Technology · Efficiency

EU Code of Conduct on UPS energy efficiency

The EU Code of Conduct on the efficiency of AC UPS (version 2.0, the European Commission's Joint Research Centre) sets minimum efficiencies for UPS to EN 62040-3, by performance class and power band, at 25, 50, 75 and 100% load. Signing it is voluntary; this page gives AEC's efficiency curves at the same loads.

What it asks

What version 2.0 of the Code asks

  • It covers AC UPS to EN 62040-3; UPS with DC output, for example, are outside it.
  • It sets a minimum efficiency for each performance class (VFI, VI, VFD of EN 62040-3) and power band, at 25, 50, 75 and 100% load.
  • The minimums hold as guaranteed and as measured values, with the test methods of EN 62040-3.
  • The manufacturer also reports behaviour and efficiency in higher-efficiency modes such as ECO.
  • A signatory signs a form and reports its UPS data on the Code's data sheet.

The thresholds of each band are in the Code's tables: JRC publication (version 2.0, 2021).

AEC

AEC UPS efficiency at the same loads

The range pages' curves read at 25, 50, 75 and 100%: measured where AEC has the table, otherwise derived from the datasheet.

AC/AC efficiency in double conversion at the load shown, and in ECO mode
Range · models25%50%75%100%ECOCurve
IST3 IST3-186.14%188.7%90.06%90.83%98.3%measured
IST3 IST3-289.36%191.23%92.16%92.56%98.3%measured
IST3 IST3-390.84%191.85%93.3%93.1%98.3%measured
IST3 IST3-6, IST3-1093.04%194.05%95.5%95.3%98.3%derived from the 95.5% datasheet figure
IST3-J IST3-J 1 kVA86.14%188.7%90.06%90.83%98.3%measured
IST3-J IST3-J 2 kVA89.36%191.23%92.16%92.56%98.3%measured
IST3-J IST3-J 3 kVA90.84%191.85%93.3%93.1%98.3%measured
IST3-J IST3-J 6 kVA, IST3-J 10 kVA93.04%194.05%95.5%95.3%98.3%derived from the 95.5% datasheet figure
IST8 IST8-186.81%189.37%90.73%91.5%—derived from the 91.5% datasheet figure
IST8 IST8-288.3%190.17%91.1%91.5%—derived from the 91.5% datasheet figure
IST8 IST8-390.54%191.55%93.0%92.8%—derived from the 93.0% datasheet figure
All-in-One All-in-One 20 kVA95.4%96.0%95.7%95.4%99.0%derived from the 96.0% datasheet figure
IST9 IST9 10 kVA, IST9 15 kVA, IST9 20 kVA, IST9 30 kVA, IST9 40 kVA95.4%96.0%95.7%95.4%99.0%derived from the 96.0% datasheet figure
IST7 10–40 IST7-10, IST7-20, IST7-30, IST7-4095.4%96.0%95.7%95.4%99.0%derived from the 96.0% datasheet figure
IST7 60–200 IST7-60, IST7-80, IST7-100, IST7-120, IST7-160, IST7-20095.9%96.5%96.2%95.9%99.0%derived from the 96.5% datasheet figure
IST6-120 IST6-120, 1 × 30 kVA, IST6-120, 2 × 30 kVA, IST6-120, 3 × 30 kVA, IST6-120, 4 × 30 kVA96.4%97.0%96.7%96.4%99.0%derived from the 97.0% datasheet figure
IST6 200–500 IST6-200, 4 × 50 kVA, IST6-300, 6 × 50 kVA, IST6-400, 8 × 50 kVA, IST6-500, 10 × 50 kVA97.5%98.1%97.8%97.5%99.2%derived from the 98.1% datasheet figure
IST6 400–1200 IST6-400H, 4 × 100 kVA, IST6-500H, 5 × 100 kVA, IST6-600H, 6 × 100 kVA, IST6-800, 8 × 100 kVA, IST6-1000, 10 × 100 kVA, IST6-1200, 12 × 100 kVA97.5%98.1%97.8%97.5%99.2%derived from the 98.1% datasheet figure

Measured: AEC's AC/AC efficiency tables (IST3-J 1–3 kVA at 30/50/75/100%: in the 25% column the value marked ¹ is the one at 30%; IST6-PM100 power module at 25/50/75/100%). Derived: the measured curve's shape moved to the datasheet's peak efficiency (AEC method), a typical curve, not a measurement. IST7-T: no figure.

For the losses as heat and their cost at your load, see the guide to UPS efficiency and ECO mode and the efficiency page.

Questions

Questions people ask

Is the EU Code of Conduct on UPS mandatory?

No. It is a voluntary commitment run by the European Commission's Joint Research Centre (JRC): a signatory commits to its minimum efficiencies and reports the data of its UPS. A specification can still ask for the Code's values as a requirement.

At which loads is the efficiency measured?

At 25, 50, 75 and 100% of the rated power, with the methods of EN 62040-3, in normal mode. The Code also asks for information on behaviour and efficiency in higher-efficiency modes such as ECO.

How do I compare an AEC UPS with the Code's thresholds?

Take your range's row in the table and the values for the UPS's power band and class in the Code's tables published by the JRC. Measured curves are AEC data; derived curves are typical curves, to confirm with AEC for a specification.

Talk to an AEC engineer

Tell us the load, the supply and the backup time you need: we answer with the model and the batteries that fit.