Modular UPS: hot-swap modules and N+X redundancy
A modular UPS is a frame of slots and a set of identical power modules: the modules share the load, any one can be swapped with the system running, and one spare module more than the load needs keeps the load on the inverter if a module stops.
Cabinets and modules
Every IST6 cabinet in the catalogue.
Power modules are hot-swappable and slide in from the front; the output power factor is 1 (kVA = kW) as standard.
| Cabinet | Module | Slots | Cabinet power | Battery | Notes |
|---|---|---|---|---|---|
| IST6-120 | 30 kVA | 4 + 1 | 120 kVA | External, lead-acid or lithium (BMS card) | Fifth slot for an N+1 module. 2U power modules, 24 kg. More cabinets in parallel with the parallel kit. |
| IST6 200–500 | 50 kVA | 4 | 200 kVA | External, lead-acid or lithium | Cabinet 607 × 860 × 2000 mm, 224 kg without power modules. 3U bypass module. |
| IST6 200–500 | 50 kVA | 6 | 300 kVA | External, lead-acid or lithium | Cabinet 607 × 860 × 2000 mm, 236 kg without power modules. 3U bypass module. |
| IST6 200–500 | 50 kVA | 8 | 400 kVA | External, lead-acid or lithium | Cabinet 1203 × 864 × 2000 mm, 459 kg without power modules. 3U bypass module. |
| IST6 200–500 | 50 kVA | 10 | 500 kVA | External, lead-acid or lithium | Cabinet 1203 × 864 × 2000 mm, 506 kg without power modules. 4.5U bypass module. Up to 8 UPS in parallel. |
| IST6 400–1200 | 100 kVA | 4 | 400 kVA | External, lead-acid or lithium | Cabinet 801 × 1000 × 2000 mm, 345 kg without power modules. 3U bypass module. |
| IST6 400–1200 | 100 kVA | 5 | 500 kVA | External, lead-acid or lithium | Cabinet 801 × 1000 × 2000 mm, 434 kg without power modules. 4.5U bypass module. |
| IST6 400–1200 | 100 kVA | 6 | 600 kVA | External, lead-acid or lithium | Cabinet 801 × 1000 × 2000 mm, 434 kg without power modules. 4.5U bypass module. |
| IST6 400–1200 | 100 kVA | 8 | 800 kVA | External, lead-acid or lithium | Cabinet 801 × 1000 × 2000 mm, 435 kg without power modules. 4.5U bypass module. |
| IST6 400–1200 | 100 kVA | 10 | 1,000 kVA | External, lead-acid or lithium | Cabinet 1201 × 1000 × 2000 mm, 662 kg without power modules. 4.5U bypass module. |
| IST6 400–1200 | 100 kVA | 12 | 1,200 kVA | External, lead-acid or lithium | Cabinet 1201 × 1000 × 2000 mm, 662 kg without power modules. 4.5U bypass module. Up to 98.1% efficiency with PLUS modules; up to 8 UPS in parallel: 9.6 MW. |


Hot-swap
Open it, pull a module
In an IST6 each power module carries its own rectifier, inverter and battery converter; the cabinet holds the centralised bypass module, the control cards, the switches and the display. Pulling a module out leaves the others sharing the load, so service happens with the load on the inverter, as long as the remaining modules can carry it.
N + X
Redundancy you can count
N modules carry the load; X are spare. With 90 kVA of load on 30 kVA modules, N is 3: fit 4 and any one module can fail (N+1), fit 5 and two can (N+2). The display shows the state.


Standards
Standards for a modular system
A modular UPS is classed and tested as one UPS: IEC 62040-3 sets how its performance is stated and measured (online double conversion is its VFI class), IEC 62040-1 its safety and IEC 62040-2 its electromagnetic compatibility. The AEC catalogue gives the derating above 2000 m of altitude of the IST6-120 per IEC 62040-3.
Redundancy is counted in modules: with N modules carrying the load, one more (N+1) keeps the load on the inverter if a module fails, and the failed one is pulled with the system running.
Talk to an engineer
Tell us the load, the voltage and the minutes you need. We answer with the model and the batteries that fit.