CIRRO · 480V three-phase UPS
CIR1600-16X100 CIRRO 1,600 kVA, 480V three-phase UPS
The AEC CIRRO CIR1600-16X100 is a 1,600 kVA / 1,600 kW online double-conversion UPS for 480 V three-phase loads, built on 16 × 100 kVA power modules, with external battery cabinets. Kept at 80 % of its rating, it carries loads up to 1,280 kW.
All 16 module slots are fitted, so the frame is at its full 1,600 kVA; with one module held as a spare (N+1) it carries 1,500 kVA. As configured it weighs 3,796.1 lb (1,721.9 kg) net.
4-wire · 3P+N480 V 4-wire, wye: three phases, neutral and ground (277/480 V)
Drag to turnThe same on every CIRRO:The CIRRO display
Load by load
The CIR1600-16X100 at 25, 50, 75 and 100 % load.
Its 1,600 kW rating in four steps, worked out from its own catalog figures.
| Load | Output current per phase, at 480 V | Load on each of its 16 power modules | Efficiency | Heat to remove | Heat to remove (BTU/h) |
|---|---|---|---|---|---|
| 25 % of the CIR1600-16X100, 400 kW | 481 A per phase | 25 % on each module | 96.2 % efficient | 16 kW of heat | 53,910 BTU/h to cool |
| 50 % of the CIR1600-16X100, 800 kW | 962 A per phase | 50 % on each module | 96.9 % efficient | 26 kW of heat | 87,320 BTU/h to cool |
| 75 % of the CIR1600-16X100, 1,200 kW | 1,443 A per phase | 75 % on each module | 97.0 % efficient | 37 kW of heat | 126,630 BTU/h to cool |
| 100 % of the CIR1600-16X100, 1,600 kW | 1,925 A per phase | 100 % on each module | 96.8 % efficient | 53 kW of heat | 180,470 BTU/h to cool |
Current = kVA × load ÷ (√3 × volts).
Module load = load ÷ the kVA of the power modules fitted.
Heat = load × (100 ÷ efficiency − 1); 1 kW is 3,412 BTU/h.
Efficiency
How efficient is the CIR1600-16X100 at your load?
The CIR1600-16X100 in normal double-conversion mode, from the 2026 catalog's efficiency curve. Drag along it to see the heat lost and its yearly cost.
- Load
- —
- Lost as heat
- —
- Heat to remove
- —
- Energy lost in a year, 24/7
- —
- Its cost in a year at per kWh
- —
From the 2026 catalog
What is the CIR1600-16X100?
The code CIR1600-16X100 orders these catalog items:
- 1 × CIR1600-FRAME: 1,600 kVA frame, without power modules, 63 × 39.4 × 78.7 in (1,600 × 1,001 × 1,999 mm)
- 16 × CIR-PWR-100: 100 kVA hot-swappable power module, 103.6 lb (47 kg) each
- Architecture: 16 × 100 kVA hot-swappable power modules in a 1,600 kVA / 1,600 kW frame (16 slots, scalable to 16 modules / 1,600 kVA); parallel up to 8 units.
- Battery: external VRLA (battery bank sized separately). DC bus ±240 Vdc (480 Vdc total), 40 × 12 V blocks by default; selectable 30 to 50 blocks (±15 to ±25 per pole).
- Switchgear: no breakers in the frame — external switchgear required for main input, output, bypass input and maintenance bypass.
- Efficiency: up to 97%.
The lines every CIRRO shares, from technology to warranty, are in the CIRRO key facts and in the datasheet below.
16 × 100 kVA power modules fitted in a 16-slot frame: the frame is full.
Size and floor
How big it is
63" W × 39.4" D × 78.7" H (1,600 × 1,001 × 1,999 mm); 3,796.1 lb (1,721.9 kg) net.
Floor load = net weight ÷ footprint, without batteries outside the cabinet.
Installation
Clearances, wiring, cable entry and breakers of the CIR1600-16X100 are those of the CIR1600-13X100, in the same frame, from the AEC US user manual of the CIRRO: see them on its page.
Place the CIR1600-16X100 in your room, to the inch, with Room fit
Datasheet
CIR1600-16X100 datasheet.
The CIR1600-16X100 in the AEC 2026 catalog, figure by figure. Compare it with every CIRRO model.
| Parameter | CIR1600-16X100 |
|---|---|
| Power | |
| Rated power (kVA) | 1,600 |
| Active power (kW) | 1,600 |
| Output power factor | 1.0 |
| Electrical | |
| Input / output | 480 V three-phase, 4-wire (3P+N) |
| Topology | Online double conversion, modular N+X |
| Efficiency, up to | 97% |
| Battery DC bus | 480 V DC |
| Battery and runtime | |
| Battery type | VRLA (sealed lead-acid) |
| Battery configuration | External battery bank |
| Mechanical | |
| Form factor | Modular |
| Dimensions W × D × H | 63 × 39.4 × 78.7 in (1,600 × 1,001 × 1,999 mm) |
| Net weight | 3,796.1 lb (1,721.9 kg) |
| Footprint | 17.2 ft² (1.60 m²) |
| Common to every CIRRO | |
| Technology | 3-level IGBT; unity power factor (kVA = kW); 80 A settable charger |
| Display | personalized AEC red color touchscreen |
| Comms | RS232, RS485, USB, dry contacts, intelligent slot and EPO standard; battery cold start |
| Battery, CIR1600-16X100 | external VRLA (battery bank sized separately). DC bus ±240 Vdc (480 Vdc total), 40 x 12 V blocks by default; selectable 30 to 50 blocks (±15 to ±25 per pole) |
| Network card | SNMP-M (SNMP) |
| Warranty | 3 years on UPS · 2 years on VRLA batteries |
| Quality system | ISO 9001:2015, the group's quality system (SGS) |
From the AEC 2026 catalog. Figures can change: the order confirmation rules.
Downloads
Manuals and catalogs.
The CIRRO documents cover every model of the series, this one included. PDF, in English.
Catalogs and datasheets
Quick answers
CIR1600-16X100: what people ask
What is the output current of the CIR1600-16X100?
1,924.5 A per phase at full load: 1,600 kVA ÷ (√3 × 480 V). Size the input breaker and the cables of the CIR1600-16X100 from its installation manual and the local electrical code, not from this figure alone.
How much heat does the CIR1600-16X100 give off?
About 53 kW, 180,470 BTU/h, at full load, where it is 96.8% efficient. Plan the room's cooling for a little more than that: the CIR1600-16X100 is less efficient at part load and while its battery recharges.
Will the CIR1600-16X100 fit through a standard door?
Not upright through a standard 36 × 80-inch door, which clears about 34 in: at 39.4 in (1,001 mm) across it needs an opening wider than 39.4 in. Check elevators and the floor load on the way in too.
The method, for any UPS: runtime explained · amps from kVA · heat output in BTU/h
CIRRO
Other CIRRO models
By power, the CIR1600-16X100 is the largest in the CIRRO series, which runs from 60 to 1,600 kVA. One size down is the CIR1600-15X100 (100 kVA less and 104 lb lighter).
Every CIRRO model side by side (21)
| Model | Power | Power against this model | Net weight | Weight against this model |
|---|---|---|---|---|
| CIR360-1X60 | 60 kVA | 1,540 kVA less | 636 lb | 3,160 lb lighter |
| CIR600-1X100 | 100 kVA | 1,500 kVA less | 997 lb | 2,800 lb lighter |
| CIR360-2X60 | 120 kVA | 1,480 kVA less | 727 lb | 3,069 lb lighter |
| CIR360-3X60 | 180 kVA | 1,420 kVA less | 817 lb | 2,979 lb lighter |
| CIR600-2X100 | 200 kVA | 1,400 kVA less | 1,100 lb | 2,696 lb lighter |
| CIR360-4X60 | 240 kVA | 1,360 kVA less | 908 lb | 2,889 lb lighter |
| CIR360-5X60 | 300 kVA | 1,300 kVA less | 998 lb | 2,798 lb lighter |
| CIR360-6X60 | 360 kVA | 1,240 kVA less | 1,088 lb | 2,708 lb lighter |
| CIR600-4X100 | 400 kVA | 1,200 kVA less | 1,307 lb | 2,489 lb lighter |
| CIR600-5X100 | 500 kVA | 1,100 kVA less | 1,411 lb | 2,385 lb lighter |
| CIR600-6X100 | 600 kVA | 1,000 kVA less | 1,515 lb | 2,282 lb lighter |
| CIR800-7X100 | 700 kVA | 900 kVA less | 1,799 lb | 1,997 lb lighter |
| CIR800-8X100 | 800 kVA | 800 kVA less | 1,902 lb | 1,894 lb lighter |
| CIR1200-9X100 | 900 kVA | 700 kVA less | 2,308 lb | 1,488 lb lighter |
| CIR1200-10X100 | 1,000 kVA | 600 kVA less | 2,412 lb | 1,384 lb lighter |
| CIR1200-11X100 | 1,100 kVA | 500 kVA less | 2,515 lb | 1,281 lb lighter |
| CIR1200-12X100 | 1,200 kVA | 400 kVA less | 2,619 lb | 1,177 lb lighter |
| CIR1600-13X100 | 1,300 kVA | 300 kVA less | 3,485 lb | 311 lb lighter |
| CIR1600-14X100 | 1,400 kVA | 200 kVA less | 3,589 lb | 207 lb lighter |
| CIR1600-15X100 | 1,500 kVA | 100 kVA less | 3,693 lb | 104 lb lighter |
| CIR1600-16X100 | 1,600 kVA | this page | 3,796 lb | this page |
Install and run it:RADIANT and CIRRO operating guide
The CIR1600-16X100 for your project
Send the load, the voltage and the minutes you need from the CIR1600-16X100. We reply with the configuration, the batteries and the lead time.