IST6 400–1200 · Modular UPS

IST6-1000, 10 × 100 kVA Modular UPS, 400 V, for data centres

VRLA1000 kVAmodular online UPS, 100 kVA modules

The IST6-1000 is a double-column modular online UPS with ten 100 kVA modules: 1 MW in 1201 × 1000 × 2000 mm. For hyperscale and colocation halls, hospitals and process plants that need 1 MW per UPS.

1000 kVA / 1000 kWRating
1201 × 1000 × 2000 mmW × D × H
662 kg without modulesWeight

Quick answers

IST6-1000, 10 × 100 kVA: quick answers

What it is
The IST6-1000 is a double-column modular online UPS with ten 100 kVA modules: 1 MW in 1201 × 1000 × 2000 mm.
Who it is for
For hyperscale and colocation halls, hospitals and process plants that need 1 MW per UPS.
Supply and configuration
380 / 400 / 415 V
Battery and backup
480 V DC nominal (360–600 V), 30–50 × 12 V blocks, standard 40; neutral optional
Size and weight
1201 × 1000 × 2000 mm · 662 kg without modules
Ordering code
IST6-1000

IST6 400–1200

What sets apart the IST6-1000, 10 × 100 kVA

The IST6-1000 opens the double-column cabinet, 1201 mm wide and 662 kg without modules. Its optional distribution cabinet (1800 mm line-up) carries mains, bypass and output breakers, without a maintenance bypass. At full load it draws 1652 A at the mains and needs 7902 m³/h of air.

The catalogue's efficiency example is this cabinet at 80% load (800 kW): moving from General modules (97.2%) to PLUS modules (98.1%) cuts the losses from 23.0 to 15.5 kW. The 1200 kVA uses the same double-column cabinet and weight, with twelve modules.

  • Against the IST6-800, 8 × 100 kVA (one size down): Power modules (100 kVA) 10 against 8; W × D × H 1201 × 1000 × 2000 mm against 801 × 1000 × 2000 mm; With distribution cabinet 1800 mm wide against 1400 mm wide; Weight without modules 662 kg against 435 kg.
  • Against the IST6-1200, 12 × 100 kVA (one size up): Power modules (100 kVA) 10 against 12.

Installation

Installing the IST6-1000, 10 × 100 kVA: space, heat, cables

Each figure with its source. Heat is the power lost at the peak efficiency stated.

IST6-1000, 10 × 100 kVA · installation
ItemFigureSource
Clearancesrear 800 mm; front, left, right and top: not givenIST6 400–1200 user manual §3.2.3 p.45; EMEA 2026 catalogue p.165 (600 kVA: 500 mm)
Cable entryTop (standard); Bottom, with the side wiring cabinetIST6 400–1200 user manual §3.2.3 p.45; EMEA 2026 catalogue p.165 (600 kVA: 500 mm)
Heat at full load28.8 kW at 1,000 kW load, 97.2 % efficiencyIST6 400–1200 AEC data; output PF 1 (EMEA 2026 catalogue)
Operating temperature0 to 40 °CIST6 400–1200 AEC user manual
Switches and terminals600 kVA: switches inside the UPS cabinet. 800–1200 kVA: in the 599 mm distribution cabinet on the left.IST6 400–1200 user manual §3.2.3 p.45; EMEA 2026 catalogue p.165 (600 kVA: 500 mm)
Module withdrawal760 mm in front of the cabinet to withdraw a moduleEMEA 2026 catalogue p.163, 180
Units in parallelUp to 8 unitsAEC IST6 400–1200 user manual; EMEA 2026 catalogue p.160–178

Size and floor

How big it is

1201 × 1000 × 2000 mm · 662 kg without modules.

1.2 m²footprint
2 mheight

1.75 mFrontSide120110002000

Efficiency

How efficient is the AEC IST6-1000, 10 × 100 kVA at your load?

IST6-1000, 10 × 100 kVA, 1,000 kW at its rating, online, double conversion (typical curve, AEC's method). Heat to remove on this curve: 25%: 6.41 kW (η 97.5%) · 50%: 9.68 kW (η 98.1%) · 75%: 16.9 kW (η 97.8%) · 100%: 25.6 kW (η 97.5%). At 50% load, 24/7, it loses about 84,832 kWh a year.

98.1%50% · Typical curve, derived from the datasheet efficiency of 98.1% (AEC method)

How the curve is drawn and where each figure comes from: the IST6 400–1200 range page.

Load
—
Lost as heat
—
Energy lost in a year, 24/7
—
Its cost in a year at € per kWh
—
The catalogue's examples use €0.20 per kWh.
Where each figure comes from
ModeEfficiencyKindModelsSource
Online, double conversion25%: 97.5% · 50%: 98.1% · 75%: 97.8% · 100%: 97.5%Typical curve, derived from the datasheet efficiency of 98.1% (AEC method)allAEC datasheet: AC/AC efficiency of the IST6-PM100 100 kW power module (the curve's shape)
ECO99.2%Datasheet figure, load not statedall
W-ECO99%Datasheet figure, load not statedall

EMEA 2026 catalogue figures: Double conversion, General modules up to 97.2% · Double conversion, PLUS modules up to 98.1% · ECO up to 99.2% · W-ECO up to 99%.

AEC IST6 1200 kVA, rendered from its 3D modelDrag to turn

In 3D

Look around the IST6-1000, 10 × 100 kVA

The turntable shows the IST6 1200 kVA; the full 3D view opens on the IST6 1000 kVA.

Technical data

Technical data IST6-1000, 10 × 100 kVA

Only this model's values, from the EMEA 2026 catalogue table.

IST6-1000, 10 × 100 kVA · Technical data
Cabinet
Power modules (100 kVA)10
Bypass module4.5U
Input
System · voltage3Ph+N+PE · 380 / 400 / 415 V; 138–485 V (full power 324–485 V, linear derating below)
Frequency · PF · THDi40–70 Hz · ≥ 0.99 · ≤ 3% at full load
Bypass304–438 V; synchronisation 50 / 60 ± 6 Hz; settable window
Battery
Lead-acid480 V DC nominal (360–600 V), 30–50 × 12 V blocks, standard 40; neutral optional
Lithium (with BMS card)512 V DC nominal (384–640 V), 120–200 cells, standard 160
Charging current20 A × number of modules · cold start · shared battery
Output
System · voltage3Ph+N+PE · 380 / 400 / 415 V ± 1%
Power factor · THDvsettable 0.8–1.0 (default 1.0) · ≤ 1% linear, ≤ 3% non-linear
Frequency · phase errortracks the bypass; 50 / 60 ± 0.1 Hz with mains abnormal · ≤ 1° balanced, ≤ 2° unbalanced
Transfermains ↔ battery 0 ms · bypass ↔ inverter < 1 ms synchronised, < 15 ms
Inverter overload (PF ≥ 0.95)≤ 105% continuous · 105–110% 60 min · 110–125% 10 min · 125–150% 1 min · > 150% to bypass
Bypass overload≤ 135% continuous · 135–150% 5 min · 150–200% 1 s · 200–300% 100 ms
System
Efficiency · modes97.2% (General) / 98.1% (PLUS) · ECO 99.2% · W-ECO 99% · energy storage, sleep, generator
Parallelup to 8 UPS, current imbalance ≤ 5% · BSC dual bus and multi-bus (3 buses)
CommunicationModbus · RS232 · RS485 · 4 inputs / 3 outputs dry contact · options: SNMP, expansion, BMS
Environment0 … 40 °C · 0–95% RH · ≤ 2000 m · IP20 · < 80 dB · EMC category C3
W × D × H (mm)1201 × 1000 × 2000
With distribution cabinet1800 mm wide
Weight without modules662 kg
IST6-1000, 10 × 100 kVA · Models
ItemIST6-1000, 10 × 100 kVA
Power modules (100 kVA)10
Columns · doors2 · 2
Internal power switchesoption¹
W × D (mm) · H 20001201 × 1000
Weight without modules662 kg
Mains input current1652 A
Cooling air flow (min.)7902 m³/h

Power module 440 × 760 × 130 mm (without ears and handles), 54 kg. Data from the IST6 400–1200 kVA user manual. Specifications are subject to change without notice.

More technical detailshow it works, ordering codes

Diagrams

How the power flows: AEC IST6-1000, 10 × 100 kVA

Pick an operating mode: the path the power takes to the load lights up.

Power module × NMaintenance bypassMainsRectifierDC busBatteryInverterStatic switchLoadStatic bypassPower module × NMaintenance bypassMainsRectifierDC busBatteryInverterStatic switchLoadStatic bypass

Normal. Double conversion: the rectifier feeds the DC bus, the inverter rebuilds a clean voltage and the load always runs on the inverter. The battery stays on charge. Efficiency up to 98.1% (PLUS modules; 97.2% with General modules).

Modules and redundancy

Move the slider: the modules the load needs light up, and the spare slot holds the N+1 redundancy. Each slot takes one 100 kVA module.

modules working · redundant · free slot

Ordering codes

Ordering codes IST6-1000, 10 × 100 kVA

Ordering codes IST6-1000, 10 × 100 kVA
CodeDescription
IST6-1000Modular cabinet, max. 10 × 100 kVA power modules, without modules
IST6-100-J100 kVA / 100 kW power module
PAR - IST6Parallel kit

Questions

Questions about the IST6-1000, 10 × 100 kVA

Is the maintenance bypass included on the IST6-1000?

Not in the distribution cabinet: for 1000 and 1200 kVA it holds mains, bypass and output breakers only. Plan the maintenance bypass in the site switchboard; AEC engineers size the whole system.

How much do PLUS modules save on an IST6-1000?

At 800 kW, 8,760 hours a year, losses fall from 23.0 kW (General, 97.2%) to 15.5 kW (PLUS, 98.1%), cooling excluded. The catalogue gives this as an indicative example.

How long does a 1000 kVA UPS like the IST6-1000, 10 × 100 kVA run?

3 to 31 minutes at full load (1,000 kW), and 7 to 62 minutes at half load, with the AEC battery options in the table: the battery chosen sets the figure. With 180 × 12 V 100 Ah · 6 × 30 (IST6-1000-180X100): 3 minutes at 100% and 7 at 50%. For other loads and batteries use the backup-time tool.

How big is the AEC IST6-1000, 10 × 100 kVA and how much does it weigh?

The AEC IST6-1000, 10 × 100 kVA measures 1201 × 1000 × 2000 mm; weight: 662 kg without modules (EMEA 2026 catalogue).

What is the ordering code of the AEC IST6-1000, 10 × 100 kVA?

In the EMEA 2026 catalogue the AEC IST6-1000, 10 × 100 kVA is listed as IST6-1000; AEC gives the full code, batteries included, from the load and the backup time.