IST9 · Three-phase UPS
IST9 15 kVA Three-phase rack UPS 15 kVA, 3U, 400 V
The IST9 15 kVA is a 15 kVA / 15 kW online double-conversion UPS in the 3U chassis of the 10 and 20 kVA, 18.4 kg, for 3/3, 3/1 or 1/1. For loads of 10 to 15 kW in a 19-inch rack: the step between the 10 and the 20 kVA, with more headroom than the first and a lighter battery than the second.
Quick answers
IST9 15 kVA: quick answers
- What it is
- The IST9 15 kVA is a 15 kVA / 15 kW online double-conversion UPS in the 3U chassis of the 10 and 20 kVA, 18.4 kg, for 3/3, 3/1 or 1/1.
- Who it is for
- For loads of 10 to 15 kW in a 19-inch rack: the step between the 10 and the 20 kVA, with more headroom than the first and a lighter battery than the second.
- Supply and configuration
- 3W + N + PE (settable 1W + N + PE) · 220 / 230 / 240 V L-N · 380 / 400 / 415 V L-L
- Size and weight
- 438 × 535 × 130 mm (3U) · 18.4 kg
- Ordering code
- IST9-15-[n]X9
IST9
What sets apart the IST9 15 kVA
Same body, same electronics family as the 10 and 20 kVA: the touch screen that turns with the unit, the connector jumpers for 3/3, 3/1 or 1/1, the 1–10 A charger and the ±96 to ±240 V DC battery string. AEC orders it as IST9-15 with the power distribution box and maintenance breaker, or IST9-15-[n]X9 with 2, 4, 6, 8 or 10 BBJ2 rack battery cabinets (32 to 160 × 12 V 9 Ah).
Backup at full load in AEC's product data: 3 minutes with 32 batteries, 9 with 64, 17 with 96, 26 with 128 and 34 with 160 (12 V 9 Ah, new batteries, 25 °C); at half load 9, 26, 45, 58 and 86 minutes.
- Against the IST9 10 kVA (one size down): Rated power 15 kVA / 15 kW against 10 kVA / 10 kW; Rated power (kVA / kW, low-voltage mode) not published against 10 kVA / 10 kW.
- Against the IST9 20 kVA (one size up): Rated power 15 kVA / 15 kW against 20 kVA / 20 kW; Rated power (kVA / kW, low-voltage mode) not published against 10 kVA / 10 kW.
Installation
Installing the IST9 15 kVA: space, heat, cables
Each figure with its source. Heat is the power lost at the peak efficiency stated.
| Item | Figure | Source |
|---|---|---|
| Cable entry | At the rear | EMEA 2026 catalogue p.64 |
| Heat at full load | 0.63 kW at 15 kW load, 96 % efficiency | EMEA 2026 catalogue p.64; output PF 1 (EMEA 2026 catalogue) |
| Operating temperature | −5 to 40 °C | EMEA 2026 catalogue p.64 |
Size and floor
How big it is
438 × 535 × 130 mm · 18.4 kg.
Floor load = weight ÷ footprint (18.4 kg).
Drag to turnIn 3D
Look around the IST9 15 kVA
The turntable shows the IST9 20 kVA; the full 3D view opens on the IST9 15 kVA.
Technical data
Technical data IST9 15 kVA
Only this model's values, from the EMEA 2026 catalogue table.
| General | |
|---|---|
| Rated power (kVA / kW, high-voltage mode) | 15 / 15 |
| Rated power (kVA / kW, low-voltage mode) | not published |
| Configuration | 3/3 · 3/1 · 1/1 |
| Input | |
| Connection | 3W + N + PE (settable 1W + N + PE) |
| Voltage range (phase) | high-voltage mode 176–280 V full load, 80–176 V linear derating · low-voltage mode 90–155 V full load, 70–90 V derating |
| Frequency · power factor · THDi | 40–70 Hz · ≥ 0.99 · ≤ 3% resistive, ≤ 5% non-linear full load |
| Bypass | 50 / 60 Hz ± 10% · voltage ± 20% |
| Battery | |
| Voltage | high-voltage mode ± 96 … ± 240 V DC (± 48 … ± 120 cells of 2 V, default ± 96) · low-voltage mode ± 96 … ± 120 V (± 48 … ± 60 cells, default ± 60) |
| Charging current | 1–10 A (default 4 A) |
| Output | |
| Voltage | 220 / 230 / 240 V L-N, 380 / 400 / 415 V L-L (low-voltage mode 110 / 115 / 120 V); 3W + N + PE, settable 1W + N + PE |
| Frequency | tracks the bypass; 50 ± 0.1 or 60 ± 0.1 Hz in battery mode |
| Waveform · distortion · power factor | sine wave · ≤ 2% resistive full load · 1.0 |
| Transfer inverter ↔ bypass | < 1 ms synchronised · < 10 ms not synchronised |
| Inverter overload | ≤ 105% continuous · 105–110% 60 min · 110–130% 10 min · 130–155% 1 min · > 155% 200 ms · > 200% immediate |
| Bypass overload | < 130% continuous · 130–155% 1 min · > 155% 200 ms |
| System | |
| Efficiency | up to 96% (high-voltage mode) · 94% (low-voltage mode) · 99% ECO |
| Display · cold start | touch screen · battery cold start fitted |
| Communication | RS232 · options: SNMP, RS485 + dry contact, protocol card for the approved lithium system, parallel card |
| Noise (20–25 °C) | ≤ 50 dB half load · ≤ 55 dB 75% and full load |
| Environment | −5 … 40 °C · 0–95% RH non-condensing · ≤ 2000 m |
| Dimensions (W × D × H) | 438 × 535 × 130 mm (3U) |
| Weight | 18.4 kg |
| Item | IST9 15 kVA |
|---|---|
| kVA / kW (high-voltage mode) | 15 / 15 |
| kVA / kW (low-voltage mode) | not published |
| Configuration | 3/3 · 3/1 · 1/1 |
| W × D × H (mm) | 438 × 535 × 130 |
| Weight | 18.4 kg |
— not stated in the user manual. Specifications are subject to change without notice.
More technical detailsordering codes
Ordering codes
Ordering codes IST9 15 kVA
| Code | Description |
|---|---|
| IST9-10-[n]X9 · IST9-15-[n]X9 | IST9 10 or 15 kVA in the same way: power distribution box, maintenance breaker and 2, 4, 6, 8 or 10 BBJ2 rack battery cabinets (AEC EMEA product data) |
| PAR-IST9 | Parallel board |
| DRYCNT-IST3/9 · SNMP | Dry-contact relay board · internal SNMP board |
| BBJ2 | Rack battery cabinet, max. 16 × 12 V 9 Ah, 3U |
Questions
Questions about the IST9 15 kVA
Is the IST9 15 kVA bigger than the 10 kVA?
No. The 10, 15 and 20 kVA share one chassis: 438 × 535 × 130 mm (3U) and 18.4 kg. Only the 30 and 40 kVA are deeper (720 mm).
How long does the IST9 15 kVA run on battery?
At 15 kW: 3 to 34 minutes with 2 to 10 BBJ2 cabinets (32 to 160 × 12 V 9 Ah). At 7.5 kW: 9 to 86 minutes. AEC sizes every system for the real load.
How big is the AEC IST9 15 kVA and how much does it weigh?
The AEC IST9 15 kVA measures 438 × 535 × 130 mm (3U); weight: 18.4 kg (EMEA 2026 catalogue).