IST9 · Three-phase UPS

IST9 10 kVA Three-phase rack UPS 10 kVA, 3U, 400 V

VRLA10 kVAonline rack UPS, 3U, 3/3 · 3/1 · 1/1

The IST9 10 kVA is a 10 kVA / 10 kW online double-conversion UPS in a 19-inch, 3U chassis, 535 mm deep, that works 3/3, 3/1 or 1/1. For racks and small rooms that need three-phase-grade protection in three rack units, on a three-phase or a single-phase supply.

10 kVA / 10 kWRating
438 × 535 × 130 mm (3U)W × D × H
18.4 kgWeight

Quick answers

IST9 10 kVA: quick answers

What it is
The IST9 10 kVA is a 10 kVA / 10 kW online double-conversion UPS in a 19-inch, 3U chassis, 535 mm deep, that works 3/3, 3/1 or 1/1.
Who it is for
For racks and small rooms that need three-phase-grade protection in three rack units, on a three-phase or a single-phase supply.
Supply and configuration
3W + N + PE (settable 1W + N + PE) · 220 / 230 / 240 V L-N · 380 / 400 / 415 V L-L
Size and weight
438 × 535 × 130 mm (3U) · 18.4 kg
Ordering code
IST9-10-[n]X9 · IST9-10

IST9

What sets apart the IST9 10 kVA

The IST9 10 kVA weighs 18.4 kg, the same chassis as the 20 kVA. It is the IST9 with the lowest currents: 19 A per phase in 3/3 on 32 A 3P breakers, 57 A in 1/1 on an 80 A 1P breaker, and 56 A from the battery on a 100 A 3P DC breaker. In low-voltage mode (110 / 115 / 120 V phase) it keeps its full 10 kVA, where the 20 and 40 kVA are halved.

The battery string is set on site, ±48 to ±120 cells of 2 V (±96 to ±240 V DC), with a charger of 1–10 A (default 4 A). The touch screen turns with the unit, landscape in a rack and portrait as a tower, in seven languages including Italian. The catalogue lists its ordering code as on request.

  • Against the IST9 15 kVA (one size up): Rated power 10 kVA / 10 kW against 15 kVA / 15 kW; Rated power 10 kVA / 10 kW against not published.

Planning data

IST9 10 kVA: currents, breakers, cables, batteries

The rows and columns of the EMEA 2026 catalogue's and AEC manuals' tables that concern the IST9 10 kVA.

Connected, and ready for redundancy

IST9 10 kVA · Connected, and ready for redundancy
ModelModeAC input (A)Bypass input (A)DC input (A)AC output (A)
10 kVA3/332 × 3P32 × 3P100 × 3P32 × 3P
10 kVA3/132 × 3P63 × 1P100 × 3P63 × 1P
10 kVA1/180 × 1P63 × 1P100 × 3P63 × 1P

Currents, codes and options

IST9 10 kVA · Currents, codes and options
ModelModeAC input (A)Bypass input (A)DC input (A)AC output (A)
10 kVA3/319155615
10 kVA3/119465646
10 kVA1/157465646

Installation

Installing the IST9 10 kVA: space, heat, cables

Each figure with its source. Heat is the power lost at the peak efficiency stated.

IST9 10 kVA · installation
ItemFigureSource
Cable entryAt the rearEMEA 2026 catalogue p.64
Heat at full load0.42 kW at 10 kW load, 96 % efficiencyEMEA 2026 catalogue p.64; output PF 1 (EMEA 2026 catalogue)
Operating temperature−5 to 40 °CEMEA 2026 catalogue p.64

Size and floor

How big it is

438 × 535 × 130 mm · 18.4 kg.

0.23 m²footprint
79 kg/m²floor load
0.13 mheight

Floor load = weight ÷ footprint (18.4 kg).

1.75 mFrontSide438535130

Efficiency

How efficient is the AEC IST9 10 kVA at your load?

IST9 10 kVA, 10 kW at its rating, double conversion, high-voltage mode (typical curve, AEC's method). Heat to remove on this curve: 25%: 0.12 kW (η 95.4%) · 50%: 0.21 kW (η 96%) · 75%: 0.34 kW (η 95.7%) · 100%: 0.48 kW (η 95.4%). At 50% load, 24/7, it loses about 1,825 kWh a year.

96%50% · Typical curve, derived from the datasheet efficiency of 96% (AEC method)

How the curve is drawn and where each figure comes from: the IST9 range page.

Load
—
Lost as heat
—
Energy lost in a year, 24/7
—
Its cost in a year at € per kWh
—
The catalogue's examples use €0.20 per kWh.
Where each figure comes from
ModeEfficiencyKindModelsSource
Double conversion, high-voltage mode25%: 95.4% · 50%: 96% · 75%: 95.7% · 100%: 95.4%Typical curve, derived from the datasheet efficiency of 96% (AEC method)allAEC datasheet: AC/AC efficiency of the IST6-PM100 100 kW power module (the curve's shape)
Double conversion, low-voltage mode25%: 93.4% · 50%: 94% · 75%: 93.7% · 100%: 93.4%Typical curve, derived from the datasheet efficiency of 94% (AEC method)IST9 10 kVA · IST9 20 kVA · IST9 40 kVAAEC datasheet: AC/AC efficiency of the IST6-PM100 100 kW power module (the curve's shape)
ECO99%Datasheet figure, load not statedall

EMEA 2026 catalogue figures: Double conversion, high-voltage mode up to 96% · Double conversion, low-voltage mode up to 94% · ECO up to 99%.

AEC IST9 20 kVA, rendered from its 3D modelDrag to turn

In 3D

Look around the IST9 10 kVA

The turntable shows the IST9 20 kVA; the full 3D view opens on the IST9 10 kVA.

Technical data

Technical data IST9 10 kVA

Only this model's values, from the EMEA 2026 catalogue table.

IST9 10 kVA · Technical data
General
Rated power (kVA / kW, high-voltage mode)10 / 10
Rated power (kVA / kW, low-voltage mode)10 / 10
Configuration3/3 · 3/1 · 1/1
Input
Connection3W + N + PE (settable 1W + N + PE)
Voltage range (phase)high-voltage mode 176–280 V full load, 80–176 V linear derating · low-voltage mode 90–155 V full load, 70–90 V derating
Frequency · power factor · THDi40–70 Hz · ≥ 0.99 · ≤ 3% resistive, ≤ 5% non-linear full load
Bypass50 / 60 Hz ± 10% · voltage ± 20%
Battery
Voltagehigh-voltage mode ± 96 … ± 240 V DC (± 48 … ± 120 cells of 2 V, default ± 96) · low-voltage mode ± 96 … ± 120 V (± 48 … ± 60 cells, default ± 60)
Charging current1–10 A (default 4 A)
Output
Voltage220 / 230 / 240 V L-N, 380 / 400 / 415 V L-L (low-voltage mode 110 / 115 / 120 V); 3W + N + PE, settable 1W + N + PE
Frequencytracks the bypass; 50 ± 0.1 or 60 ± 0.1 Hz in battery mode
Waveform · distortion · power factorsine wave · ≤ 2% resistive full load · 1.0
Transfer inverter ↔ bypass< 1 ms synchronised · < 10 ms not synchronised
Inverter overload≤ 105% continuous · 105–110% 60 min · 110–130% 10 min · 130–155% 1 min · > 155% 200 ms · > 200% immediate
Bypass overload< 130% continuous · 130–155% 1 min · > 155% 200 ms
System
Efficiencyup to 96% (high-voltage mode) · 94% (low-voltage mode) · 99% ECO
Display · cold starttouch screen · battery cold start fitted
CommunicationRS232 · options: SNMP, RS485 + dry contact, protocol card for the approved lithium system, parallel card
Noise (20–25 °C)≤ 50 dB half load · ≤ 55 dB 75% and full load
Environment−5 … 40 °C · 0–95% RH non-condensing · ≤ 2000 m
Dimensions (W × D × H)438 × 535 × 130 mm (3U)
Weight18.4 kg
IST9 10 kVA · Models
ItemIST9 10 kVA
kVA / kW (high-voltage mode)10 / 10
kVA / kW (low-voltage mode)10 / 10
Configuration3/3 · 3/1 · 1/1
W × D × H (mm)438 × 535 × 130
Weight18.4 kg

— not stated in the user manual. Specifications are subject to change without notice.

More technical detailsordering codes

Ordering codes

Ordering codes IST9 10 kVA

Ordering codes IST9 10 kVA
CodeDescription
IST9-10-[n]X9 · IST9-15-[n]X9IST9 10 or 15 kVA in the same way: power distribution box, maintenance breaker and 2, 4, 6, 8 or 10 BBJ2 rack battery cabinets (AEC EMEA product data)
IST9-10 · IST9-30 · IST9-40Code on request
PAR-IST9Parallel board
DRYCNT-IST3/9 · SNMPDry-contact relay board · internal SNMP board
BBJ2Rack battery cabinet, max. 16 × 12 V 9 Ah, 3U

Questions

Questions about the IST9 10 kVA

Can the IST9 10 kVA run on a 120 V system?

Yes. In low-voltage mode (110 / 115 / 120 V phase, 190 / 200 / 208 V line) the 10 kVA keeps 10 kVA / 10 kW, at 94% efficiency. Full load holds from 90 to 155 V phase voltage.

Which breakers does the IST9 10 kVA need?

In 3/3: 32 A 3P on AC input, bypass and output, 100 A 3P on the battery. In 3/1: 63 A 1P on bypass and output. In 1/1: 80 A 1P on the input. Breakers 1.5–2 times the maximum input current, without leakage protection.

How long does a 10 kVA UPS like the IST9 10 kVA run?

5 to 56 minutes at full load (10 kW), and 17 to 146 minutes at half load, with the AEC battery options in the table: the battery chosen sets the figure. With 32 × 12 V 9 Ah · 2 × 16 (IST9-10-32X9): 5 minutes at 100% and 17 at 50%. For other loads and batteries use the backup-time tool.

How big is the AEC IST9 10 kVA and how much does it weigh?

The AEC IST9 10 kVA measures 438 × 535 × 130 mm (3U); weight: 18.4 kg (EMEA 2026 catalogue).

Talk to an AEC engineer

Tell us the load, the supply and the backup time you need for the AEC IST9 10 kVA: we answer with the model and the batteries that fit. AEC International sells through distributors in about 80 countries and an agency in every Italian region: ask AEC which one serves your area.