CIRRO · 480V three-phase UPS

CIR360-4X60 CIRRO 240 kVA, 480V three-phase UPS

VRLA240 kVAOnline double conversion

The AEC CIRRO CIR360-4X60 is a 240 kVA / 240 kW online double-conversion UPS for 480 V three-phase loads, built on four 60 kVA power modules, with external battery cabinets. Kept at 80 % of its rating, it carries loads up to 192 kW.

Four of the frame's six module slots are fitted and two are free; with one module held as a spare (N+1) it carries 180 kVA. As configured it weighs 907.6 lb (411.7 kg) net.

4-wire · 3P+N480 V 4-wire, wye: three phases, neutral and ground (277/480 V)

240 kVA / 240 kWRating
23.6 × 39.3 × 78.7 inW × D × H
907.6 lbWeight
VRLA, externalBattery
AEC CIR360-4X60, rendered from its 3D modelDrag to turn

In 3D

Look around the CIR360-4X60

Load by load

The CIR360-4X60 at 25, 50, 75 and 100 % load.

Its 240 kW rating in four steps, worked out from its own catalog figures.

At 25, 50, 75 and 100 % load
LoadOutput current per phase, at 480 VLoad on each of its 4 power modulesEfficiencyHeat to removeHeat to remove (BTU/h)
25 % of the CIR360-4X60, 60 kW72.2 A per phase25 % on each module95.1 % efficient3.1 kW of heat10,550 BTU/h to cool
50 % of the CIR360-4X60, 120 kW144 A per phase50 % on each module95.9 % efficient5.1 kW of heat17,500 BTU/h to cool
75 % of the CIR360-4X60, 180 kW217 A per phase75 % on each module96.0 % efficient7.5 kW of heat25,590 BTU/h to cool
100 % of the CIR360-4X60, 240 kW289 A per phase100 % on each module95.8 % efficient11 kW of heat35,900 BTU/h to cool

Current = kVA × load ÷ (√3 × volts).

Module load = load ÷ the kVA of the power modules fitted.

Heat = load × (100 ÷ efficiency − 1); 1 kW is 3,412 BTU/h.

From the 2026 catalog

What is the CIR360-4X60?

The code CIR360-4X60 orders these catalog items:

  • 1 × CIR360-FRAME: 360 kVA frame, without power modules, 23.6 × 39.4 × 78.7 in (600 × 1,000 × 2,000 mm)
  • 4 × CIR-PWR-60: 60 kVA hot-swappable power module, 77 lb (34.9 kg) each
  • Architecture: 4 × 60 kVA hot-swappable power modules in a 360 kVA / 360 kW frame (6 slots, scalable to 6 modules / 360 kVA); parallel up to 8 units.
  • Battery: external VRLA (battery bank sized separately). DC bus ±240 Vdc (480 Vdc total), 40 × 12 V blocks by default; selectable ±15 to ±22 blocks per pole (30 to 44 blocks).
  • Switchgear: 1 breaker included in the frame.
  • Efficiency: up to 96%.

The lines every CIRRO shares, from technology to warranty, are in the CIRRO key facts and in the datasheet below.

4 × 60 kVA power modules fitted in a 6-slot frame: 2 free slots to grow or add redundancy.

Size and floor

How big it is

23.6" W × 39.3" D × 78.7" H (599 × 998 × 1,999 mm); 907.6 lb (411.7 kg) net. It ships in one carton of 27 × 42.7 × 82.1 in, 1,040.6 lb (472 kg) gross.

6.4 ft²footprint (0.60 m²)
141 lb/ft²floor load of the cabinet alone
Modularform factor

Floor load = net weight ÷ footprint, without batteries outside the cabinet.

5′9″ FrontSide 23.6″39.3″78.7″

Datasheet

CIR360-4X60 datasheet.

The CIR360-4X60 in the AEC 2026 catalog, figure by figure. Compare it with every CIRRO model.

CIR360-4X60 datasheet
ParameterCIR360-4X60
Power
Rated power (kVA)240
Active power (kW)240
Output power factor1.0
Electrical
Input / output480 V three-phase, 4-wire (3P+N)
TopologyOnline double conversion, modular N+X
Efficiency, up to96%
Battery DC bus480 V DC
Battery and runtime
Battery typeVRLA (sealed lead-acid)
Battery configurationExternal battery bank
Mechanical
Form factorModular
Dimensions W × D × H23.6 × 39.3 × 78.7 in (599 × 998 × 1,999 mm)
Net weight907.6 lb (411.7 kg)
Footprint6.4 ft² (0.60 m²)
Shipping
Cartons1
Shipping weight1,040.6 lb
Common to every CIRRO
Technology3-level IGBT; unity power factor (kVA = kW); 80 A settable charger
Displaypersonalized AEC red color touchscreen
CommsRS232, RS485, USB, dry contacts, intelligent slot and EPO standard; battery cold start
Battery, CIR360-4X60external VRLA (battery bank sized separately). DC bus ±240 Vdc (480 Vdc total), 40 x 12 V blocks by default; selectable ±15 to ±22 blocks per pole (30 to 44 blocks)
Network cardSNMP-M (SNMP)
Warranty3 years on UPS · 2 years on VRLA batteries
Quality systemISO 9001:2015, the group's quality system (SGS)

From the AEC 2026 catalog. Figures can change: the order confirmation rules.

Quick answers

CIR360-4X60: what people ask

What is the output current of the CIR360-4X60?

288.7 A per phase at full load: 240 kVA ÷ (√3 × 480 V). Size the input breaker and the cables of the CIR360-4X60 from its installation manual and the local electrical code, not from this figure alone.

How much heat does the CIR360-4X60 give off?

About 11 kW, 35,900 BTU/h, at full load, where it is 95.8% efficient. Plan the room's cooling for a little more than that: the CIR360-4X60 is less efficient at part load and while its battery recharges.

Will the CIR360-4X60 fit through a standard door?

Yes: 23.6 in (599 mm) across its narrow side and 78.7 in (1,999 mm) high, it passes a standard 36 × 80-inch door upright, with little to spare in height. On the way in, check corridors, elevators and the floor load of the CIR360-4X60 (size section above).

The method, for any UPS: runtime explained · amps from kVA · heat output in BTU/h

CIRRO

Other CIRRO models

The CIRRO series, with pictures

By power, the CIR360-4X60 is number 6 of 21 in the CIRRO series, which runs from 60 to 1,600 kVA. One size down is the CIR600-2X100 (40 kVA less and 192 lb heavier). One size up is the CIR360-5X60 (60 kVA more and 90 lb heavier).

Every CIRRO model side by side (21)
CIRRO models side by side
ModelPowerPower against this modelNet weightWeight against this model
CIR360-1X6060 kVA180 kVA less636 lb271 lb lighter
CIR600-1X100100 kVA140 kVA less997 lb89 lb heavier
CIR360-2X60120 kVA120 kVA less727 lb181 lb lighter
CIR360-3X60180 kVA60 kVA less817 lb90 lb lighter
CIR600-2X100200 kVA40 kVA less1,100 lb192 lb heavier
CIR360-4X60240 kVAthis page908 lbthis page
CIR360-5X60300 kVA60 kVA more998 lb90 lb heavier
CIR360-6X60360 kVA120 kVA more1,088 lb181 lb heavier
CIR600-4X100400 kVA160 kVA more1,307 lb400 lb heavier
CIR600-5X100500 kVA260 kVA more1,411 lb503 lb heavier
CIR600-6X100600 kVA360 kVA more1,515 lb607 lb heavier
CIR800-7X100700 kVA460 kVA more1,799 lb891 lb heavier
CIR800-8X100800 kVA560 kVA more1,902 lb995 lb heavier
CIR1200-9X100900 kVA660 kVA more2,308 lb1,401 lb heavier
CIR1200-10X1001,000 kVA760 kVA more2,412 lb1,504 lb heavier
CIR1200-11X1001,100 kVA860 kVA more2,515 lb1,608 lb heavier
CIR1200-12X1001,200 kVA960 kVA more2,619 lb1,711 lb heavier
CIR1600-13X1001,300 kVA1,060 kVA more3,485 lb2,578 lb heavier
CIR1600-14X1001,400 kVA1,160 kVA more3,589 lb2,681 lb heavier
CIR1600-15X1001,500 kVA1,260 kVA more3,693 lb2,785 lb heavier
CIR1600-16X1001,600 kVA1,360 kVA more3,796 lb2,889 lb heavier

The CIR360-4X60 for your project

Send the load, the voltage and the minutes you need from the CIR360-4X60. We reply with the configuration, the batteries and the lead time.