IST3-J · Single-phase UPS

IST3-J 2 kVA Online rack UPS 2 kVA, 2U, 230 V

VRLA2 kVAonline rack UPS, 2U, 230 V

The IST3-J 2 kVA is a 2 kVA / 2 kW single-phase online double-conversion UPS, 2U high and 572 mm deep, with four internal 12 V 9 Ah batteries. For a rack of servers, storage and switches drawing up to about 1.8 kW, in a data cabinet with standard depth.

2 kVA / 2 kWRating
438 × 572 × 86 mmW × D × H
20 kgWeight
48 VBattery

Quick answers

IST3-J 2 kVA: quick answers

What it is
The IST3-J 2 kVA is a 2 kVA / 2 kW single-phase online double-conversion UPS, 2U high and 572 mm deep, with four internal 12 V 9 Ah batteries.
Who it is for
For a rack of servers, storage and switches drawing up to about 1.8 kW, in a data cabinet with standard depth.
Supply and configuration
208 / 220 / 230 / 240 V
Battery and backup
48 V · 3 min full load · < 10 h
Size and weight
438 × 572 × 86 mm · 20 kg
Ordering code
IST3J-2-4X9

IST3-J

What sets apart the IST3-J 2 kVA

From 2 kVA the IST3-J is 572 mm deep and adds an IEC C19 outlet to the eight C13, for a server with a 16 A cord. Its 48 V battery gives 2 minutes at full load and 8 at half load in AEC's data (the catalogue prints 3 minutes); above 75% load the UPS caps the discharge time (6.0 minutes at 75% down to 3.0 at 100%) to protect the battery.

With the optional programmable outlets, non-critical loads switch off after a set time on battery (0–999 minutes, from the PC), so the critical ones run longer. The optional 7 A charging module raises the charge current from 1 A to as much as 8 A for larger external batteries.

  • Against the IST3-J 1 kVA (one size down): Power 2000 VA / 2000 W against 1000 VA / 1000 W; Battery voltage 48 V against 36 V; Dimensions W × D × H 438 × 572 × 86 mm against 438 × 423 × 86 mm; Weight 20 kg against 14 kg.
  • Against the IST3-J 3 kVA (one size up): Power 2000 VA / 2000 W against 3000 VA / 3000 W; Battery voltage 48 V against 72 V; Weight 20 kg against 26 kg.

Planning data

IST3-J 2 kVA: currents, breakers, cables, batteries

The rows and columns of the EMEA 2026 catalogue's and AEC manuals' tables that concern the IST3-J 2 kVA.

From 1 to 10 kVA, always 2U

IST3-J 2 kVA · From 1 to 10 kVA, always 2U
UPS2 kVA
Battery box: batteries2 × (4 × 12 V 9 Ah)
W × D × H (mm)438 × 570 × 87
kg29

In the rack or on the floor

IST3-J 2 kVA · In the rack or on the floor
Model2 kVA
AC input max. (A)12
AC breaker (A)20
DC input max. (A)42.6 (rated)
DC breaker (A)—
AC cable (mm²)1.5
DC cable (mm²)6

Installation

Installing the IST3-J 2 kVA: space, cables

Each figure with its source.

IST3-J 2 kVA · installation
ItemFigureSource
Clearancesfront 300 mm (recommended 500), rear 300 mm (recommended 500), left 300 mm (recommended 500), right 300 mm (recommended 500), top 500 mmAEC IST3-J 1–3 user manual p.22 §3.1
Cable entryPlugs and sockets at the rearAEC IST3-J 1–3 user manual
Operating temperature−5 to 40 °C, best 20 °CAEC IST3-J 1–3 user manual p.22 §3.1, p.24
Switches and terminalsInput socket, IEC outputs, over-current protector and the battery port on the rear panel.AEC IST3-J 1–3 user manual p.22 §3.1

Size and floor

How big it is

438 × 572 × 86 mm · 20 kg.

0.25 m²footprint
80 kg/m²floor load
0.09 mheight

Floor load = weight ÷ footprint (20 kg).

1.75 mFrontSide43857286

Efficiency

How efficient is the AEC IST3-J 2 kVA at your load?

IST3-J 2 kVA, 2 kW at its rating, online, double conversion (AEC's measured curve). Heat to remove on this curve: 50%: 0.10 kW (η 91.23%) · 75%: 0.13 kW (η 92.16%) · 100%: 0.16 kW (η 92.56%). At 50% load, 24/7, it loses about 842 kWh a year.

92.56%100% · Measured (AEC datasheet)

How the curve is drawn and where each figure comes from: the IST3-J range page.

Load
—
Lost as heat
—
Energy lost in a year, 24/7
—
Its cost in a year at € per kWh
—
The catalogue's examples use €0.20 per kWh.
Where each figure comes from
ModeEfficiencyKindModelsSource
Online, double conversion30%: 89.36% · 50%: 91.23% · 75%: 92.16% · 100%: 92.56%Measured (AEC datasheet)IST3-J 2 kVAAEC technical datasheet IST3-J 1–3 kVA: AC/AC efficiency
ECO98.3%Datasheet figure, load not statedallAEC technical datasheet IST3-J 1–3 kVA: AC/AC efficiency
Online, double conversion30%: 86.14% · 50%: 88.7% · 75%: 90.06% · 100%: 90.83%Measured (AEC datasheet)IST3-J 1 kVAAEC technical datasheet IST3-J 1–3 kVA: AC/AC efficiency
Online, double conversion30%: 90.84% · 50%: 91.85% · 75%: 93.3% · 100%: 93.1%Measured (AEC datasheet)IST3-J 3 kVAAEC technical datasheet IST3-J 1–3 kVA: AC/AC efficiency
Online, double conversion30%: 93.04% · 50%: 94.05% · 75%: 95.5% · 100%: 95.3%Typical curve, derived from the datasheet efficiency of 95.5% (AEC method)IST3-J 6 kVA · IST3-J 10 kVAAEC technical datasheet IST3-J 1–3 kVA: AC/AC efficiency

EMEA 2026 catalogue figures: Online, double conversion up to 95.5%.

AEC IST3-J 2 kVA, rendered from its 3D modelDrag to turn

In 3D

Look around the IST3-J 2 kVA

Technical data

Technical data IST3-J 2 kVA

Only this model's values, from the EMEA 2026 catalogue table.

IST3-J 2 kVA · Technical data
Rating
Power (VA / W)2000 / 2000
Efficiency (AC/AC)up to 92.6% · 98.3% in ECO mode
Input
Voltage range176–295 V > 75% load · 154–176 V 50–75% · 120–154 V < 50%
Frequency · connection50 / 60 Hz ± 10%, self-adapting · single phase, L + N + PE, TN system
Output
Voltage208 / 220 / 230 / 240 V ± 1%, settable
Frequency · waveform · transfer50 / 60 Hz ± 0.2% in battery mode · sine wave · 0 ms
Voltage distortionTHD < 2% (linear load)
Power factor1.0 (kVA = kW)
Overload105–110% 10 min · 110–130% 1 min · 130–150% 1 s · > 150% 200 ms
Output outlets8 × C13 (1 kVA) · 8 × C13 + 1 × C19 (2–3 kVA)
Battery
Battery voltage48 V
Backup · recharge3 min full load · < 10 h
General
CommunicationRS232 + USB · options: RS485 + dry contact, protocol card, SNMP
Protectionsbattery under-voltage, overload, short circuit, over-temperature, input overvoltage
Noise< 50 dB
Environment−5 … 50 °C (derated 40–50 °C) · 0–95% RH · IP20 · 2000 m
Dimensions W × D × H (mm)438 × 572 × 86
Weight (kg)20

Specifications are subject to change without notice.

More technical detailsordering codes

Ordering codes

Ordering codes IST3-J 2 kVA

Ordering codes IST3-J 2 kVA
CodeDescription
IST3J-1-3X9 · IST3J-2-4X9 · IST3J-3-6X9UPS with internal 12 V 9 Ah batteries (3 · 4 · 6)
IST3J-[kVA]-[n]X91–3 kVA with internal batteries plus BBJ / BBJ2 rack cabinets, n × 12 V 9 Ah in total
BBJ · BBJ2Rack battery cabinet, max. 8 × 12 V 9 Ah (2U) · max. 16 × 12 V 9 Ah (3U)

Questions

Questions about the IST3-J 2 kVA

How much rack space do the IST3-J 2 kVA and its batteries take?

2U for the UPS (438 × 572 × 86 mm, 20 kg) and 2U for each battery box of the same footprint, which holds 2 × (4 × 12 V 9 Ah) and weighs 29 kg. The catalogue's example rack is the UPS with two battery boxes below it.

What breaker and cable does the IST3-J 2 kVA need?

12 A maximum input current, a 20 A breaker without leakage protection and a 1.5 mm² AC cable for about 5 m; 6 mm² for the external battery, rated 42.6 A.

How long does a 2 kVA UPS like the IST3-J 2 kVA run?

2 to 41 minutes at full load (2 kW), and 8 to 101 minutes at half load, with the AEC battery options in the table: the battery chosen sets the figure. With 4 × 12 V 9 Ah (IST3J-2-4X9): 2 minutes at 100% and 8 at 50%. For other loads and batteries use the backup-time tool.

How big is the AEC IST3-J 2 kVA and how much does it weigh?

The AEC IST3-J 2 kVA measures 438 × 572 × 86 mm; weight: 20 kg (size from AEC's CAD drawing, weight from the EMEA 2026 catalogue).

What is the ordering code of the AEC IST3-J 2 kVA?

In the EMEA 2026 catalogue the AEC IST3-J 2 kVA is listed as IST3J-2-4X9; AEC gives the full code, batteries included, from the load and the backup time.

Talk to an AEC engineer