IST3-J · Single-phase UPS

IST3-J 1 kVA Online rack UPS 1 kVA, 2U, 230 V

VRLA1 kVAonline rack UPS, 2U, 230 V

The IST3-J 1 kVA is a 1 kVA / 1 kW single-phase online double-conversion UPS in a 2U, 19-inch chassis, 438 × 423 mm, with three internal 12 V 9 Ah batteries. For a network rack, a telecom cabinet or a single server where only two rack units are free; it also stands as a tower.

1 kVA / 1 kWRating
438 × 423 × 86 mmW × D × H
14 kgWeight
36 VBattery

Quick answers

IST3-J 1 kVA: quick answers

What it is
The IST3-J 1 kVA is a 1 kVA / 1 kW single-phase online double-conversion UPS in a 2U, 19-inch chassis, 438 × 423 mm, with three internal 12 V 9 Ah batteries.
Who it is for
For a network rack, a telecom cabinet or a single server where only two rack units are free; it also stands as a tower.
Supply and configuration
208 / 220 / 230 / 240 V
Battery and backup
36 V · 3 min full load · < 10 h
Size and weight
438 × 423 × 86 mm · 14 kg
Ordering code
IST3J-1-3X9

IST3-J

What sets apart the IST3-J 1 kVA

The 1 kVA is the shortest IST3-J: 423 mm deep and 14 kg, with one cooling fan and eight IEC C13 outlets. Its 36 V battery gives 4 minutes at full load and 15 at half load in AEC's data (the catalogue prints 3 minutes) and, unlike the 2 and 3 kVA, it has no discharge time limit: the battery alone decides how long it runs. The battery packs are hot-pluggable from the front.

For more backup the catalogue lists a 2U battery box of the same footprint (438 × 420 × 87 mm, 20 kg) with 2 × (3 × 12 V 9 Ah) for this rating; the codes IST3J-[kVA]-[n]X9 also pair it with BBJ rack cabinets of up to 8 × 12 V 9 Ah. The battery box always goes below the UPS in the rack.

  • Against the IST3-J 2 kVA (one size up): Power 1000 VA / 1000 W against 2000 VA / 2000 W; Battery voltage 36 V against 48 V; Dimensions W × D × H 438 × 423 × 86 mm against 438 × 572 × 86 mm; Weight 14 kg against 20 kg.

Planning data

IST3-J 1 kVA: currents, breakers, cables, batteries

The rows and columns of the EMEA 2026 catalogue's and AEC manuals' tables that concern the IST3-J 1 kVA.

From 1 to 10 kVA, always 2U

IST3-J 1 kVA · From 1 to 10 kVA, always 2U
UPS1 kVA
Battery box: batteries2 × (3 × 12 V 9 Ah)
W × D × H (mm)438 × 420 × 87
kg20

In the rack or on the floor

IST3-J 1 kVA · In the rack or on the floor
Model1 kVA
AC input max. (A)6
AC breaker (A)10
DC input max. (A)29.1 (rated)
DC breaker (A)—
AC cable (mm²)0.75
DC cable (mm²)6

Installation

Installing the IST3-J 1 kVA: space, cables

Each figure with its source.

IST3-J 1 kVA · installation
ItemFigureSource
Clearancesfront 300 mm (recommended 500), rear 300 mm (recommended 500), left 300 mm (recommended 500), right 300 mm (recommended 500), top 500 mmAEC IST3-J 1–3 user manual p.22 §3.1
Cable entryPlugs and sockets at the rearAEC IST3-J 1–3 user manual
Operating temperature−5 to 40 °C, best 20 °CAEC IST3-J 1–3 user manual p.22 §3.1, p.24
Switches and terminalsInput socket, IEC outputs, over-current protector and the battery port on the rear panel.AEC IST3-J 1–3 user manual p.22 §3.1

Size and floor

How big it is

438 × 423 × 86 mm · 14 kg.

0.19 m²footprint
76 kg/m²floor load
0.09 mheight

Floor load = weight ÷ footprint (14 kg).

1.75 mFrontSide43842386

Efficiency

How efficient is the AEC IST3-J 1 kVA at your load?

IST3-J 1 kVA, 1 kW at its rating, online, double conversion (AEC's measured curve). Heat to remove on this curve: 50%: 0.06 kW (η 88.7%) · 75%: 0.08 kW (η 90.06%) · 100%: 0.10 kW (η 90.83%). At 50% load, 24/7, it loses about 558 kWh a year.

90.83%100% · Measured (AEC datasheet)

How the curve is drawn and where each figure comes from: the IST3-J range page.

Load
—
Lost as heat
—
Energy lost in a year, 24/7
—
Its cost in a year at € per kWh
—
The catalogue's examples use €0.20 per kWh.
Where each figure comes from
ModeEfficiencyKindModelsSource
Online, double conversion30%: 86.14% · 50%: 88.7% · 75%: 90.06% · 100%: 90.83%Measured (AEC datasheet)IST3-J 1 kVAAEC technical datasheet IST3-J 1–3 kVA: AC/AC efficiency
ECO98.3%Datasheet figure, load not statedallAEC technical datasheet IST3-J 1–3 kVA: AC/AC efficiency
Online, double conversion30%: 89.36% · 50%: 91.23% · 75%: 92.16% · 100%: 92.56%Measured (AEC datasheet)IST3-J 2 kVAAEC technical datasheet IST3-J 1–3 kVA: AC/AC efficiency
Online, double conversion30%: 90.84% · 50%: 91.85% · 75%: 93.3% · 100%: 93.1%Measured (AEC datasheet)IST3-J 3 kVAAEC technical datasheet IST3-J 1–3 kVA: AC/AC efficiency
Online, double conversion30%: 93.04% · 50%: 94.05% · 75%: 95.5% · 100%: 95.3%Typical curve, derived from the datasheet efficiency of 95.5% (AEC method)IST3-J 6 kVA · IST3-J 10 kVAAEC technical datasheet IST3-J 1–3 kVA: AC/AC efficiency

EMEA 2026 catalogue figures: Online, double conversion up to 95.5%.

AEC IST3-J 1 kVA, rendered from its 3D modelDrag to turn

In 3D

Look around the IST3-J 1 kVA

Technical data

Technical data IST3-J 1 kVA

Only this model's values, from the EMEA 2026 catalogue table.

IST3-J 1 kVA · Technical data
Rating
Power (VA / W)1000 / 1000
Efficiency (AC/AC)up to 90.8% · 98.3% in ECO mode
Input
Voltage range176–295 V > 75% load · 154–176 V 50–75% · 120–154 V < 50%
Frequency · connection50 / 60 Hz ± 10%, self-adapting · single phase, L + N + PE, TN system
Output
Voltage208 / 220 / 230 / 240 V ± 1%, settable
Frequency · waveform · transfer50 / 60 Hz ± 0.2% in battery mode · sine wave · 0 ms
Voltage distortionTHD < 2% (linear load)
Power factor1.0 (kVA = kW)
Overload105–110% 10 min · 110–130% 1 min · 130–150% 1 s · > 150% 200 ms
Output outlets8 × C13 (1 kVA) · 8 × C13 + 1 × C19 (2–3 kVA)
Battery
Battery voltage36 V
Backup · recharge3 min full load · < 10 h
General
CommunicationRS232 + USB · options: RS485 + dry contact, protocol card, SNMP
Protectionsbattery under-voltage, overload, short circuit, over-temperature, input overvoltage
Noise< 50 dB
Environment−5 … 50 °C (derated 40–50 °C) · 0–95% RH · IP20 · 2000 m
Dimensions W × D × H (mm)438 × 423 × 86
Weight (kg)14
IST3-J 1 kVA · Models
ItemIST3-J 1 kVA
VA / W1000 / 1000
W × D × H (mm)438 × 423 × 86, 2U
kg14
Battery36 V, 3 min at full load
Outlets / version8 × IEC C13

Specifications are subject to change without notice.

More technical detailsordering codes

Ordering codes

Ordering codes IST3-J 1 kVA

Ordering codes IST3-J 1 kVA
CodeDescription
IST3J-1-3X9 · IST3J-2-4X9 · IST3J-3-6X9UPS with internal 12 V 9 Ah batteries (3 · 4 · 6)
IST3J-[kVA]-[n]X91–3 kVA with internal batteries plus BBJ / BBJ2 rack cabinets, n × 12 V 9 Ah in total
BBJ · BBJ2Rack battery cabinet, max. 8 × 12 V 9 Ah (2U) · max. 16 × 12 V 9 Ah (3U)

Questions

Questions about the IST3-J 1 kVA

Rack or tower: how is the IST3-J 1 kVA installed?

In a 19-inch rack with two angle irons (default reading RCK), or upright on its support bases with the display set to TWR from the panel. With a battery box, two 1U joint bases are added per box.

What are the input limits of the IST3-J 1 kVA?

176–295 V above 75% load, 154–176 V at 50–75% and 120–154 V below 50%: at light load the battery is not touched down to 120 V. The maximum input current is 6 A, on a 10 A breaker.

How long does a 1 kVA UPS like the IST3-J 1 kVA run?

4 to 53 minutes at full load (1 kW), and 15 to 131 minutes at half load, with the AEC battery options in the table: the battery chosen sets the figure. With 3 × 12 V 9 Ah (IST3J-1-3X9): 4 minutes at 100% and 15 at 50%. For other loads and batteries use the backup-time tool.

How big is the AEC IST3-J 1 kVA and how much does it weigh?

The AEC IST3-J 1 kVA measures 438 × 423 × 86 mm; weight: 14 kg (size from AEC's CAD drawing, weight from the EMEA 2026 catalogue).

What is the ordering code of the AEC IST3-J 1 kVA?

In the EMEA 2026 catalogue the AEC IST3-J 1 kVA is listed as IST3J-1-3X9; AEC gives the full code, batteries included, from the load and the backup time.

Talk to an AEC engineer

Tell us the load, the supply and the backup time you need for the AEC IST3-J 1 kVA: we answer with the model and the batteries that fit. AEC International sells through distributors in about 80 countries and an agency in every Italian region: ask AEC which one serves your area.