CIRRO · 480V three-phase UPS
CIR600-1X100 CIRRO 100 kVA, 480V three-phase UPS
The AEC CIRRO CIR600-1X100 is a 100 kVA / 100 kW online double-conversion UPS for 480 V three-phase loads, built on one 100 kVA power module, with external battery cabinets. Kept at 80 % of its rating, it carries loads up to 80 kW.
One of the frame's six module slots is fitted, so no module is spare at this size; five more modules take the frame to 600 kVA. As configured it weighs 996.5 lb (452 kg) net.
4-wire · 3P+N480 V 4-wire, wye: three phases, neutral and ground (277/480 V)
Drag to turnThe same on every CIRRO:The CIRRO display
Load by load
The CIR600-1X100 at 25, 50, 75 and 100 % load.
Its 100 kW rating in four steps, worked out from its own catalog figures.
| Load | Output current per phase, at 480 V | Efficiency | Heat to remove | Heat to remove (BTU/h) |
|---|---|---|---|---|
| 25 % of the CIR600-1X100, 25 kW | 30.1 A per phase | 96.2 % efficient | 988 W of heat | 3,370 BTU/h to cool |
| 50 % of the CIR600-1X100, 50 kW | 60.1 A per phase | 96.9 % efficient | 1.6 kW of heat | 5,460 BTU/h to cool |
| 75 % of the CIR600-1X100, 75 kW | 90.2 A per phase | 97.0 % efficient | 2.3 kW of heat | 7,910 BTU/h to cool |
| 100 % of the CIR600-1X100, 100 kW | 120 A per phase | 96.8 % efficient | 3.3 kW of heat | 11,280 BTU/h to cool |
Current = kVA × load ÷ (√3 × volts).
Heat = load × (100 ÷ efficiency − 1); 1 kW is 3,412 BTU/h.
Efficiency
How efficient is the CIR600-1X100 at your load?
The CIR600-1X100 in normal double-conversion mode, from the 2026 catalog's efficiency curve. Drag along it to see the heat lost and its yearly cost.
- Load
- —
- Lost as heat
- —
- Heat to remove
- —
- Energy lost in a year, 24/7
- —
- Its cost in a year at per kWh
- —
From the 2026 catalog
What is the CIR600-1X100?
The code CIR600-1X100 orders these catalog items:
- 1 × CIR600-FRAME: 600 kVA frame, without power modules, 31.5 × 39.4 × 78.7 in (800 × 1,001 × 1,999 mm)
- 1 × CIR-PWR-100: 100 kVA hot-swappable power module, 103.6 lb (47 kg)
- Architecture: 1 × 100 kVA hot-swappable power module in a 600 kVA / 600 kW frame (6 slots, scalable to 6 modules / 600 kVA); parallel up to 8 units.
- Battery: external VRLA (battery bank sized separately). DC bus ±240 Vdc (480 Vdc total), 40 × 12 V blocks by default; selectable 30 to 50 blocks (±15 to ±25 per pole).
- Switchgear: 4 breakers included in the frame — main input, output, bypass input, maintenance bypass.
- Efficiency: up to 97%.
The lines every CIRRO shares, from technology to warranty, are in the CIRRO key facts and in the datasheet below.
1 × 100 kVA power modules fitted in a 6-slot frame: 5 free slots to grow or add redundancy.
Size and floor
How big it is
31.5" W × 39.4" D × 78.7" H (800 × 1,001 × 1,999 mm); 996.5 lb (452 kg) net.
Floor load = net weight ÷ footprint, without batteries outside the cabinet.
Installation
What does the CIRRO need in the room?
From the AEC US user manual of the CIRRO. Where the manual gives no distance, none is printed here: ask AEC.
- Clearances
- Front 36 in (914 mm), rear 31.5 in (800 mm), top 19.7 in (500 mm) on the 600, 800 and 1200 frames. Sides: not given.
- Wiring
- Hardwired: an electrician connects it to the panel.
- Cable entry
- Top, through the cable entry plate; Bottom (Only with the optional side wiring cabinet beside the UPS: its size from AEC)
- Breakers and terminals
- Four breakers (bypass input, maintenance bypass, main input, output) at the top of the frame behind the front door; power terminals behind both rear doors, 53–77 in (1,350–1,960 mm) above the floor. Battery breaker external.
- Door
- Hinge side not given.
- Space to pull a module
- Keep at least 27.8 in (705 mm) free in front to slide a module out.
- Units in parallel
- Up to 8 of the same model.
Datasheet
CIR600-1X100 datasheet.
The CIR600-1X100 in the AEC 2026 catalog, figure by figure. Compare it with every CIRRO model.
| Parameter | CIR600-1X100 |
|---|---|
| Power | |
| Rated power (kVA) | 100 |
| Active power (kW) | 100 |
| Output power factor | 1.0 |
| Electrical | |
| Input / output | 480 V three-phase, 4-wire (3P+N) |
| Topology | Online double conversion, modular N+X |
| Efficiency, up to | 97% |
| Battery DC bus | 480 V DC |
| Battery and runtime | |
| Battery type | VRLA (sealed lead-acid) |
| Battery configuration | External battery bank |
| Mechanical | |
| Form factor | Modular |
| Dimensions W × D × H | 31.5 × 39.4 × 78.7 in (800 × 1,001 × 1,999 mm) |
| Net weight | 996.5 lb (452 kg) |
| Footprint | 8.6 ft² (0.80 m²) |
| Common to every CIRRO | |
| Technology | 3-level IGBT; unity power factor (kVA = kW); 80 A settable charger |
| Display | personalized AEC red color touchscreen |
| Comms | RS232, RS485, USB, dry contacts, intelligent slot and EPO standard; battery cold start |
| Battery, CIR600-1X100 | external VRLA (battery bank sized separately). DC bus ±240 Vdc (480 Vdc total), 40 x 12 V blocks by default; selectable 30 to 50 blocks (±15 to ±25 per pole) |
| Network card | SNMP-M (SNMP) |
| Warranty | 3 years on UPS · 2 years on VRLA batteries |
| Quality system | ISO 9001:2015, the group's quality system (SGS) |
From the AEC 2026 catalog. Figures can change: the order confirmation rules.
Downloads
Manuals and catalogs.
The CIRRO documents cover every model of the series, this one included. PDF, in English.
Catalogs and datasheets
Quick answers
CIR600-1X100: what people ask
What is the output current of the CIR600-1X100?
120.3 A per phase at full load: 100 kVA ÷ (√3 × 480 V). Size the input breaker and the cables of the CIR600-1X100 from its installation manual and the local electrical code, not from this figure alone.
How much heat does the CIR600-1X100 give off?
About 3.3 kW, 11,280 BTU/h, at full load, where it is 96.8% efficient. Plan the room's cooling for a little more than that: the CIR600-1X100 is less efficient at part load and while its battery recharges.
How much power do 8 CIR600-1X100 give in parallel?
800 kVA: up to 8 units of the same model run in parallel, by the AEC US user manual of the CIRRO. Kept as N+1, with one unit spare, 8 CIR600-1X100 carry 700 kVA (700 kW).
Will the CIR600-1X100 fit through a standard door?
Yes: 31.5 in (800 mm) across its narrow side and 78.7 in (1,999 mm) high, it passes a standard 36 × 80-inch door upright, with little to spare in height. On the way in, check corridors, elevators and the floor load of the CIR600-1X100 (size section above).
The method, for any UPS: runtime explained · amps from kVA · heat output in BTU/h
CIRRO
Other CIRRO models
By power, the CIR600-1X100 is number 2 of 21 in the CIRRO series, which runs from 60 to 1,600 kVA. One size down is the CIR360-1X60 (40 kVA less and 360 lb lighter). One size up is the CIR360-2X60 (20 kVA more and 270 lb lighter).
Every CIRRO model side by side (21)
| Model | Power | Power against this model | Net weight | Weight against this model |
|---|---|---|---|---|
| CIR360-1X60 | 60 kVA | 40 kVA less | 636 lb | 360 lb lighter |
| CIR600-1X100 | 100 kVA | this page | 997 lb | this page |
| CIR360-2X60 | 120 kVA | 20 kVA more | 727 lb | 270 lb lighter |
| CIR360-3X60 | 180 kVA | 80 kVA more | 817 lb | 179 lb lighter |
| CIR600-2X100 | 200 kVA | 100 kVA more | 1,100 lb | 104 lb heavier |
| CIR360-4X60 | 240 kVA | 140 kVA more | 908 lb | 89 lb lighter |
| CIR360-5X60 | 300 kVA | 200 kVA more | 998 lb | 2 lb heavier |
| CIR360-6X60 | 360 kVA | 260 kVA more | 1,088 lb | 92 lb heavier |
| CIR600-4X100 | 400 kVA | 300 kVA more | 1,307 lb | 311 lb heavier |
| CIR600-5X100 | 500 kVA | 400 kVA more | 1,411 lb | 414 lb heavier |
| CIR600-6X100 | 600 kVA | 500 kVA more | 1,515 lb | 518 lb heavier |
| CIR800-7X100 | 700 kVA | 600 kVA more | 1,799 lb | 802 lb heavier |
| CIR800-8X100 | 800 kVA | 700 kVA more | 1,902 lb | 906 lb heavier |
| CIR1200-9X100 | 900 kVA | 800 kVA more | 2,308 lb | 1,312 lb heavier |
| CIR1200-10X100 | 1,000 kVA | 900 kVA more | 2,412 lb | 1,415 lb heavier |
| CIR1200-11X100 | 1,100 kVA | 1,000 kVA more | 2,515 lb | 1,519 lb heavier |
| CIR1200-12X100 | 1,200 kVA | 1,100 kVA more | 2,619 lb | 1,622 lb heavier |
| CIR1600-13X100 | 1,300 kVA | 1,200 kVA more | 3,485 lb | 2,489 lb heavier |
| CIR1600-14X100 | 1,400 kVA | 1,300 kVA more | 3,589 lb | 2,592 lb heavier |
| CIR1600-15X100 | 1,500 kVA | 1,400 kVA more | 3,693 lb | 2,696 lb heavier |
| CIR1600-16X100 | 1,600 kVA | 1,500 kVA more | 3,796 lb | 2,800 lb heavier |
Install and run it:RADIANT and CIRRO operating guide
The CIR600-1X100 for your project
Send the load, the voltage and the minutes you need from the CIR600-1X100. We reply with the configuration, the batteries and the lead time.