CIRRO · 480V three-phase UPS
CIR1600-13X100 CIRRO 1,300 kVA, 480V three-phase UPS
The AEC CIRRO CIR1600-13X100 is a 1,300 kVA / 1,300 kW online double-conversion UPS for 480 V three-phase loads, built on 13 × 100 kVA power modules, with external battery cabinets. Kept at 80 % of its rating, it carries loads up to 1,040 kW.
13 of the frame's 16 module slots are fitted and three are free; with one module held as a spare (N+1) it carries 1,200 kVA. As configured it weighs 3,485.3 lb (1,580.9 kg) net.
4-wire · 3P+N480 V 4-wire, wye: three phases, neutral and ground (277/480 V)
Drag to turnThe same on every CIRRO:The CIRRO display
Load by load
The CIR1600-13X100 at 25, 50, 75 and 100 % load.
Its 1,300 kW rating in four steps, worked out from its own catalog figures.
| Load | Output current per phase, at 480 V | Load on each of its 13 power modules | Efficiency | Heat to remove | Heat to remove (BTU/h) |
|---|---|---|---|---|---|
| 25 % of the CIR1600-13X100, 325 kW | 391 A per phase | 25 % on each module | 96.2 % efficient | 13 kW of heat | 43,800 BTU/h to cool |
| 50 % of the CIR1600-13X100, 650 kW | 782 A per phase | 50 % on each module | 96.9 % efficient | 21 kW of heat | 70,950 BTU/h to cool |
| 75 % of the CIR1600-13X100, 975 kW | 1,173 A per phase | 75 % on each module | 97.0 % efficient | 30 kW of heat | 102,890 BTU/h to cool |
| 100 % of the CIR1600-13X100, 1,300 kW | 1,564 A per phase | 100 % on each module | 96.8 % efficient | 43 kW of heat | 146,630 BTU/h to cool |
Current = kVA × load ÷ (√3 × volts).
Module load = load ÷ the kVA of the power modules fitted.
Heat = load × (100 ÷ efficiency − 1); 1 kW is 3,412 BTU/h.
Efficiency
How efficient is the CIR1600-13X100 at your load?
The CIR1600-13X100 in normal double-conversion mode, from the 2026 catalog's efficiency curve. Drag along it to see the heat lost and its yearly cost.
- Load
- —
- Lost as heat
- —
- Heat to remove
- —
- Energy lost in a year, 24/7
- —
- Its cost in a year at per kWh
- —
From the 2026 catalog
What is the CIR1600-13X100?
The code CIR1600-13X100 orders these catalog items:
- 1 × CIR1600-FRAME: 1,600 kVA frame, without power modules, 63 × 39.4 × 78.7 in (1,600 × 1,001 × 1,999 mm)
- 13 × CIR-PWR-100: 100 kVA hot-swappable power module, 103.6 lb (47 kg) each
- Architecture: 13 × 100 kVA hot-swappable power modules in a 1,600 kVA / 1,600 kW frame (16 slots, scalable to 16 modules / 1,600 kVA); parallel up to 8 units.
- Battery: external VRLA (battery bank sized separately). DC bus ±240 Vdc (480 Vdc total), 40 × 12 V blocks by default; selectable 30 to 50 blocks (±15 to ±25 per pole).
- Switchgear: no breakers in the frame — external switchgear required for main input, output, bypass input and maintenance bypass.
- Efficiency: up to 97%.
The lines every CIRRO shares, from technology to warranty, are in the CIRRO key facts and in the datasheet below.
13 × 100 kVA power modules fitted in a 16-slot frame: 3 free slots to grow or add redundancy.
Size and floor
How big it is
63" W × 39.4" D × 78.7" H (1,600 × 1,001 × 1,999 mm); 3,485.3 lb (1,580.9 kg) net.
Floor load = net weight ÷ footprint, without batteries outside the cabinet.
Installation
What does the CIRRO need in the room?
From the AEC US user manual of the CIRRO. Where the manual gives no distance, none is printed here: ask AEC.
- Clearances
- Front 36 in (914 mm), rear 31.5 in (800 mm), top 19.7 in (500 mm) on the 600, 800 and 1200 frames. Sides: not given.
- Wiring
- Hardwired: an electrician connects it to the panel.
- Cable entry
- Top, through the cable entry plate; Bottom (Only with the optional side wiring cabinet beside the UPS: its size from AEC)
- Breakers and terminals
- Switchgear by others. Ask AEC for the 1600's layout.
- Door
- Two front doors; hinge sides not given.
- Space to pull a module
- Keep at least 27.8 in (705 mm) free in front to slide a module out.
- Units in parallel
- Up to 8 of the same model.
- Note
- CIRRO 1600: rear and top clearances, terminal place and drawings not issued yet.
Datasheet
CIR1600-13X100 datasheet.
The CIR1600-13X100 in the AEC 2026 catalog, figure by figure. Compare it with every CIRRO model.
| Parameter | CIR1600-13X100 |
|---|---|
| Power | |
| Rated power (kVA) | 1,300 |
| Active power (kW) | 1,300 |
| Output power factor | 1.0 |
| Electrical | |
| Input / output | 480 V three-phase, 4-wire (3P+N) |
| Topology | Online double conversion, modular N+X |
| Efficiency, up to | 97% |
| Battery DC bus | 480 V DC |
| Battery and runtime | |
| Battery type | VRLA (sealed lead-acid) |
| Battery configuration | External battery bank |
| Mechanical | |
| Form factor | Modular |
| Dimensions W × D × H | 63 × 39.4 × 78.7 in (1,600 × 1,001 × 1,999 mm) |
| Net weight | 3,485.3 lb (1,580.9 kg) |
| Footprint | 17.2 ft² (1.60 m²) |
| Common to every CIRRO | |
| Technology | 3-level IGBT; unity power factor (kVA = kW); 80 A settable charger |
| Display | personalized AEC red color touchscreen |
| Comms | RS232, RS485, USB, dry contacts, intelligent slot and EPO standard; battery cold start |
| Battery, CIR1600-13X100 | external VRLA (battery bank sized separately). DC bus ±240 Vdc (480 Vdc total), 40 x 12 V blocks by default; selectable 30 to 50 blocks (±15 to ±25 per pole) |
| Network card | SNMP-M (SNMP) |
| Warranty | 3 years on UPS · 2 years on VRLA batteries |
| Quality system | ISO 9001:2015, the group's quality system (SGS) |
From the AEC 2026 catalog. Figures can change: the order confirmation rules.
Downloads
Manuals and catalogs.
The CIRRO documents cover every model of the series, this one included. PDF, in English.
Catalogs and datasheets
Quick answers
CIR1600-13X100: what people ask
What is the output current of the CIR1600-13X100?
1,563.7 A per phase at full load: 1,300 kVA ÷ (√3 × 480 V). Size the input breaker and the cables of the CIR1600-13X100 from its installation manual and the local electrical code, not from this figure alone.
How much heat does the CIR1600-13X100 give off?
About 43 kW, 146,630 BTU/h, at full load, where it is 96.8% efficient. Plan the room's cooling for a little more than that: the CIR1600-13X100 is less efficient at part load and while its battery recharges.
Will the CIR1600-13X100 fit through a standard door?
Not upright through a standard 36 × 80-inch door, which clears about 34 in: at 39.4 in (1,001 mm) across it needs an opening wider than 39.4 in. Check elevators and the floor load on the way in too.
The method, for any UPS: runtime explained · amps from kVA · heat output in BTU/h
CIRRO
Other CIRRO models
By power, the CIR1600-13X100 is number 18 of 21 in the CIRRO series, which runs from 60 to 1,600 kVA. One size down is the CIR1200-12X100 (100 kVA less and 866 lb lighter). One size up is the CIR1600-14X100 (100 kVA more and 104 lb heavier).
Every CIRRO model side by side (21)
| Model | Power | Power against this model | Net weight | Weight against this model |
|---|---|---|---|---|
| CIR360-1X60 | 60 kVA | 1,240 kVA less | 636 lb | 2,849 lb lighter |
| CIR600-1X100 | 100 kVA | 1,200 kVA less | 997 lb | 2,489 lb lighter |
| CIR360-2X60 | 120 kVA | 1,180 kVA less | 727 lb | 2,759 lb lighter |
| CIR360-3X60 | 180 kVA | 1,120 kVA less | 817 lb | 2,668 lb lighter |
| CIR600-2X100 | 200 kVA | 1,100 kVA less | 1,100 lb | 2,385 lb lighter |
| CIR360-4X60 | 240 kVA | 1,060 kVA less | 908 lb | 2,578 lb lighter |
| CIR360-5X60 | 300 kVA | 1,000 kVA less | 998 lb | 2,487 lb lighter |
| CIR360-6X60 | 360 kVA | 940 kVA less | 1,088 lb | 2,397 lb lighter |
| CIR600-4X100 | 400 kVA | 900 kVA less | 1,307 lb | 2,178 lb lighter |
| CIR600-5X100 | 500 kVA | 800 kVA less | 1,411 lb | 2,074 lb lighter |
| CIR600-6X100 | 600 kVA | 700 kVA less | 1,515 lb | 1,971 lb lighter |
| CIR800-7X100 | 700 kVA | 600 kVA less | 1,799 lb | 1,687 lb lighter |
| CIR800-8X100 | 800 kVA | 500 kVA less | 1,902 lb | 1,583 lb lighter |
| CIR1200-9X100 | 900 kVA | 400 kVA less | 2,308 lb | 1,177 lb lighter |
| CIR1200-10X100 | 1,000 kVA | 300 kVA less | 2,412 lb | 1,074 lb lighter |
| CIR1200-11X100 | 1,100 kVA | 200 kVA less | 2,515 lb | 970 lb lighter |
| CIR1200-12X100 | 1,200 kVA | 100 kVA less | 2,619 lb | 866 lb lighter |
| CIR1600-13X100 | 1,300 kVA | this page | 3,485 lb | this page |
| CIR1600-14X100 | 1,400 kVA | 100 kVA more | 3,589 lb | 104 lb heavier |
| CIR1600-15X100 | 1,500 kVA | 200 kVA more | 3,693 lb | 207 lb heavier |
| CIR1600-16X100 | 1,600 kVA | 300 kVA more | 3,796 lb | 311 lb heavier |
Install and run it:RADIANT and CIRRO operating guide
The CIR1600-13X100 for your project
Send the load, the voltage and the minutes you need from the CIR1600-13X100. We reply with the configuration, the batteries and the lead time.