Technology · Power electronics
From thyristor to silicon carbide
Seventy years of the power switch inside a UPS: SCR, bipolar transistors, MOSFET, IGBT, 3-level IGBT and silicon carbide. What each one changed in a typical UPS of its time (input power factor, current distortion, efficiency), and what AEC UPS use today.
The eras
Seven switches, one story.
Tap an era, or use the arrow keys.
1957 · Thyristor (SCR)
The thyristor: the first silicon power switch
General Electric brought out the silicon-controlled rectifier (SCR) in 1957. A gate pulse turns it on, but it turns off only when its current falls to zero. The first static UPS used it as a 6- or 12-pulse rectifier and, with extra commutation circuits, as an inverter driving a heavy output transformer.
Typical UPS of the time: input power factor around 0.8, input current distortion around 30% on a 6-pulse bridge, efficiency in the high 80s.
AEC 1968: Allis Electric is founded in Taipei, building switchboards, motor control and industrial controls.
1970s · Bipolar transistor (BJT)
Bipolar transistors: the inverter learns PWM
A bipolar power transistor (often a Darlington pair) turns off from its base, so the inverter no longer needs commutation circuits. The first pulse-width-modulated (PWM) inverters switch at a few kHz and small UPS get lighter. The price: a base current to supply all the time, and a slow turn-off.
The rectifier stays a thyristor bridge; the inverter's sine wave gets cleaner and the output transformer smaller.
1980s · Power MOSFET
The power MOSFET: speed, at low voltage
Driven by voltage, with almost no gate current, the power MOSFET switches at tens to hundreds of kHz. Its on-resistance climbs steeply with the voltage it has to block, so in a UPS it found its place in the low-voltage stages: battery DC/DC converters, auxiliary supplies, small single-phase units.
Still in every AEC UPS today, in the low-voltage parts.
1990s · IGBT
The IGBT: a MOSFET's gate, a bipolar's current
The insulated-gate bipolar transistor joins a MOSFET's easy gate to a bipolar transistor's low conduction loss. Developed in the early 1980s and in production by the middle of the decade, it took over the UPS: inverters switching at 2–20 kHz with a clean sine wave and, at the input, PFC rectifiers with power factor 0.99 and current distortion under 5%. With them the output transformer became optional: the transformerless UPS of the 2000s.
Typical double conversion: 90–93% with a transformer, 93–95% without.
AEC IST7-T: IGBT rectifier with THDi < 5% and PF ≥ 0.99, and an isolation transformer kept in every model for the loads that need one.
2010s · 3-level IGBT
Three levels: half the voltage on each switch
Neutral-point-clamped (NPC) and T-type inverters, first described in 1981, put three voltage levels on each output instead of two. Each IGBT blocks half the DC bus, so switching losses fall, the ripple halves and the output filter shrinks: double conversion reaches 96–97%.
The workhorse of today's three-phase UPS.
AEC IST6 modular: a PFC rectifier and a three-level inverter in every power module, up to 98.1% with PLUS modules (IST6 200–500). CPSS 10–200: 3-level inverter, 96%.
2020s · Silicon carbide (SiC)
Silicon carbide: a wider band gap
Silicon carbide has a band gap of 3.26 eV against silicon's 1.12, a critical electric field about ten times higher and three times the thermal conductivity. SiC Schottky diodes reached the market in 2001 and SiC MOSFETs in 2011: they block high voltage in a thin chip and switch fast with low losses, so a double-conversion UPS reaches 98–99% and needs less cooling.
Typical double conversion: 97.5–99%.
Next · Gallium nitride (GaN)
Gallium nitride: what comes next
Gallium nitride (band gap 3.4 eV) already switches at MHz in phone chargers and server power supplies, at lower voltages than a three-phase UPS needs. Its first place in UPS is the small, low-voltage stages; for the high-power stage, silicon carbide stays the material to beat.
Side by side
What each generation gained.
The faster and cleaner the switching, the higher the efficiency and the smaller the filters and transformers.
| Generation | Years | Switching, kHz | Input PF | THDi | Efficiency |
|---|---|---|---|---|---|
| Thyristor rectifier and inverter, transformer | 1960s–80s | 0.05–1 | ≈0.8 | ≈30% | 85–90% |
| Thyristor rectifier, BJT PWM inverter | 1970s–80s | 1–5 | ≈0.8 | ≈30% | 88–91% |
| IGBT inverter with output transformer | 1990s | 2–10 | 0.9–0.95 | 8–10% | 90–93% |
| IGBT rectifier and inverter, transformerless | 2000s | 10–20 | 0.99 | < 5% | 93–95% |
| 3-level IGBT | 2010s | 10–20 | 0.99 | < 3% | 96–97% |
| Silicon carbide (SiC) | 2020s | 20–100 | 0.99 | < 3% | 97.5–99% |
| IST6 200–500 (AEC) | today | — | — | — | 98.1% |
The heat
Every point of efficiency is heat you do not make.
Losses = load × (1 ÷ efficiency − 1), at the middle of each generation's typical band, with a steady 100 kW load.
Did you know?
Notes from power electronics.
The word thyristor joins thyratron, the gas-filled tube it replaced, and transistor.
Silicon carbide was first made in 1891 by Edward Acheson, as an abrasive he called carborundum. Henri Moissan found it in nature, in a meteorite, in 1893: the mineral is named moissanite after him.
In 1907 Henry Round saw a silicon carbide crystal glow under voltage: the first light-emitting diode, a hundred years before SiC reached the UPS.
At 90% a 1 MW load wastes about 111 kW as heat; at 99%, about 10 kW. The difference is about 885,000 kWh a year, before the air conditioning that removes the heat.
A 3-level inverter's output already looks like a staircase: the filter only has to smooth half the step of a 2-level one.
AEC is the UPS brand of the AEC Group, which began with switchboards and motor control in 1968; the group's transformers today reach 36 kV and 15,000 kVA.
Films
Power electronics on film.
Our own films, with sound: press play.
Questions
Questions people ask
What is the difference between an IGBT and a MOSFET?
Both are driven by a voltage on the gate. A MOSFET conducts like a resistor and switches faster, but its resistance rises steeply with the voltage it blocks; an IGBT conducts like a bipolar transistor, with low losses at high voltage and current, which is why it is the switch of a three-phase UPS's power stages.
What does a 3-level inverter change?
Each switch blocks half the DC bus voltage and the output has three levels instead of two: lower switching losses, half the ripple and a smaller filter. Double conversion goes from the typical 93–95% of 2-level designs to 96–97%.
Why does silicon carbide raise UPS efficiency?
SiC has a band gap of 3.26 eV and a critical field about ten times silicon's: it blocks high voltage in a thin chip, conducts with little resistance and switches fast with low losses. Double-conversion UPS with SiC reach 98–99%.
Are thyristors still used in UPS?
Yes, where a rugged switch at line frequency is needed: the static bypass of every online UPS is a pair of thyristors in anti-parallel, which moves the load to the utility without a break.