IST3-J · Single-phase UPS
IST3-J 1 kVA Online rack UPS 1 kVA, 2U, 230 V
The IST3-J 1 kVA is a 1 kVA / 1 kW single-phase online double-conversion UPS in a 2U, 19-inch chassis, 438 × 423 mm, with three internal 12 V 9 Ah batteries. For a network rack, a telecom cabinet or a single server where only two rack units are free; it also stands as a tower.
Quick answers
IST3-J 1 kVA: quick answers
- What it is
- The IST3-J 1 kVA is a 1 kVA / 1 kW single-phase online double-conversion UPS in a 2U, 19-inch chassis, 438 × 423 mm, with three internal 12 V 9 Ah batteries.
- Who it is for
- For a network rack, a telecom cabinet or a single server where only two rack units are free; it also stands as a tower.
- Supply and configuration
- 208 / 220 / 230 / 240 V
- Battery and backup
- 36 V · 3 min full load · < 10 h
- Size and weight
- 438 × 423 × 86 mm · 14 kg
- Ordering code
- IST3J-1-3X9
IST3-J
What sets apart the IST3-J 1 kVA
The 1 kVA is the shortest IST3-J: 423 mm deep and 14 kg, with one cooling fan and eight IEC C13 outlets. Its 36 V battery gives 4 minutes at full load and 15 at half load in AEC's data (the catalogue prints 3 minutes) and, unlike the 2 and 3 kVA, it has no discharge time limit: the battery alone decides how long it runs. The battery packs are hot-pluggable from the front.
For more backup the catalogue lists a 2U battery box of the same footprint (438 × 420 × 87 mm, 20 kg) with 2 × (3 × 12 V 9 Ah) for this rating; the codes IST3J-[kVA]-[n]X9 also pair it with BBJ rack cabinets of up to 8 × 12 V 9 Ah. The battery box always goes below the UPS in the rack.
- Against the IST3-J 2 kVA (one size up): Power 1000 VA / 1000 W against 2000 VA / 2000 W; Battery voltage 36 V against 48 V; Dimensions W × D × H 438 × 423 × 86 mm against 438 × 572 × 86 mm; Weight 14 kg against 20 kg.
Planning data
IST3-J 1 kVA: currents, breakers, cables, batteries
The rows and columns of the EMEA 2026 catalogue's and AEC manuals' tables that concern the IST3-J 1 kVA.
From 1 to 10 kVA, always 2U
| UPS | 1 kVA |
|---|---|
| Battery box: batteries | 2 × (3 × 12 V 9 Ah) |
| W × D × H (mm) | 438 × 420 × 87 |
| kg | 20 |
In the rack or on the floor
| Model | 1 kVA |
|---|---|
| AC input max. (A) | 6 |
| AC breaker (A) | 10 |
| DC input max. (A) | 29.1 (rated) |
| DC breaker (A) | — |
| AC cable (mm²) | 0.75 |
| DC cable (mm²) | 6 |
Installation
Installing the IST3-J 1 kVA: space, cables
Each figure with its source.
| Item | Figure | Source |
|---|---|---|
| Clearances | front 300 mm (recommended 500), rear 300 mm (recommended 500), left 300 mm (recommended 500), right 300 mm (recommended 500), top 500 mm | AEC IST3-J 1–3 user manual p.22 §3.1 |
| Cable entry | Plugs and sockets at the rear | AEC IST3-J 1–3 user manual |
| Operating temperature | −5 to 40 °C, best 20 °C | AEC IST3-J 1–3 user manual p.22 §3.1, p.24 |
| Switches and terminals | Input socket, IEC outputs, over-current protector and the battery port on the rear panel. | AEC IST3-J 1–3 user manual p.22 §3.1 |
Size and floor
How big it is
438 × 423 × 86 mm · 14 kg.
Floor load = weight ÷ footprint (14 kg).
Efficiency
How efficient is the AEC IST3-J 1 kVA at your load?
IST3-J 1 kVA, 1 kW at its rating, online, double conversion (AEC's measured curve). Heat to remove on this curve: 50%: 0.06 kW (η 88.7%) · 75%: 0.08 kW (η 90.06%) · 100%: 0.10 kW (η 90.83%). At 50% load, 24/7, it loses about 558 kWh a year.
How the curve is drawn and where each figure comes from: the IST3-J range page.
- Load
- —
- Lost as heat
- —
- Energy lost in a year, 24/7
- —
- Its cost in a year at € per kWh
- —
- The catalogue's examples use €0.20 per kWh.
Where each figure comes from
| Mode | Efficiency | Kind | Models | Source |
|---|---|---|---|---|
| Online, double conversion | 30%: 86.14% · 50%: 88.7% · 75%: 90.06% · 100%: 90.83% | Measured (AEC datasheet) | IST3-J 1 kVA | AEC technical datasheet IST3-J 1–3 kVA: AC/AC efficiency |
| ECO | 98.3% | Datasheet figure, load not stated | all | AEC technical datasheet IST3-J 1–3 kVA: AC/AC efficiency |
| Online, double conversion | 30%: 89.36% · 50%: 91.23% · 75%: 92.16% · 100%: 92.56% | Measured (AEC datasheet) | IST3-J 2 kVA | AEC technical datasheet IST3-J 1–3 kVA: AC/AC efficiency |
| Online, double conversion | 30%: 90.84% · 50%: 91.85% · 75%: 93.3% · 100%: 93.1% | Measured (AEC datasheet) | IST3-J 3 kVA | AEC technical datasheet IST3-J 1–3 kVA: AC/AC efficiency |
| Online, double conversion | 30%: 93.04% · 50%: 94.05% · 75%: 95.5% · 100%: 95.3% | Typical curve, derived from the datasheet efficiency of 95.5% (AEC method) | IST3-J 6 kVA · IST3-J 10 kVA | AEC technical datasheet IST3-J 1–3 kVA: AC/AC efficiency |
EMEA 2026 catalogue figures: Online, double conversion up to 95.5%.
Drag to turnTechnical data
Technical data IST3-J 1 kVA
Only this model's values, from the EMEA 2026 catalogue table.
| Rating | |
|---|---|
| Power (VA / W) | 1000 / 1000 |
| Efficiency (AC/AC) | up to 90.8% · 98.3% in ECO mode |
| Input | |
| Voltage range | 176–295 V > 75% load · 154–176 V 50–75% · 120–154 V < 50% |
| Frequency · connection | 50 / 60 Hz ± 10%, self-adapting · single phase, L + N + PE, TN system |
| Output | |
| Voltage | 208 / 220 / 230 / 240 V ± 1%, settable |
| Frequency · waveform · transfer | 50 / 60 Hz ± 0.2% in battery mode · sine wave · 0 ms |
| Voltage distortion | THD < 2% (linear load) |
| Power factor | 1.0 (kVA = kW) |
| Overload | 105–110% 10 min · 110–130% 1 min · 130–150% 1 s · > 150% 200 ms |
| Output outlets | 8 × C13 (1 kVA) · 8 × C13 + 1 × C19 (2–3 kVA) |
| Battery | |
| Battery voltage | 36 V |
| Backup · recharge | 3 min full load · < 10 h |
| General | |
| Communication | RS232 + USB · options: RS485 + dry contact, protocol card, SNMP |
| Protections | battery under-voltage, overload, short circuit, over-temperature, input overvoltage |
| Noise | < 50 dB |
| Environment | −5 … 50 °C (derated 40–50 °C) · 0–95% RH · IP20 · 2000 m |
| Dimensions W × D × H (mm) | 438 × 423 × 86 |
| Weight (kg) | 14 |
| Item | IST3-J 1 kVA |
|---|---|
| VA / W | 1000 / 1000 |
| W × D × H (mm) | 438 × 423 × 86, 2U |
| kg | 14 |
| Battery | 36 V, 3 min at full load |
| Outlets / version | 8 × IEC C13 |
Specifications are subject to change without notice.
More technical detailsordering codes
Ordering codes
Ordering codes IST3-J 1 kVA
| Code | Description |
|---|---|
| IST3J-1-3X9 · IST3J-2-4X9 · IST3J-3-6X9 | UPS with internal 12 V 9 Ah batteries (3 · 4 · 6) |
| IST3J-[kVA]-[n]X9 | 1–3 kVA with internal batteries plus BBJ / BBJ2 rack cabinets, n × 12 V 9 Ah in total |
| BBJ · BBJ2 | Rack battery cabinet, max. 8 × 12 V 9 Ah (2U) · max. 16 × 12 V 9 Ah (3U) |
Questions
Questions about the IST3-J 1 kVA
Rack or tower: how is the IST3-J 1 kVA installed?
In a 19-inch rack with two angle irons (default reading RCK), or upright on its support bases with the display set to TWR from the panel. With a battery box, two 1U joint bases are added per box.
What are the input limits of the IST3-J 1 kVA?
176–295 V above 75% load, 154–176 V at 50–75% and 120–154 V below 50%: at light load the battery is not touched down to 120 V. The maximum input current is 6 A, on a 10 A breaker.
How long does a 1 kVA UPS like the IST3-J 1 kVA run?
4 to 53 minutes at full load (1 kW), and 15 to 131 minutes at half load, with the AEC battery options in the table: the battery chosen sets the figure. With 3 × 12 V 9 Ah (IST3J-1-3X9): 4 minutes at 100% and 15 at 50%. For other loads and batteries use the backup-time tool.
How big is the AEC IST3-J 1 kVA and how much does it weigh?
The AEC IST3-J 1 kVA measures 438 × 423 × 86 mm; weight: 14 kg (size from AEC's CAD drawing, weight from the EMEA 2026 catalogue).
What is the ordering code of the AEC IST3-J 1 kVA?
In the EMEA 2026 catalogue the AEC IST3-J 1 kVA is listed as IST3J-1-3X9; AEC gives the full code, batteries included, from the load and the backup time.
Talk to an AEC engineer
Tell us the load, the supply and the backup time you need for the AEC IST3-J 1 kVA: we answer with the model and the batteries that fit. AEC International sells through distributors in about 80 countries and an agency in every Italian region: ask AEC which one serves your area.