Technology · how it works

Online double conversion: how an AEC UPS rebuilds its output

Every AEC UPS rebuilds its output from scratch: the mains is rectified to DC, the inverter makes a new, clean sine wave, and the battery sits on the DC bus, so a mains failure changes nothing at the output.

Six operating modes

Pick a mode. Watch the power move.

The diagram follows the power; beside it, a real AEC UPS touchscreen in that mode, with a note on what is happening.

M.BYP BYPASS MAINS RectifierAC → DC DC Battery InverterDC → AC SS LOAD
AEC UPS display in this mode
Mains inverter output (normal)

Mains → rectifier → inverter → output, the battery charged at the same time. Tap any block of the diagram for its readings.

SS: static switch. M.BYP: external maintenance bypass. Screens: an AEC UPS touchscreen, one per mode.

From the catalogue

Diagrams, explained.

Click any diagram to open it large.

Power flow blockThe power path, block by block: rectifier, DC bus with the battery, inverter and static bypass.
Frequency converterFrequency-converter operation: the output runs at its own set frequency and the bypass is not used.
Maintenance bypassThe maintenance bypass feeds the load straight from the mains while the UPS is serviced.
Short-circuit protectionHow the UPS reacts to a short circuit on its output.
Power walk-inPower walk-in: when the mains returns, the rectifier takes the load back gradually.
Generator compatibilityThe UPS working with a generator set.
Peak shavingPeak shaving: the battery covers part of the load at peak times to limit what is drawn from the grid.

Why online

Zero transfer time, by design

Because the inverter is always the source of the output, there is nothing to switch when the mains fails: the battery is already on the DC bus. The output voltage and frequency are the UPS's own, whatever the mains does: sags, surges, frequency drift and noise stay on the input side.

The static bypass is the safety net: on an overload or an inverter fault the static switch moves the load to the bypass in a few milliseconds, and back once the inverter is ready. Every AEC range works this way, from the single-phase IST3 to the modular IST6.

ModeLoad fed byBattery
NormalRectifier → inverterCharging
Mains failureBattery → inverterDischarging
Static bypassBypass lineCharging
ECOBypass, inverter readyCharging
Frequency converterRectifier → inverter, bypass offCharging
Maintenance bypassMains, UPS isolatedOff

Standards

Which standard classes it

The UPS standard has four parts: IEC 62040-1 sets the general and safety requirements, IEC 62040-2 the electromagnetic compatibility (EMC), IEC 62040-3 how performance is specified and tested, and IEC 62040-4 the environmental aspects. In Europe they are published as EN 62040.

IEC 62040-3 sorts UPS by how the output depends on the input: VFD (voltage and frequency dependent, the standby UPS), VI (voltage independent, the line-interactive UPS) and VFI (voltage and frequency independent). Online double conversion is the VFI class: the output voltage and frequency are the inverter's, whatever the mains does.

What the AEC catalogue states for the ranges: the IST7-T to EN/IEC 62040-1 (safety) and EN/IEC 62040-2 (EMC, category C3); the IST7 60–200 EMC to IEC 62040-2:2016, category C3, which is not for residential use without additional measures; the derating above 2000 m of altitude of the IST7 10–40, IST6-120, All-in-One and L6 follows IEC 62040-3.