IST3 · Single-phase UPS
IST3-3 Single-phase online UPS 3 kVA, tower, 230 V
The IST3-3 is a 3 kVA / 3000 W single-phase online double-conversion tower UPS with six internal 12 V 9 Ah batteries. For a full small server room on a 230 V socket circuit: servers, storage, switches and a router on one UPS.
Quick answers
IST3-3: quick answers
- What it is
- The IST3-3 is a 3 kVA / 3000 W single-phase online double-conversion tower UPS with six internal 12 V 9 Ah batteries.
- Who it is for
- For a full small server room on a 230 V socket circuit: servers, storage, switches and a router on one UPS.
- Supply and configuration
- 208 / 220 / 230 / 240 V
- Battery and backup
- 72 V · 3 min at full load
- Size and weight
- 190 × 397 × 330 mm · 22.5 / 9.2 kg
- Ordering code
- IST3-3-6X9 · IST3-3-L
IST3
What sets apart the IST3-3
The IST3-3 is the largest IST3 that still plugs in: same 190 × 397 × 330 mm cabinet as the IST3-2, 22.5 kg with six 9 Ah blocks (72 V battery). Its maximum input current is 18 A, so the catalogue asks for a 32 A breaker and a 4 mm² cable, more than an ordinary socket circuit: plan the supply before delivery.
Backup is 2 minutes at full load and 8 at half load in AEC's data, as on the 1 and 2 kVA (the catalogue prints 3 minutes). Its noise rises to below 55 dB (below 50 dB on the smaller two), worth knowing if it stands in an office.
- Against the IST3-2 (one size down): Power 3000 VA / 3000 W against 2000 VA / 2000 W; Voltage, standard model 72 V against 48 V; Voltage, long backup model 96 V against 72 V; Noise < 55 dB against < 50 dB; Weight standard / long backup 22.5 / 9.2 kg against 17.6 / 9.0 kg.
- Against the IST3-6 (one size up): Power 3000 VA / 3000 W against 6000 VA / 6000 W; Voltage range 176–295 V full load · 154–176 V load < 75% · 120–154 V load < 50% against 176–275 V full load · 80–176 V linear derating; Voltage distortion THD < 3% (linear load) against THD < 1% linear · < 4% non-linear; Overload 100–130% 1 min · 130–150% 1 s · > 150% 200 ms against 105–130% 10 min (1 min above 30 °C) · 130–150% 30 s · > 150% 500 ms; Voltage, standard model 72 V against 192 V (16–20 × 12 V settable).
Planning data
IST3-3: currents, breakers, cables, batteries
The rows and columns of the EMEA 2026 catalogue's and AEC manuals' tables that concern the IST3-3.
Wall socket or terminal bar
| Model | 3 kVA |
|---|---|
| AC input max. (A) | 18 |
| AC breaker (A) | 32 |
| DC input max. (A, long backup) | 42 |
| DC breaker (A) | 50 |
| AC cable (mm²) | 4 |
| Battery cable (mm²) | 6 |
Installation
Installing the IST3-3: space, cables
Each figure with its source.
| Item | Figure | Source |
|---|---|---|
| Clearances | rear 300 mm (recommended 500), left 300 mm (recommended 500), right 300 mm (recommended 500); front and top: not given | AEC IST3 user manual p.6 §1.2 |
| Cable entry | Plugs and sockets at the rear | AEC IST3 user manual |
| Operating temperature | −5 to 40 °C, best 20–25 °C | AEC IST3 user manual p.6 §1.2 |
| Switches and terminals | Sockets, over-current protector and the battery connector on the rear panel. | AEC IST3 user manual p.6 §1.2 |
Size and floor
How big it is
190 × 397 × 330 mm · 22.5 / 9.2 kg.
Floor load = weight ÷ footprint: 122 kg/m² at the lowest weight given (9.2 kg), 298 kg/m² at the highest (22.5 kg).
Efficiency
How efficient is the AEC IST3-3 at your load?
IST3-3, 3 kW at its rating, online, double conversion (AEC's measured curve). Heat to remove on this curve: 50%: 0.13 kW (η 91.85%) · 75%: 0.16 kW (η 93.3%) · 100%: 0.22 kW (η 93.1%). At 50% load, 24/7, it loses about 1,166 kWh a year.
How the curve is drawn and where each figure comes from: the IST3 range page. The IST3 pages of the EMEA 2026 catalogue give no efficiency figure. The 1, 2 and 3 kVA curves are the ones AEC measured on the IST3-J of the same rating (AEC technical datasheet IST3-J 1–3 kVA), which AEC states has the same electronics; the 6 and 10 kVA curve has the same shape, moved to their 95.5% figure.
- Load
- —
- Lost as heat
- —
- Energy lost in a year, 24/7
- —
- Its cost in a year at € per kWh
- —
- The catalogue's examples use €0.20 per kWh.
Where each figure comes from
| Mode | Efficiency | Kind | Models | Source |
|---|---|---|---|---|
| Online, double conversion | 30%: 90.84% · 50%: 91.85% · 75%: 93.3% · 100%: 93.1% | Measured (AEC datasheet) | IST3-3 | AEC technical datasheet IST3-J 1–3 kVA: AC/AC efficiency |
| ECO | 98.3% | Datasheet figure, load not stated | all | AEC technical datasheet IST3-J 1–3 kVA: AC/AC efficiency |
| Online, double conversion | 30%: 86.14% · 50%: 88.7% · 75%: 90.06% · 100%: 90.83% | Measured (AEC datasheet) | IST3-1 | AEC technical datasheet IST3-J 1–3 kVA: AC/AC efficiency |
| Online, double conversion | 30%: 89.36% · 50%: 91.23% · 75%: 92.16% · 100%: 92.56% | Measured (AEC datasheet) | IST3-2 | AEC technical datasheet IST3-J 1–3 kVA: AC/AC efficiency |
| Online, double conversion | 30%: 93.04% · 50%: 94.05% · 75%: 95.5% · 100%: 95.3% | Typical curve, derived from the datasheet efficiency of 95.5% (AEC method) | IST3-6 · IST3-10 | AEC technical datasheet IST3-J 1–3 kVA: AC/AC efficiency |
Drag to turnTechnical data
Technical data IST3-3
Only this model's values, from the EMEA 2026 catalogue table.
| Rating | |
|---|---|
| Power (VA / W) | 3000 / 3000 |
| Efficiency (AC/AC) | up to 93.3% · 98.3% in ECO mode |
| Input | |
| Voltage range | 176–295 V full load · 154–176 V load < 75% · 120–154 V load < 50% |
| Frequency · connection | 50 / 60 Hz ± 10%, self-adapting · single phase, L + N + PE |
| Output | |
| Voltage | 220 V ± 2% (default) · 208 / 220 / 230 / 240 V settable from the panel |
| Frequency · waveform | 50 / 60 Hz ± 0.2% in battery mode · sine wave |
| Voltage distortion | THD < 3% (linear load) |
| Power factor · transfer time | 1.0 (kVA = kW) · 0 ms mains to battery |
| Overload | 100–130% 1 min · 130–150% 1 s · > 150% 200 ms |
| Battery | |
| Voltage, standard model | 72 V |
| Voltage, long backup model | 96 V |
| Backup time, standard model | 3 min at full load |
| Charge recovery | standard model < 10 h · long backup: depends on the battery pack |
| General | |
| Communication | RS232 and USB standard · SNMP card or RS485 and dry-contact card optional · EPO |
| Protections | battery undervoltage, overload, short circuit, over-temperature, input overvoltage |
| Noise | < 55 dB |
| Environment | −5 … 40 °C · 0–95% RH non-condensing · ≤ 1000 m without derating |
| Dimensions W × D × H, standard | 190 × 397 × 330 |
| Dimensions W × D × H, long backup | 190 × 397 × 330 |
| Weight standard / long backup (kg) | 22.5 / 9.2 |
| Item | IST3-3 |
|---|---|
| VA / W | 3000 / 3000 |
| Internal batteries | 6 × 9 Ah · 72 V |
| Backup, full / half load | 3 min |
| W × D × H (mm) | 190 × 397 × 330 |
| kg | 22.5 |
| Long backup: battery | 96 V |
| Long backup: kg | 9.2 |
Specifications are subject to change without notice.
More technical detailsordering codes
Ordering codes
Ordering codes IST3-3
| Code | Description |
|---|---|
| IST3-1-2X9 · IST3-2-4X9 · IST3-3-6X9 | Standard models with internal 12 V 9 Ah batteries (2, 4, 6) |
| IST3-1-L · IST3-2-L · IST3-3-L | Long backup, external batteries only (36 / 72 / 96 V) |
| IST3-[kVA]-[n]X9 | UPS with battery cabinet BB1, BB2 or BB3, n × 12 V 9 Ah in total |
| DRYCNT-IST3/9 · SNMP | Dry-contact relay board · internal SNMP board |
| MBYP-3K · MBYP-6K | External manual maintenance bypass, rack, max. 3 kVA · max. 10 kVA |
Questions
Questions about the IST3-3
Does the IST3-3 plug into a normal socket?
Not without a check: it has an input socket, but the catalogue gives an 18 A maximum input current with a 32 A breaker and 4 mm² cable. Have an electrician check that the circuit carries it.
How do I get a longer backup from the IST3-3?
Add a BB2 cabinet with up to 12 × 12 V 9 Ah (code IST3-3-12X9: 8 minutes at full load and 24 at half load in AEC's data), or choose the long backup model IST3-3-L with an external 96 V battery. The backup then depends on the battery chosen; AEC sizes it on your load.
How long does a 3 kVA UPS like the IST3-3 run?
2 to 86 minutes at full load (3 kW), and 8 to 218 minutes at half load, with the AEC battery options in the table: the battery chosen sets the figure. With 6 × 12 V 9 Ah (IST3-3-6X9): 2 minutes at 100% and 8 at 50%. For other loads and batteries use the backup-time tool.
How big is the AEC IST3-3 and how much does it weigh?
The AEC IST3-3 measures 190 × 397 × 330 mm; weight: 22.5 / 9.2 kg (size from AEC's CAD drawing, weight from the EMEA 2026 catalogue).
What is the ordering code of the AEC IST3-3?
In the EMEA 2026 catalogue the AEC IST3-3 is listed as IST3-3-6X9, IST3-3-L; AEC gives the full code, batteries included, from the load and the backup time.
Talk to an AEC engineer
Tell us the load, the supply and the backup time you need for the AEC IST3-3: we answer with the model and the batteries that fit. AEC International sells through distributors in about 80 countries and an agency in every Italian region: ask AEC which one serves your area.