IST9 · Three-phase UPS
IST9 40 kVA Three-phase rack UPS 40 kVA, 3U, 400 V
The IST9 40 kVA is a 40 kVA / 40 kW online double-conversion UPS in 3U, the most powerful 19-inch AEC UPS, for 3/3 or 3/1. For data rooms and edge sites that need 40 kW in a rack, or N+1 systems of several IST9 in parallel.
Quick answers
IST9 40 kVA: quick answers
- What it is
- The IST9 40 kVA is a 40 kVA / 40 kW online double-conversion UPS in 3U, the most powerful 19-inch AEC UPS, for 3/3 or 3/1.
- Who it is for
- For data rooms and edge sites that need 40 kW in a rack, or N+1 systems of several IST9 in parallel.
- Supply and configuration
- 3W + N + PE · 220 / 230 / 240 V L-N · 380 / 400 / 415 V L-L
- Size and weight
- 438 × 720 × 130 mm (3U) · 34.2 kg
- Ordering code
- IST9-40
IST9
What sets apart the IST9 40 kVA
Forty kilowatts in 130 mm of height is what the IST9 40 kVA brings: 438 × 720 × 130 mm, 34.2 kg. It draws 75 A per phase in 3/3 and up to 111 A from the battery, so the catalogue recommends 100 A 3P AC breakers and a 200 A 3P DC breaker; in 3/1 the single-phase output reaches 182 A on a 250 A 1P breaker.
In low-voltage mode it delivers 20 kVA / 20 kW. With the optional parallel card, units join or leave the system online and share the current (N+1: total load up to N times one unit). The lithium protocol card connects the approved lithium battery system over RS485.
- Against the IST9 30 kVA (one size down): Rated power 40 kVA / 40 kW against 30 kVA / 30 kW; Weight 34.2 kg against 34.1 kg.
Planning data
IST9 40 kVA: currents, breakers, cables, batteries
The rows and columns of the EMEA 2026 catalogue's and AEC manuals' tables that concern the IST9 40 kVA.
Connected, and ready for redundancy
| Model | Mode | AC input (A) | Bypass input (A) | DC input (A) | AC output (A) |
|---|---|---|---|---|---|
| 40 kVA | 3/3 | 100 × 3P | 100 × 3P | 200 × 3P | 100 × 3P |
| 40 kVA | 3/1 | 100 × 3P | 250 × 1P | 200 × 3P | 250 × 1P |
Currents, codes and options
| Model | Mode | AC input (A) | Bypass input (A) | DC input (A) | AC output (A) |
|---|---|---|---|---|---|
| 40 kVA | 3/3 | 75 | 61 | 111 | 61 |
| 40 kVA | 3/1 | 75 | 182 | 111 | 182 |
Installation
Installing the IST9 40 kVA: space, heat, cables
Each figure with its source. Heat is the power lost at the peak efficiency stated.
| Item | Figure | Source |
|---|---|---|
| Cable entry | At the rear | EMEA 2026 catalogue p.64 |
| Heat at full load | 1.67 kW at 40 kW load, 96 % efficiency | EMEA 2026 catalogue p.64; output PF 1 (EMEA 2026 catalogue) |
| Operating temperature | −5 to 40 °C | EMEA 2026 catalogue p.64 |
Size and floor
How big it is
438 × 720 × 130 mm · 34.2 kg.
Floor load = weight ÷ footprint (34.2 kg).
Efficiency
How efficient is the AEC IST9 40 kVA at your load?
IST9 40 kVA, 40 kW at its rating, double conversion, high-voltage mode (typical curve, AEC's method). Heat to remove on this curve: 25%: 0.48 kW (η 95.4%) · 50%: 0.83 kW (η 96%) · 75%: 1.35 kW (η 95.7%) · 100%: 1.93 kW (η 95.4%). At 50% load, 24/7, it loses about 7,300 kWh a year.
How the curve is drawn and where each figure comes from: the IST9 range page.
- Load
- —
- Lost as heat
- —
- Energy lost in a year, 24/7
- —
- Its cost in a year at € per kWh
- —
- The catalogue's examples use €0.20 per kWh.
Where each figure comes from
| Mode | Efficiency | Kind | Models | Source |
|---|---|---|---|---|
| Double conversion, high-voltage mode | 25%: 95.4% · 50%: 96% · 75%: 95.7% · 100%: 95.4% | Typical curve, derived from the datasheet efficiency of 96% (AEC method) | all | AEC datasheet: AC/AC efficiency of the IST6-PM100 100 kW power module (the curve's shape) |
| Double conversion, low-voltage mode | 25%: 93.4% · 50%: 94% · 75%: 93.7% · 100%: 93.4% | Typical curve, derived from the datasheet efficiency of 94% (AEC method) | IST9 40 kVA · IST9 10 kVA · IST9 20 kVA | AEC datasheet: AC/AC efficiency of the IST6-PM100 100 kW power module (the curve's shape) |
| ECO | 99% | Datasheet figure, load not stated | all |
EMEA 2026 catalogue figures: Double conversion, high-voltage mode up to 96% · Double conversion, low-voltage mode up to 94% · ECO up to 99%.
Drag to turnTechnical data
Technical data IST9 40 kVA
Only this model's values, from the EMEA 2026 catalogue table.
| General | |
|---|---|
| Rated power (kVA / kW, high-voltage mode) | 40 / 40 |
| Rated power (kVA / kW, low-voltage mode) | 20 / 20 |
| Configuration | 3/3 · 3/1 |
| Input | |
| Connection | 3W + N + PE |
| Voltage range (phase) | high-voltage mode 176–280 V full load, 80–176 V linear derating · low-voltage mode 90–155 V full load, 70–90 V derating |
| Frequency · power factor · THDi | 40–70 Hz · ≥ 0.99 · ≤ 3% resistive, ≤ 5% non-linear full load |
| Bypass | 50 / 60 Hz ± 10% · voltage ± 20% |
| Battery | |
| Voltage | high-voltage mode ± 96 … ± 240 V DC (± 48 … ± 120 cells of 2 V, default ± 96) · low-voltage mode ± 96 … ± 120 V (± 48 … ± 60 cells, default ± 60) |
| Full-load derating by cells | ± 48 … ± 90 cells: 100 × 0.0625 × N / 6 % |
| Charging current | 1–20 A (default 15 A) |
| Output | |
| Voltage | 220 / 230 / 240 V L-N, 380 / 400 / 415 V L-L (low-voltage mode 110 / 115 / 120 V); 3W + N + PE, settable 1W + N + PE |
| Frequency | tracks the bypass; 50 ± 0.1 or 60 ± 0.1 Hz in battery mode |
| Waveform · distortion · power factor | sine wave · ≤ 2% resistive full load · 1.0 |
| Transfer inverter ↔ bypass | < 1 ms synchronised · < 10 ms not synchronised |
| Inverter overload | ≤ 105% continuous · 105–110% 60 min · 110–130% 10 min · 130–155% 1 min · > 155% 200 ms · > 200% immediate |
| Bypass overload | < 130% continuous · 130–155% 1 min · > 155% 200 ms |
| System | |
| Efficiency | up to 96% (high-voltage mode) · 94% (low-voltage mode) · 99% ECO |
| Display · cold start | touch screen · battery cold start fitted |
| Communication | RS232 · options: SNMP, RS485 + dry contact, protocol card for the approved lithium system, parallel card |
| Noise (20–25 °C) | ≤ 55 dB half load · ≤ 58 dB 75% · ≤ 60 dB full load |
| Environment | −5 … 40 °C · 0–95% RH non-condensing · ≤ 2000 m |
| Dimensions (W × D × H) | 438 × 720 × 130 mm (3U) |
| Weight | 34.2 kg |
| Item | IST9 40 kVA |
|---|---|
| kVA / kW (high-voltage mode) | 40 / 40 |
| kVA / kW (low-voltage mode) | 20 / 20 |
| Configuration | 3/3 · 3/1 |
| W × D × H (mm) | 438 × 720 × 130 |
| Weight | 34.2 kg |
— not stated in the user manual. Specifications are subject to change without notice.
More technical detailsordering codes
Ordering codes
Ordering codes IST9 40 kVA
| Code | Description |
|---|---|
| IST9-10 · IST9-30 · IST9-40 | Code on request |
| PAR-IST9 | Parallel board |
| DRYCNT-IST3/9 · SNMP | Dry-contact relay board · internal SNMP board |
| BBJ2 | Rack battery cabinet, max. 16 × 12 V 9 Ah, 3U |
Questions
Questions about the IST9 40 kVA
Can several IST9 40 kVA work in parallel?
Yes, with the parallel kit PAR-IST9 (parallel card and 2 m cable, CAN communication). Units are started one by one, then joined; a faulty unit leaves the system with an alarm and can be serviced online.
Can the IST9 40 kVA use lithium batteries?
Yes: the battery type is set on the screen, lead-acid or the approved lithium battery system, which talks to the UPS through the optional lithium protocol card (RS485 on RJ45).
How big is the AEC IST9 40 kVA and how much does it weigh?
The AEC IST9 40 kVA measures 438 × 720 × 130 mm (3U); weight: 34.2 kg (EMEA 2026 catalogue).
Talk to an AEC engineer
Tell us the load, the supply and the backup time you need for the AEC IST9 40 kVA: we answer with the model and the batteries that fit. AEC International sells through distributors in about 80 countries and an agency in every Italian region: ask AEC which one serves your area.