Technology · how it works
Online double conversion: how an AEC UPS rebuilds its output
Every AEC UPS rebuilds its output from scratch: the mains is rectified to DC, the inverter makes a new, clean sine wave, and the battery sits on the DC bus, so a mains failure changes nothing at the output.
Six operating modes
Pick a mode. Watch the power move.
The diagram follows the power; beside it, a real AEC UPS touchscreen in that mode, with a note on what is happening.

Mains → rectifier → inverter → output, the battery charged at the same time. Tap any block of the diagram for its readings.
SS: static switch. M.BYP: external maintenance bypass. Screens: an AEC UPS touchscreen, one per mode.
From the catalogue
Diagrams, explained.
Click any diagram to open it large.
Why online
Zero transfer time, by design
Because the inverter is always the source of the output, there is nothing to switch when the mains fails: the battery is already on the DC bus. The output voltage and frequency are the UPS's own, whatever the mains does: sags, surges, frequency drift and noise stay on the input side.
The static bypass is the safety net: on an overload or an inverter fault the static switch moves the load to the bypass in a few milliseconds, and back once the inverter is ready. Every AEC range works this way, from the single-phase IST3 to the modular IST6.
| Mode | Load fed by | Battery |
|---|---|---|
| Normal | Rectifier → inverter | Charging |
| Mains failure | Battery → inverter | Discharging |
| Static bypass | Bypass line | Charging |
| ECO | Bypass, inverter ready | Charging |
| Frequency converter | Rectifier → inverter, bypass off | Charging |
| Maintenance bypass | Mains, UPS isolated | Off |
Standards
Which standard classes it
The UPS standard has four parts: IEC 62040-1 sets the general and safety requirements, IEC 62040-2 the electromagnetic compatibility (EMC), IEC 62040-3 how performance is specified and tested, and IEC 62040-4 the environmental aspects. In Europe they are published as EN 62040.
IEC 62040-3 sorts UPS by how the output depends on the input: VFD (voltage and frequency dependent, the standby UPS), VI (voltage independent, the line-interactive UPS) and VFI (voltage and frequency independent). Online double conversion is the VFI class: the output voltage and frequency are the inverter's, whatever the mains does.
What the AEC catalogue states for the ranges: the IST7-T to EN/IEC 62040-1 (safety) and EN/IEC 62040-2 (EMC, category C3); the IST7 60–200 EMC to IEC 62040-2:2016, category C3, which is not for residential use without additional measures; the derating above 2000 m of altitude of the IST7 10–40, IST6-120, All-in-One and L6 follows IEC 62040-3.
Talk to an engineer
Tell us the load, the voltage and the minutes you need. We answer with the model and the batteries that fit.