CIRRO · 480V three-phase UPS

CIR1600-13X100 CIRRO 1,300 kVA, 480V three-phase UPS

VRLA1,300 kVAOnline double conversion

The AEC CIRRO CIR1600-13X100 is a 1,300 kVA / 1,300 kW online double-conversion UPS for 480 V three-phase loads, built on 13 × 100 kVA power modules, with external battery cabinets. Kept at 80 % of its rating, it carries loads up to 1,040 kW.

13 of the frame's 16 module slots are fitted and three are free; with one module held as a spare (N+1) it carries 1,200 kVA. As configured it weighs 3,485.3 lb (1,580.9 kg) net.

4-wire · 3P+N480 V 4-wire, wye: three phases, neutral and ground (277/480 V)

1,300 kVA / 1,300 kWRating
63 × 39.4 × 78.7 inW × D × H
3,485.3 lbWeight
VRLA, externalBattery
AEC CIR1600-13X100, rendered from its 3D modelDrag to turn

In 3D

Look around the CIR1600-13X100

Load by load

The CIR1600-13X100 at 25, 50, 75 and 100 % load.

Its 1,300 kW rating in four steps, worked out from its own catalog figures.

At 25, 50, 75 and 100 % load
LoadOutput current per phase, at 480 VLoad on each of its 13 power modulesEfficiencyHeat to removeHeat to remove (BTU/h)
25 % of the CIR1600-13X100, 325 kW391 A per phase25 % on each module96.2 % efficient13 kW of heat43,800 BTU/h to cool
50 % of the CIR1600-13X100, 650 kW782 A per phase50 % on each module96.9 % efficient21 kW of heat70,950 BTU/h to cool
75 % of the CIR1600-13X100, 975 kW1,173 A per phase75 % on each module97.0 % efficient30 kW of heat102,890 BTU/h to cool
100 % of the CIR1600-13X100, 1,300 kW1,564 A per phase100 % on each module96.8 % efficient43 kW of heat146,630 BTU/h to cool

Current = kVA × load ÷ (√3 × volts).

Module load = load ÷ the kVA of the power modules fitted.

Heat = load × (100 ÷ efficiency − 1); 1 kW is 3,412 BTU/h.

From the 2026 catalog

What is the CIR1600-13X100?

The code CIR1600-13X100 orders these catalog items:

  • 1 × CIR1600-FRAME: 1,600 kVA frame, without power modules, 63 × 39.4 × 78.7 in (1,600 × 1,001 × 1,999 mm)
  • 13 × CIR-PWR-100: 100 kVA hot-swappable power module, 103.6 lb (47 kg) each
  • Architecture: 13 × 100 kVA hot-swappable power modules in a 1,600 kVA / 1,600 kW frame (16 slots, scalable to 16 modules / 1,600 kVA); parallel up to 8 units.
  • Battery: external VRLA (battery bank sized separately). DC bus ±240 Vdc (480 Vdc total), 40 × 12 V blocks by default; selectable 30 to 50 blocks (±15 to ±25 per pole).
  • Switchgear: no breakers in the frame — external switchgear required for main input, output, bypass input and maintenance bypass.
  • Efficiency: up to 97%.

The lines every CIRRO shares, from technology to warranty, are in the CIRRO key facts and in the datasheet below.

13 × 100 kVA power modules fitted in a 16-slot frame: 3 free slots to grow or add redundancy.

Size and floor

How big it is

63" W × 39.4" D × 78.7" H (1,600 × 1,001 × 1,999 mm); 3,485.3 lb (1,580.9 kg) net.

17.2 ft²footprint (1.60 m²)
202 lb/ft²floor load of the cabinet alone
Modularform factor

Floor load = net weight ÷ footprint, without batteries outside the cabinet.

5′9″ FrontSide 63″39.4″78.7″

Datasheet

CIR1600-13X100 datasheet.

The CIR1600-13X100 in the AEC 2026 catalog, figure by figure. Compare it with every CIRRO model.

CIR1600-13X100 datasheet
ParameterCIR1600-13X100
Power
Rated power (kVA)1,300
Active power (kW)1,300
Output power factor1.0
Electrical
Input / output480 V three-phase, 4-wire (3P+N)
TopologyOnline double conversion, modular N+X
Efficiency, up to97%
Battery DC bus480 V DC
Battery and runtime
Battery typeVRLA (sealed lead-acid)
Battery configurationExternal battery bank
Mechanical
Form factorModular
Dimensions W × D × H63 × 39.4 × 78.7 in (1,600 × 1,001 × 1,999 mm)
Net weight3,485.3 lb (1,580.9 kg)
Footprint17.2 ft² (1.60 m²)
Common to every CIRRO
Technology3-level IGBT; unity power factor (kVA = kW); 80 A settable charger
Displaypersonalized AEC red color touchscreen
CommsRS232, RS485, USB, dry contacts, intelligent slot and EPO standard; battery cold start
Battery, CIR1600-13X100external VRLA (battery bank sized separately). DC bus ±240 Vdc (480 Vdc total), 40 x 12 V blocks by default; selectable 30 to 50 blocks (±15 to ±25 per pole)
Network cardSNMP-M (SNMP)
Warranty3 years on UPS · 2 years on VRLA batteries
Quality systemISO 9001:2015, the group's quality system (SGS)

From the AEC 2026 catalog. Figures can change: the order confirmation rules.

Quick answers

CIR1600-13X100: what people ask

What is the output current of the CIR1600-13X100?

1,563.7 A per phase at full load: 1,300 kVA ÷ (√3 × 480 V). Size the input breaker and the cables of the CIR1600-13X100 from its installation manual and the local electrical code, not from this figure alone.

How much heat does the CIR1600-13X100 give off?

About 43 kW, 146,630 BTU/h, at full load, where it is 96.8% efficient. Plan the room's cooling for a little more than that: the CIR1600-13X100 is less efficient at part load and while its battery recharges.

Will the CIR1600-13X100 fit through a standard door?

Not upright through a standard 36 × 80-inch door, which clears about 34 in: at 39.4 in (1,001 mm) across it needs an opening wider than 39.4 in. Check elevators and the floor load on the way in too.

The method, for any UPS: runtime explained · amps from kVA · heat output in BTU/h

CIRRO

Other CIRRO models

The CIRRO series, with pictures

By power, the CIR1600-13X100 is number 18 of 21 in the CIRRO series, which runs from 60 to 1,600 kVA. One size down is the CIR1200-12X100 (100 kVA less and 866 lb lighter). One size up is the CIR1600-14X100 (100 kVA more and 104 lb heavier).

Every CIRRO model side by side (21)
CIRRO models side by side
ModelPowerPower against this modelNet weightWeight against this model
CIR360-1X6060 kVA1,240 kVA less636 lb2,849 lb lighter
CIR600-1X100100 kVA1,200 kVA less997 lb2,489 lb lighter
CIR360-2X60120 kVA1,180 kVA less727 lb2,759 lb lighter
CIR360-3X60180 kVA1,120 kVA less817 lb2,668 lb lighter
CIR600-2X100200 kVA1,100 kVA less1,100 lb2,385 lb lighter
CIR360-4X60240 kVA1,060 kVA less908 lb2,578 lb lighter
CIR360-5X60300 kVA1,000 kVA less998 lb2,487 lb lighter
CIR360-6X60360 kVA940 kVA less1,088 lb2,397 lb lighter
CIR600-4X100400 kVA900 kVA less1,307 lb2,178 lb lighter
CIR600-5X100500 kVA800 kVA less1,411 lb2,074 lb lighter
CIR600-6X100600 kVA700 kVA less1,515 lb1,971 lb lighter
CIR800-7X100700 kVA600 kVA less1,799 lb1,687 lb lighter
CIR800-8X100800 kVA500 kVA less1,902 lb1,583 lb lighter
CIR1200-9X100900 kVA400 kVA less2,308 lb1,177 lb lighter
CIR1200-10X1001,000 kVA300 kVA less2,412 lb1,074 lb lighter
CIR1200-11X1001,100 kVA200 kVA less2,515 lb970 lb lighter
CIR1200-12X1001,200 kVA100 kVA less2,619 lb866 lb lighter
CIR1600-13X1001,300 kVAthis page3,485 lbthis page
CIR1600-14X1001,400 kVA100 kVA more3,589 lb104 lb heavier
CIR1600-15X1001,500 kVA200 kVA more3,693 lb207 lb heavier
CIR1600-16X1001,600 kVA300 kVA more3,796 lb311 lb heavier

The CIR1600-13X100 for your project

Send the load, the voltage and the minutes you need from the CIR1600-13X100. We reply with the configuration, the batteries and the lead time.