Technology · isolation

Isolation transformers in UPS systems, explained

An isolation transformer separates a UPS output from its input: no conductor runs straight through. It gives the load its own neutral and earth, changes the voltage when needed and filters part of the noise. Most modern UPS are built without one and add it only where the installation needs it.

What it does

Four jobs, one transformer.

  • Galvanic isolation. Input and output share no conductor; energy crosses only through the magnetic core.
  • A new neutral and earth bond. The secondary forms a new source, with its neutral earthed where it is installed.
  • Voltage change. The output voltage can differ from the input voltage, set by the ratio of the windings.
  • Less common-mode noise. Disturbances between the lines and earth are kept away from the load, which matters to some medical, laboratory and audio equipment.

Transformer-based or transformerless

Why most UPS have none inside.

A transformer adds weight, floor space and losses. Modern online double-conversion UPS make their output with the inverter alone and are more efficient without one; an APC white paper on the subject (The role of isolation transformers in data center UPS systems) concludes that a transformer belongs where the installation needs it, not in every UPS.

In the AEC range, the three-phase IST7-T, 100 to 200 kVA, carries an output isolation transformer built into every model; for the others, a transformer is added where the installation needs one.

When you need one

Four cases, and the AEC answer.

If none of these applies, a transformerless UPS is the efficient choice.

Your installationWhy a transformerWith AEC
Industrial sites, difficult grids, loads that need full electrical isolationComplete electrical isolation between input and outputIST7-T: output isolation transformer built in, 100 to 200 kVA
Supply at one voltage, loads at anotherA different voltage and a neutral at the loadA transformer after the UPS; our engineers size it with the UPS
3-wire supply, loads that need a neutralThe supply has no neutral to pass onA transformer after the UPS makes one; our engineers size it with the UPS
Medical or laboratory equipmentLow leakage current and a new, separately earthed source, as the equipment or the engineer requiresTell us the equipment: we answer with the UPS and the isolation it needs

More on the range: IST7-T, online UPS with isolation transformer · all products

Questions

Questions people ask

What does an isolation transformer do in a UPS?

It separates the output from the input galvanically: no conductor runs straight through. That lets the output have its own neutral and earth bond, change the voltage, and keeps much of the common-mode noise of the supply away from the load.

Do I need a UPS with an isolation transformer?

Not for most IT loads on a supply with a neutral: modern online UPS are transformerless and more efficient. You need one when the load needs a neutral the supply does not have, a different voltage than the supply, a separately earthed source by design, or very low leakage current (some medical and laboratory equipment).

Transformer-based or transformerless UPS?

Transformerless UPS are smaller, lighter and more efficient; transformer-based UPS isolate and can change voltage inside the cabinet. Today most large UPS are transformerless and a transformer is added outside, only where the installation needs one.

Which AEC UPS has an isolation transformer?

IST7-T, the three-phase online UPS from 100 to 200 kVA, has an output isolation transformer built into every model, according to the EMEA 2026 catalogue. For the other ranges, a transformer is added where the installation needs one.

Not sure you need one?

Send us the single-line diagram or the supply and the loads: our engineers say whether a transformer is needed and where it goes.