IST9 · Three-phase UPS

IST9 15 kVA Three-phase rack UPS 15 kVA, 3U, 400 V

VRLA15 kVAonline rack UPS, 3U, 3/3 · 3/1 · 1/1

The IST9 15 kVA is a 15 kVA / 15 kW online double-conversion UPS in the 3U chassis of the 10 and 20 kVA, 18.4 kg, for 3/3, 3/1 or 1/1. For loads of 10 to 15 kW in a 19-inch rack: the step between the 10 and the 20 kVA, with more headroom than the first and a lighter battery than the second.

15 kVA / 15 kWRating
438 × 535 × 130 mm (3U)W × D × H
18.4 kgWeight

Quick answers

IST9 15 kVA: quick answers

What it is
The IST9 15 kVA is a 15 kVA / 15 kW online double-conversion UPS in the 3U chassis of the 10 and 20 kVA, 18.4 kg, for 3/3, 3/1 or 1/1.
Who it is for
For loads of 10 to 15 kW in a 19-inch rack: the step between the 10 and the 20 kVA, with more headroom than the first and a lighter battery than the second.
Supply and configuration
3W + N + PE (settable 1W + N + PE) · 220 / 230 / 240 V L-N · 380 / 400 / 415 V L-L
Size and weight
438 × 535 × 130 mm (3U) · 18.4 kg
Ordering code
IST9-15-[n]X9

IST9

What sets apart the IST9 15 kVA

Same body, same electronics family as the 10 and 20 kVA: the touch screen that turns with the unit, the connector jumpers for 3/3, 3/1 or 1/1, the 1–10 A charger and the ±96 to ±240 V DC battery string. AEC orders it as IST9-15 with the power distribution box and maintenance breaker, or IST9-15-[n]X9 with 2, 4, 6, 8 or 10 BBJ2 rack battery cabinets (32 to 160 × 12 V 9 Ah).

Backup at full load in AEC's product data: 3 minutes with 32 batteries, 9 with 64, 17 with 96, 26 with 128 and 34 with 160 (12 V 9 Ah, new batteries, 25 °C); at half load 9, 26, 45, 58 and 86 minutes.

  • Against the IST9 10 kVA (one size down): Rated power 15 kVA / 15 kW against 10 kVA / 10 kW; Rated power (kVA / kW, low-voltage mode) not published against 10 kVA / 10 kW.
  • Against the IST9 20 kVA (one size up): Rated power 15 kVA / 15 kW against 20 kVA / 20 kW; Rated power (kVA / kW, low-voltage mode) not published against 10 kVA / 10 kW.

Installation

Installing the IST9 15 kVA: space, heat, cables

Each figure with its source. Heat is the power lost at the peak efficiency stated.

IST9 15 kVA · installation
ItemFigureSource
Cable entryAt the rearEMEA 2026 catalogue p.64
Heat at full load0.63 kW at 15 kW load, 96 % efficiencyEMEA 2026 catalogue p.64; output PF 1 (EMEA 2026 catalogue)
Operating temperature−5 to 40 °CEMEA 2026 catalogue p.64

Size and floor

How big it is

438 × 535 × 130 mm · 18.4 kg.

0.23 m²footprint
79 kg/m²floor load
0.13 mheight

Floor load = weight ÷ footprint (18.4 kg).

1.75 mFrontSide438535130
AEC IST9 20 kVA, rendered from its 3D modelDrag to turn

In 3D

Look around the IST9 15 kVA

The turntable shows the IST9 20 kVA; the full 3D view opens on the IST9 15 kVA.

Technical data

Technical data IST9 15 kVA

Only this model's values, from the EMEA 2026 catalogue table.

IST9 15 kVA · Technical data
General
Rated power (kVA / kW, high-voltage mode)15 / 15
Rated power (kVA / kW, low-voltage mode)not published
Configuration3/3 · 3/1 · 1/1
Input
Connection3W + N + PE (settable 1W + N + PE)
Voltage range (phase)high-voltage mode 176–280 V full load, 80–176 V linear derating · low-voltage mode 90–155 V full load, 70–90 V derating
Frequency · power factor · THDi40–70 Hz · ≥ 0.99 · ≤ 3% resistive, ≤ 5% non-linear full load
Bypass50 / 60 Hz ± 10% · voltage ± 20%
Battery
Voltagehigh-voltage mode ± 96 … ± 240 V DC (± 48 … ± 120 cells of 2 V, default ± 96) · low-voltage mode ± 96 … ± 120 V (± 48 … ± 60 cells, default ± 60)
Charging current1–10 A (default 4 A)
Output
Voltage220 / 230 / 240 V L-N, 380 / 400 / 415 V L-L (low-voltage mode 110 / 115 / 120 V); 3W + N + PE, settable 1W + N + PE
Frequencytracks the bypass; 50 ± 0.1 or 60 ± 0.1 Hz in battery mode
Waveform · distortion · power factorsine wave · ≤ 2% resistive full load · 1.0
Transfer inverter ↔ bypass< 1 ms synchronised · < 10 ms not synchronised
Inverter overload≤ 105% continuous · 105–110% 60 min · 110–130% 10 min · 130–155% 1 min · > 155% 200 ms · > 200% immediate
Bypass overload< 130% continuous · 130–155% 1 min · > 155% 200 ms
System
Efficiencyup to 96% (high-voltage mode) · 94% (low-voltage mode) · 99% ECO
Display · cold starttouch screen · battery cold start fitted
CommunicationRS232 · options: SNMP, RS485 + dry contact, protocol card for the approved lithium system, parallel card
Noise (20–25 °C)≤ 50 dB half load · ≤ 55 dB 75% and full load
Environment−5 … 40 °C · 0–95% RH non-condensing · ≤ 2000 m
Dimensions (W × D × H)438 × 535 × 130 mm (3U)
Weight18.4 kg
IST9 15 kVA · Models
ItemIST9 15 kVA
kVA / kW (high-voltage mode)15 / 15
kVA / kW (low-voltage mode)not published
Configuration3/3 · 3/1 · 1/1
W × D × H (mm)438 × 535 × 130
Weight18.4 kg

— not stated in the user manual. Specifications are subject to change without notice.

More technical detailsordering codes

Ordering codes

Ordering codes IST9 15 kVA

Ordering codes IST9 15 kVA
CodeDescription
IST9-10-[n]X9 · IST9-15-[n]X9IST9 10 or 15 kVA in the same way: power distribution box, maintenance breaker and 2, 4, 6, 8 or 10 BBJ2 rack battery cabinets (AEC EMEA product data)
PAR-IST9Parallel board
DRYCNT-IST3/9 · SNMPDry-contact relay board · internal SNMP board
BBJ2Rack battery cabinet, max. 16 × 12 V 9 Ah, 3U

Questions

Questions about the IST9 15 kVA

Is the IST9 15 kVA bigger than the 10 kVA?

No. The 10, 15 and 20 kVA share one chassis: 438 × 535 × 130 mm (3U) and 18.4 kg. Only the 30 and 40 kVA are deeper (720 mm).

How long does the IST9 15 kVA run on battery?

At 15 kW: 3 to 34 minutes with 2 to 10 BBJ2 cabinets (32 to 160 × 12 V 9 Ah). At 7.5 kW: 9 to 86 minutes. AEC sizes every system for the real load.

How big is the AEC IST9 15 kVA and how much does it weigh?

The AEC IST9 15 kVA measures 438 × 535 × 130 mm (3U); weight: 18.4 kg (EMEA 2026 catalogue).