CIRRO · 480V three-phase UPS
CIR360-3X60 CIRRO 180 kVA, 480V three-phase UPS
The AEC CIRRO CIR360-3X60 is a 180 kVA / 180 kW online double-conversion UPS for 480 V three-phase loads, built on three 60 kVA power modules, with external battery cabinets. Kept at 80 % of its rating, it carries loads up to 144 kW.
Three of the frame's six module slots are fitted and three are free; with one module held as a spare (N+1) it carries 120 kVA. As configured it weighs 817.2 lb (370.7 kg) net.
4-wire · 3P+N480 V 4-wire, wye: three phases, neutral and ground (277/480 V)
Drag to turnThe same on every CIRRO:The CIRRO display
Load by load
The CIR360-3X60 at 25, 50, 75 and 100 % load.
Its 180 kW rating in four steps, worked out from its own catalog figures.
| Load | Output current per phase, at 480 V | Load on each of its 3 power modules | Efficiency | Heat to remove | Heat to remove (BTU/h) |
|---|---|---|---|---|---|
| 25 % of the CIR360-3X60, 45 kW | 54.1 A per phase | 25 % on each module | 95.1 % efficient | 2.3 kW of heat | 7,910 BTU/h to cool |
| 50 % of the CIR360-3X60, 90 kW | 108 A per phase | 50 % on each module | 95.9 % efficient | 3.8 kW of heat | 13,130 BTU/h to cool |
| 75 % of the CIR360-3X60, 135 kW | 162 A per phase | 75 % on each module | 96.0 % efficient | 5.6 kW of heat | 19,190 BTU/h to cool |
| 100 % of the CIR360-3X60, 180 kW | 217 A per phase | 100 % on each module | 95.8 % efficient | 7.9 kW of heat | 26,930 BTU/h to cool |
Current = kVA × load ÷ (√3 × volts).
Module load = load ÷ the kVA of the power modules fitted.
Heat = load × (100 ÷ efficiency − 1); 1 kW is 3,412 BTU/h.
Efficiency
How efficient is the CIR360-3X60 at your load?
The CIR360-3X60 in normal double-conversion mode, from the 2026 catalog's efficiency curve. Drag along it to see the heat lost and its yearly cost.
- Load
- —
- Lost as heat
- —
- Heat to remove
- —
- Energy lost in a year, 24/7
- —
- Its cost in a year at per kWh
- —
From the 2026 catalog
What is the CIR360-3X60?
The code CIR360-3X60 orders these catalog items:
- 1 × CIR360-FRAME: 360 kVA frame, without power modules, 23.6 × 39.4 × 78.7 in (600 × 1,000 × 2,000 mm)
- 3 × CIR-PWR-60: 60 kVA hot-swappable power module, 77 lb (34.9 kg) each
- Architecture: 3 × 60 kVA hot-swappable power modules in a 360 kVA / 360 kW frame (6 slots, scalable to 6 modules / 360 kVA); parallel up to 8 units.
- Battery: external VRLA (battery bank sized separately). DC bus ±240 Vdc (480 Vdc total), 40 × 12 V blocks by default; selectable ±15 to ±22 blocks per pole (30 to 44 blocks).
- Switchgear: 1 breaker included in the frame.
- Efficiency: up to 96%.
The lines every CIRRO shares, from technology to warranty, are in the CIRRO key facts and in the datasheet below.
3 × 60 kVA power modules fitted in a 6-slot frame: 3 free slots to grow or add redundancy.
Size and floor
How big it is
23.6" W × 39.3" D × 78.7" H (599 × 998 × 1,999 mm); 817.2 lb (370.7 kg) net. It ships in one carton of 27 × 42.7 × 82.1 in, 950.2 lb (431 kg) gross.
Floor load = net weight ÷ footprint, without batteries outside the cabinet.
Installation
Clearances, wiring, cable entry and breakers of the CIR360-3X60 are those of the CIR360-1X60, in the same frame, from the AEC US user manual of the CIRRO: see them on its page.
Place the CIR360-3X60 in your room, to the inch, with Room fit
Datasheet
CIR360-3X60 datasheet.
The CIR360-3X60 in the AEC 2026 catalog, figure by figure. Compare it with every CIRRO model.
| Parameter | CIR360-3X60 |
|---|---|
| Power | |
| Rated power (kVA) | 180 |
| Active power (kW) | 180 |
| Output power factor | 1.0 |
| Electrical | |
| Input / output | 480 V three-phase, 4-wire (3P+N) |
| Topology | Online double conversion, modular N+X |
| Efficiency, up to | 96% |
| Battery DC bus | 480 V DC |
| Battery and runtime | |
| Battery type | VRLA (sealed lead-acid) |
| Battery configuration | External battery bank |
| Mechanical | |
| Form factor | Modular |
| Dimensions W × D × H | 23.6 × 39.3 × 78.7 in (599 × 998 × 1,999 mm) |
| Net weight | 817.2 lb (370.7 kg) |
| Footprint | 6.4 ft² (0.60 m²) |
| Shipping | |
| Cartons | 1 |
| Shipping weight | 950.2 lb |
| Common to every CIRRO | |
| Technology | 3-level IGBT; unity power factor (kVA = kW); 80 A settable charger |
| Display | personalized AEC red color touchscreen |
| Comms | RS232, RS485, USB, dry contacts, intelligent slot and EPO standard; battery cold start |
| Battery, CIR360-3X60 | external VRLA (battery bank sized separately). DC bus ±240 Vdc (480 Vdc total), 40 x 12 V blocks by default; selectable ±15 to ±22 blocks per pole (30 to 44 blocks) |
| Network card | SNMP-M (SNMP) |
| Warranty | 3 years on UPS · 2 years on VRLA batteries |
| Quality system | ISO 9001:2015, the group's quality system (SGS) |
From the AEC 2026 catalog. Figures can change: the order confirmation rules.
Downloads
Manuals and catalogs.
The CIRRO documents cover every model of the series, this one included. PDF, in English.
Catalogs and datasheets
Quick answers
CIR360-3X60: what people ask
What is the output current of the CIR360-3X60?
216.5 A per phase at full load: 180 kVA ÷ (√3 × 480 V). Size the input breaker and the cables of the CIR360-3X60 from its installation manual and the local electrical code, not from this figure alone.
How much heat does the CIR360-3X60 give off?
About 7.9 kW, 26,930 BTU/h, at full load, where it is 95.8% efficient. Plan the room's cooling for a little more than that: the CIR360-3X60 is less efficient at part load and while its battery recharges.
How much power do 8 CIR360-3X60 give in parallel?
1,440 kVA: up to 8 units of the same model run in parallel, by the AEC US user manual of the CIRRO. Kept as N+1, with one unit spare, 8 CIR360-3X60 carry 1,260 kVA (1,260 kW).
Will the CIR360-3X60 fit through a standard door?
Yes: 23.6 in (599 mm) across its narrow side and 78.7 in (1,999 mm) high, it passes a standard 36 × 80-inch door upright, with little to spare in height. On the way in, check corridors, elevators and the floor load of the CIR360-3X60 (size section above).
The method, for any UPS: runtime explained · amps from kVA · heat output in BTU/h
CIRRO
Other CIRRO models
By power, the CIR360-3X60 is number 4 of 21 in the CIRRO series, which runs from 60 to 1,600 kVA. One size down is the CIR360-2X60 (60 kVA less and 90 lb lighter). One size up is the CIR600-2X100 (20 kVA more and 283 lb heavier).
Every CIRRO model side by side (21)
| Model | Power | Power against this model | Net weight | Weight against this model |
|---|---|---|---|---|
| CIR360-1X60 | 60 kVA | 120 kVA less | 636 lb | 181 lb lighter |
| CIR600-1X100 | 100 kVA | 80 kVA less | 997 lb | 179 lb heavier |
| CIR360-2X60 | 120 kVA | 60 kVA less | 727 lb | 90 lb lighter |
| CIR360-3X60 | 180 kVA | this page | 817 lb | this page |
| CIR600-2X100 | 200 kVA | 20 kVA more | 1,100 lb | 283 lb heavier |
| CIR360-4X60 | 240 kVA | 60 kVA more | 908 lb | 90 lb heavier |
| CIR360-5X60 | 300 kVA | 120 kVA more | 998 lb | 181 lb heavier |
| CIR360-6X60 | 360 kVA | 180 kVA more | 1,088 lb | 271 lb heavier |
| CIR600-4X100 | 400 kVA | 220 kVA more | 1,307 lb | 490 lb heavier |
| CIR600-5X100 | 500 kVA | 320 kVA more | 1,411 lb | 594 lb heavier |
| CIR600-6X100 | 600 kVA | 420 kVA more | 1,515 lb | 697 lb heavier |
| CIR800-7X100 | 700 kVA | 520 kVA more | 1,799 lb | 982 lb heavier |
| CIR800-8X100 | 800 kVA | 620 kVA more | 1,902 lb | 1,085 lb heavier |
| CIR1200-9X100 | 900 kVA | 720 kVA more | 2,308 lb | 1,491 lb heavier |
| CIR1200-10X100 | 1,000 kVA | 820 kVA more | 2,412 lb | 1,594 lb heavier |
| CIR1200-11X100 | 1,100 kVA | 920 kVA more | 2,515 lb | 1,698 lb heavier |
| CIR1200-12X100 | 1,200 kVA | 1,020 kVA more | 2,619 lb | 1,802 lb heavier |
| CIR1600-13X100 | 1,300 kVA | 1,120 kVA more | 3,485 lb | 2,668 lb heavier |
| CIR1600-14X100 | 1,400 kVA | 1,220 kVA more | 3,589 lb | 2,772 lb heavier |
| CIR1600-15X100 | 1,500 kVA | 1,320 kVA more | 3,693 lb | 2,875 lb heavier |
| CIR1600-16X100 | 1,600 kVA | 1,420 kVA more | 3,796 lb | 2,979 lb heavier |
Install and run it:RADIANT and CIRRO operating guide
The CIR360-3X60 for your project
Send the load, the voltage and the minutes you need from the CIR360-3X60. We reply with the configuration, the batteries and the lead time.