IST3 · Single-phase UPS

IST3-10 Single-phase online UPS 10 kVA, tower, 230 V

VRLA10 kVAonline tower UPS, 230 V

The IST3-10 is a 10 kVA / 10 kW single-phase online double-conversion tower UPS, the largest IST3, with 16 internal 12 V 9 Ah batteries. For buildings and plants with only a single-phase supply and loads up to about 10 kW: IT rooms, shops, surgeries, control rooms.

10 kVA / 10 kWRating
230 × 524 × 553 mmW × D × H
56.2 / 12.5 kgWeight
192 V (16–20 × 12 V settable)Battery

Quick answers

IST3-10: quick answers

What it is
The IST3-10 is a 10 kVA / 10 kW single-phase online double-conversion tower UPS, the largest IST3, with 16 internal 12 V 9 Ah batteries.
Who it is for
For buildings and plants with only a single-phase supply and loads up to about 10 kW: IT rooms, shops, surgeries, control rooms.
Supply and configuration
208 / 220 / 230 / 240 V
Battery and backup
192 V (16–20 × 12 V settable) · 1–15 min full / half load
Size and weight
230 × 524 × 553 mm · 56.2 / 12.5 kg
Ordering code
IST3-10-16X9 · IST3-10-L

IST3

What sets apart the IST3-10

The IST3-10 has the same 230 × 524 × 553 mm cabinet as the IST3-6 and weighs only 1.7 kg more (56.2 kg). With the same 16 × 9 Ah battery it gives 2 minutes at full load and 5 at half load in AEC's data (the catalogue prints 1 and 15), so at 10 kVA most projects add batteries: a BB3 with up to 32 blocks, or a BB5 with 100 × 9 Ah.

It draws up to 60 A from the mains, so it takes a 100 A breaker and a 10 mm² cable; the long backup model draws up to 65 A from the battery. For service without stopping the load there is the internal maintenance bypass switch, or the external rack MBYP-6K for UPS up to 10 kVA.

  • Against the IST3-6 (one size down): Power 10000 VA / 10000 W against 6000 VA / 6000 W; Backup time, standard model 1–15 min full / half load against 5–20 min full / half load; Weight standard / long backup 56.2 / 12.5 kg against 54.5 / 11.0 kg.

Planning data

IST3-10: currents, breakers, cables, batteries

The rows and columns of the EMEA 2026 catalogue's and AEC manuals' tables that concern the IST3-10.

Wall socket or terminal bar

IST3-10 · Wall socket or terminal bar
Model10 kVA
AC input max. (A)60
AC breaker (A)100
DC input max. (A, long backup)65
DC breaker (A)100
AC cable (mm²)10
Battery cable (mm²)10

Installation

Installing the IST3-10: space, cables

Each figure with its source.

IST3-10 · installation
ItemFigureSource
Clearancesrear 300 mm (recommended 500), left 300 mm (recommended 500), right 300 mm (recommended 500); front and top: not givenAEC IST3 user manual p.6 §1.2
Cable entryRear terminal blockAEC IST3 user manual
Operating temperature−5 to 40 °C, best 20–25 °CAEC IST3 user manual p.6 §1.2
Switches and terminalsTerminal block (input, output, battery) under a cover at the rear; mains, bypass and battery breakers and the maintenance bypass switch on the rear panel (standard model).AEC IST3 user manual p.6 §1.2

Size and floor

How big it is

230 × 524 × 553 mm · 56.2 / 12.5 kg.

0.12 m²footprint
104–466 kg/m²floor load
0.55 mheight

Floor load = weight ÷ footprint: 104 kg/m² at the lowest weight given (12.5 kg), 466 kg/m² at the highest (56.2 kg).

1.75 mFrontSide230524553

Efficiency

How efficient is the AEC IST3-10 at your load?

IST3-10, 10 kW at its rating, online, double conversion (typical curve, AEC's method). Heat to remove on this curve: 50%: 0.32 kW (η 94.05%) · 75%: 0.35 kW (η 95.5%) · 100%: 0.49 kW (η 95.3%). At 50% load, 24/7, it loses about 2,771 kWh a year.

95.5%75% · Typical curve, derived from the datasheet efficiency of 95.5% (AEC method)

How the curve is drawn and where each figure comes from: the IST3 range page. The IST3 pages of the EMEA 2026 catalogue give no efficiency figure. The 1, 2 and 3 kVA curves are the ones AEC measured on the IST3-J of the same rating (AEC technical datasheet IST3-J 1–3 kVA), which AEC states has the same electronics; the 6 and 10 kVA curve has the same shape, moved to their 95.5% figure.

Load
—
Lost as heat
—
Energy lost in a year, 24/7
—
Its cost in a year at € per kWh
—
The catalogue's examples use €0.20 per kWh.
Where each figure comes from
ModeEfficiencyKindModelsSource
Online, double conversion30%: 93.04% · 50%: 94.05% · 75%: 95.5% · 100%: 95.3%Typical curve, derived from the datasheet efficiency of 95.5% (AEC method)IST3-10 · IST3-6AEC technical datasheet IST3-J 1–3 kVA: AC/AC efficiency
ECO98.3%Datasheet figure, load not statedallAEC technical datasheet IST3-J 1–3 kVA: AC/AC efficiency
Online, double conversion30%: 86.14% · 50%: 88.7% · 75%: 90.06% · 100%: 90.83%Measured (AEC datasheet)IST3-1AEC technical datasheet IST3-J 1–3 kVA: AC/AC efficiency
Online, double conversion30%: 89.36% · 50%: 91.23% · 75%: 92.16% · 100%: 92.56%Measured (AEC datasheet)IST3-2AEC technical datasheet IST3-J 1–3 kVA: AC/AC efficiency
Online, double conversion30%: 90.84% · 50%: 91.85% · 75%: 93.3% · 100%: 93.1%Measured (AEC datasheet)IST3-3AEC technical datasheet IST3-J 1–3 kVA: AC/AC efficiency
AEC IST3-10, rendered from its 3D modelDrag to turn

In 3D

Look around the IST3-10

Technical data

Technical data IST3-10

Only this model's values, from the EMEA 2026 catalogue table.

IST3-10 · Technical data
Rating
Power (VA / W)10000 / 10000
Efficiency (AC/AC)up to 95.5% · 98.3% in ECO mode
Input
Voltage range176–275 V full load · 80–176 V linear derating
Frequency · connection50 / 60 Hz ± 10%, self-adapting · single phase, L + N + PE
Output
Voltage220 V ± 2% (default) · 208 / 220 / 230 / 240 V settable from the panel
Frequency · waveform50 / 60 Hz ± 0.2% in battery mode · sine wave
Voltage distortionTHD < 1% linear · < 4% non-linear
Power factor · transfer time1.0 (kVA = kW) · 0 ms mains to battery
Overload105–130% 10 min (1 min above 30 °C) · 130–150% 30 s · > 150% 500 ms
Battery
Voltage, standard model192 V (16–20 × 12 V settable)
Voltage, long backup model192 V
Backup time, standard model1–15 min full / half load
Charge recoverystandard model < 10 h · long backup: depends on the battery pack
General
CommunicationRS232 and USB standard · SNMP card or RS485 and dry-contact card optional · EPO
Protectionsbattery undervoltage, overload, short circuit, over-temperature, input overvoltage
Noise< 55 dB
Environment−5 … 40 °C · 0–95% RH non-condensing · ≤ 1000 m without derating
Dimensions W × D × H, standard230 × 524 × 553 mm
Dimensions W × D × H, long backup190 × 429 × 337 mm
Weight standard / long backup (kg)56.2 / 12.5
IST3-10 · Models
ItemIST3-10
VA / W10000 / 10000
Internal batteries16 × 9 Ah · 192 V
Backup, full / half load1 / 15 min
W × D × H (mm)230 × 524 × 553
kg56.2
Long backup: battery192 V
Long backup: kg12.5

Specifications are subject to change without notice.

More technical detailsordering codes

Ordering codes

Ordering codes IST3-10

Ordering codes IST3-10
CodeDescription
IST3-6-16X9 · IST3-10-16X96 / 10 kVA with 16 internal 12 V 9 Ah batteries
IST3-6-L · IST3-10-LLong backup 6 / 10 kVA, external batteries only
IST3-[kVA]-[n]X9UPS with battery cabinet BB1, BB2 or BB3, n × 12 V 9 Ah in total
DRYCNT-IST3/9 · SNMPDry-contact relay board · internal SNMP board
MBYP-3K · MBYP-6KExternal manual maintenance bypass, rack, max. 3 kVA · max. 10 kVA

Questions

Questions about the IST3-10

Why is the IST3-10's internal battery so short at full load?

Its internal battery is the same 16 × 12 V 9 Ah as the IST3-6, now carrying 10 kW: 2 minutes at full load and 5 at half load in AEC's data (the catalogue prints 1 and 15). For more backup, the catalogue offers BB3 (up to 32 × 9 Ah, several per UPS) and BB5 (100 × 9 Ah for the IST3 10 kVA).

Single-phase 10 kVA: IST3-10 or IST7-10 in 1/1?

Both work single-phase in and out. The IST3-10 is 10 kW (PF 1), 56.2 kg, in a 553 mm high tower; the IST7-10 is 10 kW (PF 1) in a 880 mm cabinet, takes up to 40 internal batteries and can later be rewired 3/3 if the site gets a three-phase supply.

How long does a 10 kVA UPS like the IST3-10 run?

2 to 41 minutes at full load (10 kW), and 5 to 101 minutes at half load, with the AEC battery options in the table: the battery chosen sets the figure. With 16 × 12 V 9 Ah (IST3-10-16X9): 2 minutes at 100% and 5 at 50%. For other loads and batteries use the backup-time tool.

How big is the AEC IST3-10 and how much does it weigh?

The AEC IST3-10 measures 230 × 524 × 553 mm; weight: 56.2 / 12.5 kg (size from AEC's CAD drawing, weight from the EMEA 2026 catalogue).

What is the ordering code of the AEC IST3-10?

In the EMEA 2026 catalogue the AEC IST3-10 is listed as IST3-10-16X9, IST3-10-L; AEC gives the full code, batteries included, from the load and the backup time.

Talk to an AEC engineer

Tell us the load, the supply and the backup time you need for the AEC IST3-10: we answer with the model and the batteries that fit. AEC International sells through distributors in about 80 countries and an agency in every Italian region: ask AEC which one serves your area.