IST3-J · Single-phase UPS
IST3-J 6 kVA Online rack UPS 6 kVA, 2U, 230 V
The IST3-J 6 kVA is a 6 kVA / 6 kW single-phase online double-conversion UPS in a 2U chassis of 10.6 kg, a long backup model that runs on an external battery. For racks that need 5 kW of protected power and a backup time chosen by the number of battery cabinets.
Quick answers
IST3-J 6 kVA: quick answers
- What it is
- The IST3-J 6 kVA is a 6 kVA / 6 kW single-phase online double-conversion UPS in a 2U chassis of 10.6 kg, a long backup model that runs on an external battery.
- Who it is for
- For racks that need 5 kW of protected power and a backup time chosen by the number of battery cabinets.
- Supply and configuration
- 208 / 220 / 230 / 240 V
- Battery and backup
- 192 V default (12–20 × 12 V settable) · external battery, any backup time
- Size and weight
- 438 × 500 × 86 mm · 10.6 kg
- Ordering code
- IST3J-6 · IST3J-6/10-[n]X9
IST3-J
What sets apart the IST3-J 6 kVA
The 6 kVA has no internal batteries: its 192 V string (12 to 20 blocks of 12 V, set through communication) sits in BBJ2 rack cabinets of 3U, each with up to 16 × 12 V 9 Ah. The codes IST3J-6/10-[n]X9 go from one to eight BBJ2, 16 to 128 batteries. Input and output connect on a wire terminal; the two IEC C13 outlets take up to 10 A each.
Its input works at full load from 176 to 275 V and keeps going down to 80 V with linear derating. The overload table differs from the 1–3 kVA: 115–130% for 10 minutes, 130–150% for 30 seconds.
- Against the IST3-J 3 kVA (one size down): Power 6000 VA / 6000 W against 3000 VA / 3000 W; Voltage range 176–275 V full load · 80–176 V linear derating against 176–295 V > 75% load · 154–176 V 50–75% · 120–154 V < 50%; Voltage 220 V ± 2% default · 208 / 220 / 230 / 240 V against 208 / 220 / 230 / 240 V ± 1%, settable; Voltage distortion THD < 1% linear · < 4% non-linear against THD < 2% (linear load); Overload 115–130% 10 min · 130–150% 30 s · > 150% 500 ms against 105–110% 10 min · 110–130% 1 min · 130–150% 1 s · > 150% 200 ms.
- Against the IST3-J 10 kVA (one size up): Power 6000 VA / 6000 W against 10000 VA / 10000 W; Weight 10.6 kg against 12.2 kg.
Planning data
IST3-J 6 kVA: currents, breakers, cables, batteries
The rows and columns of the EMEA 2026 catalogue's and AEC manuals' tables that concern the IST3-J 6 kVA.
In the rack or on the floor
| Model | 6 kVA |
|---|---|
| AC input max. (A) | 36 |
| AC breaker (A) | 50 |
| DC input max. (A) | 39 |
| DC breaker (A) | 50 |
| AC cable (mm²) | — |
| DC cable (mm²) | — |
Installation
Installing the IST3-J 6 kVA: space, cables
Each figure with its source.
| Item | Figure | Source |
|---|---|---|
| Clearances | rear 300 mm (recommended 500), left 300 mm (recommended 500), right 300 mm (recommended 500); front and top: not given | AEC IST3-J 6–10 user manual p.6 §1.3 |
| Cable entry | Rear terminal block | AEC IST3-J 6–10 user manual |
| Operating temperature | −5 to 40 °C, best 20–25 °C | AEC IST3-J 6–10 user manual p.6 §1.3 |
| Switches and terminals | Input breaker, terminal block and the battery port on the rear panel. | AEC IST3-J 6–10 user manual p.6 §1.3 |
Size and floor
How big it is
438 × 500 × 86 mm · 10.6 kg.
Floor load = weight ÷ footprint (10.6 kg).
Efficiency
How efficient is the AEC IST3-J 6 kVA at your load?
IST3-J 6 kVA, 6 kW at its rating, online, double conversion (typical curve, AEC's method). Heat to remove on this curve: 50%: 0.19 kW (η 94.05%) · 75%: 0.21 kW (η 95.5%) · 100%: 0.30 kW (η 95.3%). At 50% load, 24/7, it loses about 1,663 kWh a year.
How the curve is drawn and where each figure comes from: the IST3-J range page.
- Load
- —
- Lost as heat
- —
- Energy lost in a year, 24/7
- —
- Its cost in a year at € per kWh
- —
- The catalogue's examples use €0.20 per kWh.
Where each figure comes from
| Mode | Efficiency | Kind | Models | Source |
|---|---|---|---|---|
| Online, double conversion | 30%: 93.04% · 50%: 94.05% · 75%: 95.5% · 100%: 95.3% | Typical curve, derived from the datasheet efficiency of 95.5% (AEC method) | IST3-J 6 kVA · IST3-J 10 kVA | AEC technical datasheet IST3-J 1–3 kVA: AC/AC efficiency |
| ECO | 98.3% | Datasheet figure, load not stated | all | AEC technical datasheet IST3-J 1–3 kVA: AC/AC efficiency |
| Online, double conversion | 30%: 86.14% · 50%: 88.7% · 75%: 90.06% · 100%: 90.83% | Measured (AEC datasheet) | IST3-J 1 kVA | AEC technical datasheet IST3-J 1–3 kVA: AC/AC efficiency |
| Online, double conversion | 30%: 89.36% · 50%: 91.23% · 75%: 92.16% · 100%: 92.56% | Measured (AEC datasheet) | IST3-J 2 kVA | AEC technical datasheet IST3-J 1–3 kVA: AC/AC efficiency |
| Online, double conversion | 30%: 90.84% · 50%: 91.85% · 75%: 93.3% · 100%: 93.1% | Measured (AEC datasheet) | IST3-J 3 kVA | AEC technical datasheet IST3-J 1–3 kVA: AC/AC efficiency |
EMEA 2026 catalogue figures: Online, double conversion up to 95.5%.
Drag to turnTechnical data
Technical data IST3-J 6 kVA
Only this model's values, from the EMEA 2026 catalogue table.
| Rating | |
|---|---|
| Power (VA / W) | 6000 / 6000 |
| Efficiency (AC/AC) | up to 95.5% · 98.3% in ECO mode |
| Input | |
| Voltage range | 176–275 V full load · 80–176 V linear derating |
| Frequency · connection | 50 / 60 Hz ± 10%, self-adapting · single phase, L + N + PE, TN system |
| Output | |
| Voltage | 220 V ± 2% default · 208 / 220 / 230 / 240 V |
| Frequency · waveform · transfer | 50 / 60 Hz ± 0.2% in battery mode · sine wave · 0 ms |
| Voltage distortion | THD < 1% linear · < 4% non-linear |
| Power factor | 1.0 (kVA = kW) |
| Overload | 115–130% 10 min · 130–150% 30 s · > 150% 500 ms |
| Output outlets | 2 × IEC C13 (each ≤ 10 A) + wire terminal |
| Battery | |
| Battery voltage | 192 V default (12–20 × 12 V settable) |
| Backup · recharge | external battery, any backup time |
| General | |
| Communication | RS232 · intelligent slot options |
| Protections | battery under-voltage, overload, short circuit, over-temperature, input overvoltage |
| Noise | < 55 dB |
| Environment | −5 … 40 °C · 0–95% RH · < 1000 m (derate above) |
| Dimensions W × D × H (mm) | 438 × 500 × 86 |
| Weight (kg) | 10.6 |
6 kVA: long backup model only (L). Specifications are subject to change without notice.
More technical detailsordering codes
Ordering codes
Ordering codes IST3-J 6 kVA
| Code | Description |
|---|---|
| IST3J-[kVA]-[n]X9 | 1–3 kVA with internal batteries plus BBJ / BBJ2 rack cabinets, n × 12 V 9 Ah in total |
| IST3J-6 · IST3J-10 | 6 / 10 kVA, external batteries only |
| IST3J-6/10-[n]X9 | 6 / 10 kVA with 1 to 8 BBJ2 cabinets, 16 to 128 × 12 V 9 Ah |
| BBJ · BBJ2 | Rack battery cabinet, max. 8 × 12 V 9 Ah (2U) · max. 16 × 12 V 9 Ah (3U) |
Questions
Questions about the IST3-J 6 kVA
Does the IST3-J 6 kVA have internal batteries?
No. It is a long backup model (L): the battery is external, 192 V by default, in one to eight BBJ2 rack cabinets of 16 × 12 V 9 Ah each. The backup time is set by the battery you choose.
What breaker does the IST3-J 6 kVA need?
The catalogue recommends a 50 A upstream input breaker (36 A maximum input current) and a 50 A DC breaker for the battery, which draws up to 39 A. Size the cables on these currents.
How long does a 6 kVA UPS like the IST3-J 6 kVA run?
4 to 86 minutes at full load (6 kW), and 13 to 218 minutes at half load, with the AEC battery options in the table: the battery chosen sets the figure. With 16 × 12 V 9 Ah (IST3J-6-16X9): 4 minutes at 100% and 13 at 50%. For other loads and batteries use the backup-time tool.
How big is the AEC IST3-J 6 kVA and how much does it weigh?
The AEC IST3-J 6 kVA measures 438 × 500 × 86 mm; weight: 10.6 kg (EMEA 2026 catalogue).
What is the ordering code of the AEC IST3-J 6 kVA?
In the EMEA 2026 catalogue the AEC IST3-J 6 kVA is listed as IST3J-6, IST3J-6/10-[n]X9; AEC gives the full code, batteries included, from the load and the backup time.