IST6 400–1200 · Modular UPS
IST6-600H, 6 × 100 kVA Modular UPS, 400 V, for data centres
The IST6 600 kVA is a single-column modular online UPS with six 100 kVA modules, 801 × 1000 × 2000 mm, the most power in a cabinet with switches built in. For data centres and industrial sites of 500 to 600 kW per UPS, alone or in parallel systems up to 4.8 MW.
Quick answers
IST6-600H, 6 × 100 kVA: quick answers
- What it is
- The IST6 600 kVA is a single-column modular online UPS with six 100 kVA modules, 801 × 1000 × 2000 mm, the most power in a cabinet with switches built in.
- Who it is for
- For data centres and industrial sites of 500 to 600 kW per UPS, alone or in parallel systems up to 4.8 MW.
- Supply and configuration
- 380 / 400 / 415 V
- Battery and backup
- 480 V DC nominal (360–600 V), 30–50 × 12 V blocks, standard 40; neutral optional
- Size and weight
- 801 × 1000 × 2000 mm · 434 kg without modules
- Ordering code
- IST6-600H
IST6 400–1200
What sets apart the IST6-600H, 6 × 100 kVA
The 600 kVA fills all six slots of the 434 kg cabinet it shares with the 500 kVA. It is the largest model with mains, output, maintenance bypass and bypass switches inside; from 800 kVA they move to an external distribution cabinet. At full load it draws 991 A at the mains and needs 6246 m³/h of air.
Redundancy at 600 kVA comes from parallel UPS (eight 600 kVA units make 4.8 MW); at 500 kVA the sixth module is the N+1. The battery runs at 480 V DC nominal with 40 blocks, charged at 20 A per module, up to 120 A here.
- Against the IST6-500H, 5 × 100 kVA (one size down): Power modules (100 kVA) 6 against 5.
- Against the IST6-800, 8 × 100 kVA (one size up): Power modules (100 kVA) 6 against 8; Weight without modules 434 kg against 435 kg.
Installation
Installing the IST6-600H, 6 × 100 kVA: space, heat, cables
Each figure with its source. Heat is the power lost at the peak efficiency stated.
| Item | Figure | Source |
|---|---|---|
| Clearances | rear 800 mm; front, left, right and top: not given | IST6 400–1200 user manual §3.2.3 p.45; EMEA 2026 catalogue p.165 (600 kVA: 500 mm) |
| Cable entry | Top (standard); Bottom, with the side wiring cabinet | IST6 400–1200 user manual §3.2.3 p.45; EMEA 2026 catalogue p.165 (600 kVA: 500 mm) |
| Cooling air | 6,246 m³/h | IST6 400–1200 AEC data |
| Heat at full load | 17.3 kW at 600 kW load, 97.2 % efficiency | IST6 400–1200 AEC data; output PF 1 (EMEA 2026 catalogue) |
| Operating temperature | 0 to 40 °C | IST6 400–1200 AEC user manual |
| Switches and terminals | 600 kVA: switches inside the UPS cabinet. 800–1200 kVA: in the 599 mm distribution cabinet on the left. | IST6 400–1200 user manual §3.2.3 p.45; EMEA 2026 catalogue p.165 (600 kVA: 500 mm) |
| Module withdrawal | 760 mm in front of the cabinet to withdraw a module | EMEA 2026 catalogue p.163, 180 |
| Units in parallel | Up to 8 units | AEC IST6 400–1200 user manual; EMEA 2026 catalogue p.160–178 |
Size and floor
How big it is
801 × 1000 × 2000 mm · 434 kg without modules.
Efficiency
How efficient is the AEC IST6-600H, 6 × 100 kVA at your load?
IST6-600H, 6 × 100 kVA, 600 kW at its rating, online, double conversion (typical curve, AEC's method). Heat to remove on this curve: 25%: 3.85 kW (η 97.5%) · 50%: 5.81 kW (η 98.1%) · 75%: 10.1 kW (η 97.8%) · 100%: 15.4 kW (η 97.5%). At 50% load, 24/7, it loses about 50,899 kWh a year.
How the curve is drawn and where each figure comes from: the IST6 400–1200 range page.
- Load
- —
- Lost as heat
- —
- Energy lost in a year, 24/7
- —
- Its cost in a year at € per kWh
- —
- The catalogue's examples use €0.20 per kWh.
Where each figure comes from
| Mode | Efficiency | Kind | Models | Source |
|---|---|---|---|---|
| Online, double conversion | 25%: 97.5% · 50%: 98.1% · 75%: 97.8% · 100%: 97.5% | Typical curve, derived from the datasheet efficiency of 98.1% (AEC method) | all | AEC datasheet: AC/AC efficiency of the IST6-PM100 100 kW power module (the curve's shape) |
| ECO | 99.2% | Datasheet figure, load not stated | all | |
| W-ECO | 99% | Datasheet figure, load not stated | all |
EMEA 2026 catalogue figures: Double conversion, General modules up to 97.2% · Double conversion, PLUS modules up to 98.1% · ECO up to 99.2% · W-ECO up to 99%.
Drag to turnTechnical data
Technical data IST6-600H, 6 × 100 kVA
Only this model's values, from the EMEA 2026 catalogue table.
| Cabinet | |
|---|---|
| Power modules (100 kVA) | 6 |
| Bypass module | 4.5U |
| Input | |
| System · voltage | 3Ph+N+PE · 380 / 400 / 415 V; 138–485 V (full power 324–485 V, linear derating below) |
| Frequency · PF · THDi | 40–70 Hz · ≥ 0.99 · ≤ 3% at full load |
| Bypass | 304–438 V; synchronisation 50 / 60 ± 6 Hz; settable window |
| Battery | |
| Lead-acid | 480 V DC nominal (360–600 V), 30–50 × 12 V blocks, standard 40; neutral optional |
| Lithium (with BMS card) | 512 V DC nominal (384–640 V), 120–200 cells, standard 160 |
| Charging current | 20 A × number of modules · cold start · shared battery |
| Output | |
| System · voltage | 3Ph+N+PE · 380 / 400 / 415 V ± 1% |
| Power factor · THDv | settable 0.8–1.0 (default 1.0) · ≤ 1% linear, ≤ 3% non-linear |
| Frequency · phase error | tracks the bypass; 50 / 60 ± 0.1 Hz with mains abnormal · ≤ 1° balanced, ≤ 2° unbalanced |
| Transfer | mains ↔ battery 0 ms · bypass ↔ inverter < 1 ms synchronised, < 15 ms |
| Inverter overload (PF ≥ 0.95) | ≤ 105% continuous · 105–110% 60 min · 110–125% 10 min · 125–150% 1 min · > 150% to bypass |
| Bypass overload | ≤ 135% continuous · 135–150% 5 min · 150–200% 1 s · 200–300% 100 ms |
| System | |
| Efficiency · modes | 97.2% (General) / 98.1% (PLUS) · ECO 99.2% · W-ECO 99% · energy storage, sleep, generator |
| Parallel | up to 8 UPS, current imbalance ≤ 5% · BSC dual bus and multi-bus (3 buses) |
| Communication | Modbus · RS232 · RS485 · 4 inputs / 3 outputs dry contact · options: SNMP, expansion, BMS |
| Environment | 0 … 40 °C · 0–95% RH · ≤ 2000 m · IP20 · < 80 dB · EMC category C3 |
| W × D × H (mm) | 801 × 1000 × 2000 |
| Weight without modules | 434 kg |
| Item | IST6-600H, 6 × 100 kVA |
|---|---|
| Power modules (100 kVA) | 6 |
| Columns · doors | 1 · 1 |
| Internal power switches | yes* |
| W × D (mm) · H 2000 | 801 × 1000 |
| Weight without modules | 434 kg |
| Mains input current | 991 A |
| Cooling air flow (min.) | 6246 m³/h |
Power module 440 × 760 × 130 mm (without ears and handles), 54 kg. Data from the IST6 400–1200 kVA user manual. Specifications are subject to change without notice.
More technical detailshow it works, ordering codes
Diagrams
How the power flows: AEC IST6-600H, 6 × 100 kVA
Pick an operating mode: the path the power takes to the load lights up.
Normal. Double conversion: the rectifier feeds the DC bus, the inverter rebuilds a clean voltage and the load always runs on the inverter. The battery stays on charge. Efficiency up to 98.1% (PLUS modules; 97.2% with General modules).
Battery. The mains fails: the battery feeds the DC bus and the inverter carries on without a break. The load does not notice. Transfer: mains ↔ battery 0 ms.
Bypass. Overload or internal fault: the static switch moves the load to the bypass line, fed by the mains.
ECO. The load runs on the bypass and the inverter stands ready: if the mains leaves the set window, the load goes back to the inverter. Higher efficiency, less protection. Efficiency up to 99.2%.
Maintenance. The maintenance bypass feeds the load straight from the mains, so the UPS can be isolated for service without switching the load off. maintenance bypass switch inside on 400–600 kVA; in the optional distribution cabinet on 800 kVA; none on 1000 / 1200 kVA.
Frequency converter. Output at 50 or 60 Hz whatever the input: the load always runs on the inverter and the bypass is not used.
Modules and redundancy
Move the slider: the modules the load needs light up, and the spare slot holds the N+1 redundancy. Each slot takes one 100 kVA module.
modules working · redundant · free slot
Ordering codes
Ordering codes IST6-600H, 6 × 100 kVA
| Code | Description |
|---|---|
| IST6-600H | Modular cabinet, max. 6 × 100 kVA power modules, without modules |
| IST6-100-J | 100 kVA / 100 kW power module |
| PAR - IST6 | Parallel kit |
Questions
Questions about the IST6-600H, 6 × 100 kVA
What charging current does the IST6 600 kVA give?
20 A per power module, so up to 120 A with six modules, in three stages. The charge limit for lead-acid is 0.05–0.5 C, set on the screen with the battery parameters.
Where do the cables enter the IST6 600 kVA?
From the top as standard; bottom entry needs the side wiring cabinet (trench 750 × 300 × 120 mm). The cabinet is fixed with M12 expansion bolts to the floor or a C-steel base.
How long does a 600 kVA UPS like the IST6-600H, 6 × 100 kVA run?
3 to 52 minutes at full load (600 kW), and 8 to 104 minutes at half load, with the AEC battery options in the table: the battery chosen sets the figure. With 120 × 12 V 100 Ah · 4 × 30 (IST6-600-120X100): 3 minutes at 100% and 8 at 50%. For other loads and batteries use the backup-time tool.
How big is the AEC IST6-600H, 6 × 100 kVA and how much does it weigh?
The AEC IST6-600H, 6 × 100 kVA measures 801 × 1000 × 2000 mm; weight: 434 kg without modules (EMEA 2026 catalogue).