CIRRO · 480V three-phase UPS
CIR360-1X60 CIRRO 60 kVA, 480V three-phase UPS
The AEC CIRRO CIR360-1X60 is a 60 kVA / 60 kW online double-conversion UPS for 480 V three-phase loads, built on one 60 kVA power module, with external battery cabinets. Kept at 80 % of its rating, it carries loads up to 48 kW.
One of the frame's six module slots is fitted, so no module is spare at this size; five more modules take the frame to 360 kVA. As configured it weighs 636.4 lb (288.7 kg) net.
4-wire · 3P+N480 V 4-wire, wye: three phases, neutral and ground (277/480 V)
Drag to turnThe same on every CIRRO:The CIRRO display
Load by load
The CIR360-1X60 at 25, 50, 75 and 100 % load.
Its 60 kW rating in four steps, worked out from its own catalog figures.
| Load | Output current per phase, at 480 V | Efficiency | Heat to remove | Heat to remove (BTU/h) |
|---|---|---|---|---|
| 25 % of the CIR360-1X60, 15 kW | 18.0 A per phase | 95.1 % efficient | 773 W of heat | 2,640 BTU/h to cool |
| 50 % of the CIR360-1X60, 30 kW | 36.1 A per phase | 95.9 % efficient | 1.3 kW of heat | 4,380 BTU/h to cool |
| 75 % of the CIR360-1X60, 45 kW | 54.1 A per phase | 96.0 % efficient | 1.9 kW of heat | 6,400 BTU/h to cool |
| 100 % of the CIR360-1X60, 60 kW | 72.2 A per phase | 95.8 % efficient | 2.6 kW of heat | 8,980 BTU/h to cool |
Current = kVA × load ÷ (√3 × volts).
Heat = load × (100 ÷ efficiency − 1); 1 kW is 3,412 BTU/h.
Efficiency
How efficient is the CIR360-1X60 at your load?
The CIR360-1X60 in normal double-conversion mode, from the 2026 catalog's efficiency curve. Drag along it to see the heat lost and its yearly cost.
- Load
- —
- Lost as heat
- —
- Heat to remove
- —
- Energy lost in a year, 24/7
- —
- Its cost in a year at per kWh
- —
From the 2026 catalog
What is the CIR360-1X60?
The code CIR360-1X60 orders these catalog items:
- 1 × CIR360-FRAME: 360 kVA frame, without power modules, 23.6 × 39.4 × 78.7 in (600 × 1,000 × 2,000 mm)
- 1 × CIR-PWR-60: 60 kVA hot-swappable power module, 77 lb (34.9 kg)
- Architecture: 1 × 60 kVA hot-swappable power module in a 360 kVA / 360 kW frame (6 slots, scalable to 6 modules / 360 kVA); parallel up to 8 units.
- Battery: external VRLA (battery bank sized separately). DC bus ±240 Vdc (480 Vdc total), 40 × 12 V blocks by default; selectable ±15 to ±22 blocks per pole (30 to 44 blocks).
- Switchgear: 1 breaker included in the frame.
- Efficiency: up to 96%.
The lines every CIRRO shares, from technology to warranty, are in the CIRRO key facts and in the datasheet below.
1 × 60 kVA power modules fitted in a 6-slot frame: 5 free slots to grow or add redundancy.
Size and floor
How big it is
23.6" W × 39.3" D × 78.7" H (599 × 998 × 1,999 mm); 636.4 lb (288.7 kg) net. It ships in one carton of 27 × 42.7 × 82.1 in, 769.4 lb (349 kg) gross.
Floor load = net weight ÷ footprint, without batteries outside the cabinet.
Installation
What does the CIRRO need in the room?
From the AEC US user manual of the CIRRO. Where the manual gives no distance, none is printed here: ask AEC.
- Clearances
- Front 36 in (914 mm), rear 31.5 in (800 mm), top 19.7 in (500 mm) on the 600, 800 and 1200 frames. Sides: not given.
- Wiring
- Hardwired: an electrician connects it to the panel.
- Cable entry
- Top, through the cable entry plate; Bottom (Only with the optional side wiring cabinet beside the UPS: its size from AEC)
- Breakers and terminals
- One breaker in the frame (function not named in the manual); battery breaker external. Ask AEC for the 360's layout.
- Door
- Hinge side not given.
- Space to pull a module
- Keep at least 27.8 in (705 mm) free in front to slide a module out.
- Units in parallel
- Up to 8 of the same model.
- Note
- CIRRO 360: rear and top clearances, terminal place and drawings not issued yet.
Datasheet
CIR360-1X60 datasheet.
The CIR360-1X60 in the AEC 2026 catalog, figure by figure. Compare it with every CIRRO model.
| Parameter | CIR360-1X60 |
|---|---|
| Power | |
| Rated power (kVA) | 60 |
| Active power (kW) | 60 |
| Output power factor | 1.0 |
| Electrical | |
| Input / output | 480 V three-phase, 4-wire (3P+N) |
| Topology | Online double conversion, modular N+X |
| Efficiency, up to | 96% |
| Battery DC bus | 480 V DC |
| Battery and runtime | |
| Battery type | VRLA (sealed lead-acid) |
| Battery configuration | External battery bank |
| Mechanical | |
| Form factor | Modular |
| Dimensions W × D × H | 23.6 × 39.3 × 78.7 in (599 × 998 × 1,999 mm) |
| Net weight | 636.4 lb (288.7 kg) |
| Footprint | 6.4 ft² (0.60 m²) |
| Shipping | |
| Cartons | 1 |
| Shipping weight | 769.4 lb |
| Common to every CIRRO | |
| Technology | 3-level IGBT; unity power factor (kVA = kW); 80 A settable charger |
| Display | personalized AEC red color touchscreen |
| Comms | RS232, RS485, USB, dry contacts, intelligent slot and EPO standard; battery cold start |
| Battery, CIR360-1X60 | external VRLA (battery bank sized separately). DC bus ±240 Vdc (480 Vdc total), 40 x 12 V blocks by default; selectable ±15 to ±22 blocks per pole (30 to 44 blocks) |
| Network card | SNMP-M (SNMP) |
| Warranty | 3 years on UPS · 2 years on VRLA batteries |
| Quality system | ISO 9001:2015, the group's quality system (SGS) |
From the AEC 2026 catalog. Figures can change: the order confirmation rules.
Downloads
Manuals and catalogs.
The CIRRO documents cover every model of the series, this one included. PDF, in English.
Catalogs and datasheets
Quick answers
CIR360-1X60: what people ask
What is the output current of the CIR360-1X60?
72.2 A per phase at full load: 60 kVA ÷ (√3 × 480 V). Size the input breaker and the cables of the CIR360-1X60 from its installation manual and the local electrical code, not from this figure alone.
How much heat does the CIR360-1X60 give off?
About 2.6 kW, 8,980 BTU/h, at full load, where it is 95.8% efficient. Plan the room's cooling for a little more than that: the CIR360-1X60 is less efficient at part load and while its battery recharges.
How much power do 8 CIR360-1X60 give in parallel?
480 kVA: up to 8 units of the same model run in parallel, by the AEC US user manual of the CIRRO. Kept as N+1, with one unit spare, 8 CIR360-1X60 carry 420 kVA (420 kW).
Will the CIR360-1X60 fit through a standard door?
Yes: 23.6 in (599 mm) across its narrow side and 78.7 in (1,999 mm) high, it passes a standard 36 × 80-inch door upright, with little to spare in height. On the way in, check corridors, elevators and the floor load of the CIR360-1X60 (size section above).
The method, for any UPS: runtime explained · amps from kVA · heat output in BTU/h
CIRRO
Other CIRRO models
By power, the CIR360-1X60 is the smallest in the CIRRO series, which runs from 60 to 1,600 kVA. One size up is the CIR600-1X100 (40 kVA more and 360 lb heavier).
Every CIRRO model side by side (21)
| Model | Power | Power against this model | Net weight | Weight against this model |
|---|---|---|---|---|
| CIR360-1X60 | 60 kVA | this page | 636 lb | this page |
| CIR600-1X100 | 100 kVA | 40 kVA more | 997 lb | 360 lb heavier |
| CIR360-2X60 | 120 kVA | 60 kVA more | 727 lb | 90 lb heavier |
| CIR360-3X60 | 180 kVA | 120 kVA more | 817 lb | 181 lb heavier |
| CIR600-2X100 | 200 kVA | 140 kVA more | 1,100 lb | 464 lb heavier |
| CIR360-4X60 | 240 kVA | 180 kVA more | 908 lb | 271 lb heavier |
| CIR360-5X60 | 300 kVA | 240 kVA more | 998 lb | 362 lb heavier |
| CIR360-6X60 | 360 kVA | 300 kVA more | 1,088 lb | 452 lb heavier |
| CIR600-4X100 | 400 kVA | 340 kVA more | 1,307 lb | 671 lb heavier |
| CIR600-5X100 | 500 kVA | 440 kVA more | 1,411 lb | 775 lb heavier |
| CIR600-6X100 | 600 kVA | 540 kVA more | 1,515 lb | 878 lb heavier |
| CIR800-7X100 | 700 kVA | 640 kVA more | 1,799 lb | 1,162 lb heavier |
| CIR800-8X100 | 800 kVA | 740 kVA more | 1,902 lb | 1,266 lb heavier |
| CIR1200-9X100 | 900 kVA | 840 kVA more | 2,308 lb | 1,672 lb heavier |
| CIR1200-10X100 | 1,000 kVA | 940 kVA more | 2,412 lb | 1,775 lb heavier |
| CIR1200-11X100 | 1,100 kVA | 1,040 kVA more | 2,515 lb | 1,879 lb heavier |
| CIR1200-12X100 | 1,200 kVA | 1,140 kVA more | 2,619 lb | 1,983 lb heavier |
| CIR1600-13X100 | 1,300 kVA | 1,240 kVA more | 3,485 lb | 2,849 lb heavier |
| CIR1600-14X100 | 1,400 kVA | 1,340 kVA more | 3,589 lb | 2,953 lb heavier |
| CIR1600-15X100 | 1,500 kVA | 1,440 kVA more | 3,693 lb | 3,056 lb heavier |
| CIR1600-16X100 | 1,600 kVA | 1,540 kVA more | 3,796 lb | 3,160 lb heavier |
Install and run it:RADIANT and CIRRO operating guide
The CIR360-1X60 for your project