UPS efficiency: what each point is worth
Efficiency is the share of the input power that reaches the load; the rest is heat. AEC ranges reach 93 % to 98.1 % in double conversion at their best point, and up to 99.2 % in ECO mode; the ladder below compares them at your load.
Your load
What a point of efficiency is worth.
Peak efficiency by range, from the EMEA 2026 catalogue, and the energy saved in a year of continuous running at your load.
Semiconductors
Three-level inverters
Three-level inverters split each switching step in two, lowering losses and harmonic content: IST9, IST7 10–40, IST7 60–200 and IST6-120 use them.
Unity power factor (kVA = kW) on most ranges means the full rating is usable by modern IT loads.
From the catalogue
How efficient is each AEC range?
The peak AC/AC efficiency printed in the AEC UPS Catalogue EMEA 2026 for each range, in double conversion and, where the catalogue gives it, in ECO mode. Efficiency is highest near the load the UPS is designed for and falls at light load, so compare ranges at your own load in the ladder above.
| Range | Power | Double conversion, up to | ECO mode, up to |
|---|---|---|---|
| IST8 | 1–3 kVA | 93% (3 kVA) | — |
| IST9 | 10–40 kVA | 96% | 99% |
| IST7 10–40 | 10–40 kVA | 96% | 99% |
| IST7 60–200 | 60–200 kVA | 96.5% | 99% |
| IST6-120 | 30–120 kVA | 97% | 99% |
| IST6 200–500 | 200–500 kVA | 98.1% | ECO and W-ECO modes |
| IST6 400–1200 | 400–1200 kVA | 98.1% (PLUS modules) | 99.2% |
| CPSS 10–200 | 10–200 kVA | 96% | — |
How much does one point of efficiency save?
The losses of a UPS are the load times (1 ÷ efficiency − 1). At a steady 100 kW load, running all year (8,760 hours):
| Efficiency | Losses | Energy lost per year |
|---|---|---|
| 95% | 5.3 kW | 46,100 kWh |
| 96% | 4.2 kW | 36,500 kWh |
| 97% | 3.1 kW | 27,100 kWh |
| 98.1% | 1.9 kW | 17,000 kWh |
| 99% (ECO) | 1.0 kW | 8,850 kWh |
Every kilowatt lost is also heat the room's cooling has to remove, so the saving counts twice. In ECO mode the load runs on the bypass line and the inverter takes over when the mains leaves its tolerance: the losses fall, but the load sees the mains as it is. Double conversion stays the default for sensitive IT loads; the guide UPS efficiency and ECO mode explains when ECO pays.
Standards
How efficiency is measured
EN 62040-3 sets the method: the efficiency is measured at 25, 50, 75 and 100% of the rated power, in normal mode. The same four load points are the ones the EU Code of Conduct on UPS uses for its minimum efficiencies, by performance class (VFI, VI, VFD) and power band.
A datasheet figure without its load and mode says little: a UPS that reaches its peak at 50% may lose a point or more at 25%, where many redundant systems run. The range pages give each AEC curve point by point, with its source: measured where AEC has the table, derived from the datasheet figure elsewhere.