more | 2,619 lb | 311 lb heavier |
| CIR1600-13X100 | 1,300 kVA | 400 kVA more | 3,485 lb | 1,177 lb heavier |
| CIR1600-14X100 | 1,400 kVA | 500 kVA more | 3,589 lb | 1,281 lb heavier |
| CIR1600-15X100 | 1,500 kVA | 600 kVA more | 3,693 lb | 1,384 lb heavier |
| CIR1600-16X100 | 1,600 kVA | 700 kVA more | 3,796 lb | 1,488 lb heavier |