IST7 60–200 · Three-phase UPS
IST7-160 Three-phase online UPS 160 kVA, 400 V
The IST7-160 is a 160 kVA / 160 kW three-phase online UPS with two power units in a 600 × 1000 × 1600 mm cabinet, upgradable to 200 kVA. For data centres and large buildings with 120 to 160 kW of load today and room to reach 200 kW on the same unit.
Quick answers
IST7-160: quick answers
- What it is
- The IST7-160 is a 160 kVA / 160 kW three-phase online UPS with two power units in a 600 × 1000 × 1600 mm cabinet, upgradable to 200 kVA.
- Who it is for
- For data centres and large buildings with 120 to 160 kW of load today and room to reach 200 kW on the same unit.
- Supply and configuration
- 3 phases + N + PE · 220 / 230 / 240 V L-N · 380 / 400 / 415 V L-L
- Battery and backup
- ±216 V
- Size and weight
- 600 × 1000 × 1600 mm · 294 kg
- Ordering code
- IST7-160
IST7 60–200
What sets apart the IST7-160
At 160 kVA the IST7 changes cabinet: 600 mm wide, 1600 mm high, 294 kg, with two power units instead of one, cable entry from the top and the cabinet bolted to the floor. The charger doubles to 60 A. Like the IST7-80, it is built to grow: the capacity is raised to 200 kVA from the display, in the same footprint.
On battery it draws 386 A nominal and 496 A maximum, on 95 mm² cables (PE 70 mm²). The catalogue's own example code is for this model: IST7-160-64X100, the UPS with a BB8 holding 64 × 12 V 100 Ah, 294 kg plus 2,215 kg.
- Against the IST7-120 (one size down): Rated power 160 kVA / 160 kW against 120 kVA / 120 kW; Max. charge current 60 A against 30 A; Dimensions W × D × H 600 × 1000 × 1600 mm against 400 × 960 × 1193 mm; Weight 294 kg against 167 kg.
- Against the IST7-200 (one size up): Rated power 160 kVA / 160 kW against 200 kVA / 200 kW; Weight 294 kg against 296 kg.
Planning data
IST7-160: currents, breakers, cables, batteries
The rows and columns of the EMEA 2026 catalogue's and AEC manuals' tables that concern the IST7-160.
Front, rear and footprint
| Model | W × D × H (mm) | Weight |
|---|---|---|
| IST7-160 | 600 × 1000 × 1600 | 294 kg |
BB5 to BB8, matched to every IST7
| UPS | IST7-160 |
|---|---|
| BB5 | — |
| BB6 | — |
| BB7 | 30–36 × 80 / 100 Ah |
| BB8 | 60 / 64 × 80 / 100 Ah |
| 2 × BB8 | 120 / 128 × 80 / 100 Ah |
Battery connection by UPS model
| UPS | IST7-160 |
|---|---|
| I nom. (A) | 386 |
| I max. (A) | 496 |
| +/N/− mm² | 95 |
| PE mm² | 70 |
Installation
Installing the IST7-160: space, heat, cables
Each figure with its source. Heat is the power lost at the peak efficiency stated.
| Item | Figure | Source |
|---|---|---|
| Clearances | front 800 mm, rear 800 mm, left 800 mm, right 800 mm, top 800 mm | AEC IST7 60–200 user manual p.35 §3.2.3 |
| Cable entry | Bottom, through the base | AEC IST7 60–200 user manual |
| Heat at full load | 5.80 kW at 160 kW load, 96.5 % efficiency | AEC IST7 60–200 user manual p.87 §A; output PF 1 (EMEA 2026 catalogue) |
| Operating temperature | −5 to 40 °C, best 20–30 °C | AEC IST7 60–200 user manual p.34–35 §3.2.2 |
| Switches and terminals | Mains, bypass, output and maintenance bypass switches behind the lockable front door; terminals behind the front and rear wiring covers. | AEC IST7 60–200 user manual p.13 Fig. 2-2/2-3 (handle on the left edge) |
| Door | One leaf, hinged on the right | AEC IST7 60–200 user manual p.13 Fig. 2-2/2-3 (handle on the left edge) |
Size and floor
How big it is
600 × 1000 × 1600 mm · 294 kg.
Floor load = weight ÷ footprint (294 kg).
Efficiency
How efficient is the AEC IST7-160 at your load?
IST7-160, 160 kW at its rating, online, double conversion (typical curve, AEC's method). Heat to remove on this curve: 25%: 1.71 kW (η 95.9%) · 50%: 2.90 kW (η 96.5%) · 75%: 4.74 kW (η 96.2%) · 100%: 6.84 kW (η 95.9%). At 50% load, 24/7, it loses about 25,418 kWh a year.
How the curve is drawn and where each figure comes from: the IST7 60–200 range page.
- Load
- —
- Lost as heat
- —
- Energy lost in a year, 24/7
- —
- Its cost in a year at € per kWh
- —
- The catalogue's examples use €0.20 per kWh.
Where each figure comes from
| Mode | Efficiency | Kind | Models | Source |
|---|---|---|---|---|
| Online, double conversion | 25%: 95.9% · 50%: 96.5% · 75%: 96.2% · 100%: 95.9% | Typical curve, derived from the datasheet efficiency of 96.5% (AEC method) | all | AEC datasheet: AC/AC efficiency of the IST6-PM100 100 kW power module (the curve's shape) |
| ECO | 99% | Datasheet figure, load not stated | all |
EMEA 2026 catalogue figures: Online, double conversion up to 96.5% · ECO up to 99%.
Drag to turnIn 3D
Look around the IST7-160
The turntable shows the IST7-200; the full 3D view opens on the IST7-160.
Technical data
Technical data IST7-160
Only this model's values, from the EMEA 2026 catalogue table.
| General | |
|---|---|
| Rated power (kVA / kW) | 160 |
| Capacity upgrade | to 200 |
| Input | |
| Connection | 3 phases + N + PE |
| Rated voltage | 220 / 230 / 240 V phase (380 / 400 / 415 V line) |
| Voltage range | 187–280 V phase at full power · 80–186 V with linear derating |
| Frequency · power factor · THDi | 40–70 Hz · ≥ 0.99 · ≤ 3% at full load |
| Bypass synchronisation range | 50 / 60 Hz ± 6 Hz |
| Battery | |
| Nominal DC voltage (default) | ±216 V |
| String length | 28–48 × 12 V blocks, set on site · VRLA or lithium (BMS card) |
| Max. charge current | 60 A |
| Output | |
| Voltage · frequency | 220 / 230 / 240 V phase · 50 / 60 Hz (± 0.1 Hz on battery) |
| Power factor · THDv | 1 (settable 0.9) · ≤ 1% linear, ≤ 4% non-linear load |
| Transient · unbalance · phase error | ≤ 5% for 0–100–0% step · 100% unbalanced load · ≤ 1° |
| Transfer time inverter ↔ bypass | < 1 ms synchronised · < 15 ms not synchronised |
| Inverter overload | ≤ 105% continuous · ≤ 110% 60 min · ≤ 125% 10 min · ≤ 150% 1 min (IST7-120: > 125% immediate) |
| Bypass overload | ≤ 130% continuous · ≤ 150% 5 min · ≤ 200% 1 s · ≤ 300% 100 ms |
| System | |
| Efficiency AC/AC | up to 96.5% double conversion · 99% ECO mode |
| Parallel | Up to 8 units, capacity or N+X · BSC dual-bus synchronisation |
| Communication | RS485 · Modbus RTU · RS232 · 4 IN / 3 OUT dry contacts · EPO · SNMP slot · expansion slot |
| Display | Colour touch screen, 5 status LEDs, ambient light bar, 10,000 events and 10,000 user-log entries |
| Environment | −5 … 40 °C · 0–95% RH · IP20 · < 65 dB at 1 m · forced-air cooling |
| Cable entry | bottom (all models) |
| EMC | IEC 62040-2:2016 · category C3 (not for residential use without additional measures) |
| Dimensions W × D × H | 600 × 1000 × 1600 mm |
| Weight | 294 kg |
| Item | IST7-160 |
|---|---|
| Rated power (kVA / kW) | 160 |
| Capacity upgrade | to 200 |
| Power units | 2 |
| Nominal DC voltage (default) | ±216 V |
| Max. charge current | 60 A |
| W × D × H (mm) | 600 × 1000 × 1600 |
| Weight | 294 kg |
Specifications are subject to change without notice.
More technical detailsordering codes
Ordering codes
Ordering codes IST7-160
| Code | Description |
|---|---|
| IST7-160 | 160 kVA, upgradable to 200 kVA |
| PAR-IST7-60/200 | Parallel kit |
| IST7-[kVA]-[n]X[Ah] | UPS with battery cabinet, n × 12 V [Ah] (e.g. IST7-160-64X100 = IST7-160 + BB8 with 64 × 12 V 100 Ah) |
Questions
Questions about the IST7-160
How heavy is an IST7-160 with its batteries?
The catalogue example IST7-160-64X100 weighs 294 kg for the UPS plus 2,215 kg for a BB8 with 64 × 12 V 100 Ah. A BB8 so loaded puts about 1,978 kg/m² on the floor: check the slab.
Which battery cabinets suit the IST7-160?
BB7 with 30–36 × 80 / 100 Ah, BB8 with 60 / 64 × 80 / 100 Ah, or two BB8 with 120 / 128 × 80 / 100 Ah. BB5 and BB6 are not listed for it.
How long does a 160 kVA UPS like the IST7-160 run?
2 to 26 minutes at full load (160 kW), and 5 to 60 minutes at half load, with the AEC battery options in the table: the battery chosen sets the figure. With 30 × 12 V 80 Ah (IST7-160-30X80): 2 minutes at 100% and 5 at 50%. For other loads and batteries use the backup-time tool.
How big is the AEC IST7-160 and how much does it weigh?
The AEC IST7-160 measures 600 × 1000 × 1600 mm; weight: 294 kg (size from AEC's CAD drawing, weight from the EMEA 2026 catalogue).
What is the ordering code of the AEC IST7-160?
In the EMEA 2026 catalogue the AEC IST7-160 is listed as IST7-160; AEC gives the full code, batteries included, from the load and the backup time.
Talk to an AEC engineer
Tell us the load, the supply and the backup time you need for the AEC IST7-160: we answer with the model and the batteries that fit. AEC International sells through distributors in about 80 countries and an agency in every Italian region: ask AEC which one serves your area.