IST3 · Single-phase UPS
IST3-10 Single-phase online UPS 10 kVA, tower, 230 V
The IST3-10 is a 10 kVA / 10 kW single-phase online double-conversion tower UPS, the largest IST3, with 16 internal 12 V 9 Ah batteries. For buildings and plants with only a single-phase supply and loads up to about 10 kW: IT rooms, shops, surgeries, control rooms.
Quick answers
IST3-10: quick answers
- What it is
- The IST3-10 is a 10 kVA / 10 kW single-phase online double-conversion tower UPS, the largest IST3, with 16 internal 12 V 9 Ah batteries.
- Who it is for
- For buildings and plants with only a single-phase supply and loads up to about 10 kW: IT rooms, shops, surgeries, control rooms.
- Supply and configuration
- 208 / 220 / 230 / 240 V
- Battery and backup
- 192 V (16–20 × 12 V settable) · 1–15 min full / half load
- Size and weight
- 230 × 524 × 553 mm · 56.2 / 12.5 kg
- Ordering code
- IST3-10-16X9 · IST3-10-L
IST3
What sets apart the IST3-10
The IST3-10 has the same 230 × 524 × 553 mm cabinet as the IST3-6 and weighs only 1.7 kg more (56.2 kg). With the same 16 × 9 Ah battery it gives 2 minutes at full load and 5 at half load in AEC's data (the catalogue prints 1 and 15), so at 10 kVA most projects add batteries: a BB3 with up to 32 blocks, or a BB5 with 100 × 9 Ah.
It draws up to 60 A from the mains, so it takes a 100 A breaker and a 10 mm² cable; the long backup model draws up to 65 A from the battery. For service without stopping the load there is the internal maintenance bypass switch, or the external rack MBYP-6K for UPS up to 10 kVA.
- Against the IST3-6 (one size down): Power 10000 VA / 10000 W against 6000 VA / 6000 W; Backup time, standard model 1–15 min full / half load against 5–20 min full / half load; Weight standard / long backup 56.2 / 12.5 kg against 54.5 / 11.0 kg.
Planning data
IST3-10: currents, breakers, cables, batteries
The rows and columns of the EMEA 2026 catalogue's and AEC manuals' tables that concern the IST3-10.
Wall socket or terminal bar
| Model | 10 kVA |
|---|---|
| AC input max. (A) | 60 |
| AC breaker (A) | 100 |
| DC input max. (A, long backup) | 65 |
| DC breaker (A) | 100 |
| AC cable (mm²) | 10 |
| Battery cable (mm²) | 10 |
Installation
Installing the IST3-10: space, cables
Each figure with its source.
| Item | Figure | Source |
|---|---|---|
| Clearances | rear 300 mm (recommended 500), left 300 mm (recommended 500), right 300 mm (recommended 500); front and top: not given | AEC IST3 user manual p.6 §1.2 |
| Cable entry | Rear terminal block | AEC IST3 user manual |
| Operating temperature | −5 to 40 °C, best 20–25 °C | AEC IST3 user manual p.6 §1.2 |
| Switches and terminals | Terminal block (input, output, battery) under a cover at the rear; mains, bypass and battery breakers and the maintenance bypass switch on the rear panel (standard model). | AEC IST3 user manual p.6 §1.2 |
Size and floor
How big it is
230 × 524 × 553 mm · 56.2 / 12.5 kg.
Floor load = weight ÷ footprint: 104 kg/m² at the lowest weight given (12.5 kg), 466 kg/m² at the highest (56.2 kg).
Efficiency
How efficient is the AEC IST3-10 at your load?
IST3-10, 10 kW at its rating, online, double conversion (typical curve, AEC's method). Heat to remove on this curve: 50%: 0.32 kW (η 94.05%) · 75%: 0.35 kW (η 95.5%) · 100%: 0.49 kW (η 95.3%). At 50% load, 24/7, it loses about 2,771 kWh a year.
How the curve is drawn and where each figure comes from: the IST3 range page. The IST3 pages of the EMEA 2026 catalogue give no efficiency figure. The 1, 2 and 3 kVA curves are the ones AEC measured on the IST3-J of the same rating (AEC technical datasheet IST3-J 1–3 kVA), which AEC states has the same electronics; the 6 and 10 kVA curve has the same shape, moved to their 95.5% figure.
- Load
- —
- Lost as heat
- —
- Energy lost in a year, 24/7
- —
- Its cost in a year at € per kWh
- —
- The catalogue's examples use €0.20 per kWh.
Where each figure comes from
| Mode | Efficiency | Kind | Models | Source |
|---|---|---|---|---|
| Online, double conversion | 30%: 93.04% · 50%: 94.05% · 75%: 95.5% · 100%: 95.3% | Typical curve, derived from the datasheet efficiency of 95.5% (AEC method) | IST3-10 · IST3-6 | AEC technical datasheet IST3-J 1–3 kVA: AC/AC efficiency |
| ECO | 98.3% | Datasheet figure, load not stated | all | AEC technical datasheet IST3-J 1–3 kVA: AC/AC efficiency |
| Online, double conversion | 30%: 86.14% · 50%: 88.7% · 75%: 90.06% · 100%: 90.83% | Measured (AEC datasheet) | IST3-1 | AEC technical datasheet IST3-J 1–3 kVA: AC/AC efficiency |
| Online, double conversion | 30%: 89.36% · 50%: 91.23% · 75%: 92.16% · 100%: 92.56% | Measured (AEC datasheet) | IST3-2 | AEC technical datasheet IST3-J 1–3 kVA: AC/AC efficiency |
| Online, double conversion | 30%: 90.84% · 50%: 91.85% · 75%: 93.3% · 100%: 93.1% | Measured (AEC datasheet) | IST3-3 | AEC technical datasheet IST3-J 1–3 kVA: AC/AC efficiency |
Drag to turnTechnical data
Technical data IST3-10
Only this model's values, from the EMEA 2026 catalogue table.
| Rating | |
|---|---|
| Power (VA / W) | 10000 / 10000 |
| Efficiency (AC/AC) | up to 95.5% · 98.3% in ECO mode |
| Input | |
| Voltage range | 176–275 V full load · 80–176 V linear derating |
| Frequency · connection | 50 / 60 Hz ± 10%, self-adapting · single phase, L + N + PE |
| Output | |
| Voltage | 220 V ± 2% (default) · 208 / 220 / 230 / 240 V settable from the panel |
| Frequency · waveform | 50 / 60 Hz ± 0.2% in battery mode · sine wave |
| Voltage distortion | THD < 1% linear · < 4% non-linear |
| Power factor · transfer time | 1.0 (kVA = kW) · 0 ms mains to battery |
| Overload | 105–130% 10 min (1 min above 30 °C) · 130–150% 30 s · > 150% 500 ms |
| Battery | |
| Voltage, standard model | 192 V (16–20 × 12 V settable) |
| Voltage, long backup model | 192 V |
| Backup time, standard model | 1–15 min full / half load |
| Charge recovery | standard model < 10 h · long backup: depends on the battery pack |
| General | |
| Communication | RS232 and USB standard · SNMP card or RS485 and dry-contact card optional · EPO |
| Protections | battery undervoltage, overload, short circuit, over-temperature, input overvoltage |
| Noise | < 55 dB |
| Environment | −5 … 40 °C · 0–95% RH non-condensing · ≤ 1000 m without derating |
| Dimensions W × D × H, standard | 230 × 524 × 553 mm |
| Dimensions W × D × H, long backup | 190 × 429 × 337 mm |
| Weight standard / long backup (kg) | 56.2 / 12.5 |
| Item | IST3-10 |
|---|---|
| VA / W | 10000 / 10000 |
| Internal batteries | 16 × 9 Ah · 192 V |
| Backup, full / half load | 1 / 15 min |
| W × D × H (mm) | 230 × 524 × 553 |
| kg | 56.2 |
| Long backup: battery | 192 V |
| Long backup: kg | 12.5 |
Specifications are subject to change without notice.
More technical detailsordering codes
Ordering codes
Ordering codes IST3-10
| Code | Description |
|---|---|
| IST3-6-16X9 · IST3-10-16X9 | 6 / 10 kVA with 16 internal 12 V 9 Ah batteries |
| IST3-6-L · IST3-10-L | Long backup 6 / 10 kVA, external batteries only |
| IST3-[kVA]-[n]X9 | UPS with battery cabinet BB1, BB2 or BB3, n × 12 V 9 Ah in total |
| DRYCNT-IST3/9 · SNMP | Dry-contact relay board · internal SNMP board |
| MBYP-3K · MBYP-6K | External manual maintenance bypass, rack, max. 3 kVA · max. 10 kVA |
Questions
Questions about the IST3-10
Why is the IST3-10's internal battery so short at full load?
Its internal battery is the same 16 × 12 V 9 Ah as the IST3-6, now carrying 10 kW: 2 minutes at full load and 5 at half load in AEC's data (the catalogue prints 1 and 15). For more backup, the catalogue offers BB3 (up to 32 × 9 Ah, several per UPS) and BB5 (100 × 9 Ah for the IST3 10 kVA).
Single-phase 10 kVA: IST3-10 or IST7-10 in 1/1?
Both work single-phase in and out. The IST3-10 is 10 kW (PF 1), 56.2 kg, in a 553 mm high tower; the IST7-10 is 10 kW (PF 1) in a 880 mm cabinet, takes up to 40 internal batteries and can later be rewired 3/3 if the site gets a three-phase supply.
How long does a 10 kVA UPS like the IST3-10 run?
2 to 41 minutes at full load (10 kW), and 5 to 101 minutes at half load, with the AEC battery options in the table: the battery chosen sets the figure. With 16 × 12 V 9 Ah (IST3-10-16X9): 2 minutes at 100% and 5 at 50%. For other loads and batteries use the backup-time tool.
How big is the AEC IST3-10 and how much does it weigh?
The AEC IST3-10 measures 230 × 524 × 553 mm; weight: 56.2 / 12.5 kg (size from AEC's CAD drawing, weight from the EMEA 2026 catalogue).
What is the ordering code of the AEC IST3-10?
In the EMEA 2026 catalogue the AEC IST3-10 is listed as IST3-10-16X9, IST3-10-L; AEC gives the full code, batteries included, from the load and the backup time.
Talk to an AEC engineer
Tell us the load, the supply and the backup time you need for the AEC IST3-10: we answer with the model and the batteries that fit. AEC International sells through distributors in about 80 countries and an agency in every Italian region: ask AEC which one serves your area.