Technology · architecture

Modular UPS: hot-swap modules and N+X redundancy

A modular UPS is a frame of slots and a set of identical power modules: the modules share the load, any one can be swapped with the system running, and one spare module more than the load needs keeps the load on the inverter if a module stops.

Cabinets and modules

Every IST6 cabinet in the catalogue.

Power modules are hot-swappable and slide in from the front; the output power factor is 1 (kVA = kW) as standard.

CabinetModuleSlotsCabinet powerBatteryNotes
IST6-12030 kVA4 + 1120 kVAExternal, lead-acid or lithium (BMS card)Fifth slot for an N+1 module. 2U power modules, 24 kg. More cabinets in parallel with the parallel kit.
IST6 200–50050 kVA4200 kVAExternal, lead-acid or lithiumCabinet 607 × 860 × 2000 mm, 224 kg without power modules. 3U bypass module.
IST6 200–50050 kVA6300 kVAExternal, lead-acid or lithiumCabinet 607 × 860 × 2000 mm, 236 kg without power modules. 3U bypass module.
IST6 200–50050 kVA8400 kVAExternal, lead-acid or lithiumCabinet 1203 × 864 × 2000 mm, 459 kg without power modules. 3U bypass module.
IST6 200–50050 kVA10500 kVAExternal, lead-acid or lithiumCabinet 1203 × 864 × 2000 mm, 506 kg without power modules. 4.5U bypass module. Up to 8 UPS in parallel.
IST6 400–1200100 kVA4400 kVAExternal, lead-acid or lithiumCabinet 801 × 1000 × 2000 mm, 345 kg without power modules. 3U bypass module.
IST6 400–1200100 kVA5500 kVAExternal, lead-acid or lithiumCabinet 801 × 1000 × 2000 mm, 434 kg without power modules. 4.5U bypass module.
IST6 400–1200100 kVA6600 kVAExternal, lead-acid or lithiumCabinet 801 × 1000 × 2000 mm, 434 kg without power modules. 4.5U bypass module.
IST6 400–1200100 kVA8800 kVAExternal, lead-acid or lithiumCabinet 801 × 1000 × 2000 mm, 435 kg without power modules. 4.5U bypass module.
IST6 400–1200100 kVA101,000 kVAExternal, lead-acid or lithiumCabinet 1201 × 1000 × 2000 mm, 662 kg without power modules. 4.5U bypass module.
IST6 400–1200100 kVA121,200 kVAExternal, lead-acid or lithiumCabinet 1201 × 1000 × 2000 mm, 662 kg without power modules. 4.5U bypass module. Up to 98.1% efficiency with PLUS modules; up to 8 UPS in parallel: 9.6 MW.
Modular UPS, closedModular UPS opened: the power modules in their bays

Modular UPS, closed

Hot-swap

Open it, pull a module

In an IST6 each power module carries its own rectifier, inverter and battery converter; the cabinet holds the centralised bypass module, the control cards, the switches and the display. Pulling a module out leaves the others sharing the load, so service happens with the load on the inverter, as long as the remaining modules can carry it.

N + X

Redundancy you can count

N modules carry the load; X are spare. With 90 kVA of load on 30 kVA modules, N is 3: fit 4 and any one module can fail (N+1), fit 5 and two can (N+2). The display shows the state.

Large modular UPS, closedLarge modular UPS opened: power modules stacked in the frame

Large modular UPS, closed

Standards

Standards for a modular system

A modular UPS is classed and tested as one UPS: IEC 62040-3 sets how its performance is stated and measured (online double conversion is its VFI class), IEC 62040-1 its safety and IEC 62040-2 its electromagnetic compatibility. The AEC catalogue gives the derating above 2000 m of altitude of the IST6-120 per IEC 62040-3.

Redundancy is counted in modules: with N modules carrying the load, one more (N+1) keeps the load on the inverter if a module fails, and the failed one is pulled with the system running.